Multi-zone Heat Pump Condensing Units

S2HA & T2HA REFRIGERANT PIPING INSTALLATION SECTION

The use of the superheat method is highly 

recommended for field charging or checking 

the existing refrigerant charge in a system. 

Because each installation is different in terms 

of indoor air flow, refrigerant line length, etc.., 

the factory charge may not be correct for 

every application. To assure the best perfor-

mance from the air-conditioner, the refrigerant 

charge should be checked and adjusted, if 

need be, on each installation. 

For proper superheat readings, a standard 

low-side refrigerant gauge and an accurate 

thermometer  are  needed. A  mercury  or 

stem-type  thermometer  is  not  adequate 

for suction-line temperatures. We recom-

mend electric thermocouple thermometers 

(available  at  most  refrigeration  wholesal-

ers);  however  an  accurate  remote-bulb 

thermometer  can  be  used.  When  mea-

suring  the  line  temperature,  be  sure  the 

thermometer  is  well  insulated  to  assure 

accurate measurements. The chart below 

gives superheat values at various outdoor 

temperatures. Allow at least 5 minutes run-

ning time between charge adjustments for 

the unit to stabilize.

The S & T series (S2HA, T2HA, T3HA & 

T4HA) has manifold access points on each 

of the service valves for the high and low 

pressures  in  cooling  mode.  There  is  an 

additional “common suction” access point 

above each service valve set to provide low 

pressure access in the heating mode as both 

service valves are at high side pressure.

FIELD CHARGING

S2HA & T2HA REFRIGERANT CHARGE TABLE

 

Circuit 

Capacity Btuh

Evaporator 

Pairing

Line 

Chg/ft

Line 

Length

Line 

Adjust

Factory 

Charge

Total 

Charge

9000

WLHA09

CAHB12

0.25 oz

10 ft  

25 ft     

50 ft

3 oz         

6 oz        

13 oz

42

45 oz       

48 oz       

55 oz

12000

WLHA12

CAHB12

0.25 oz

10 ft           

25 ft 

 50 ft

3 oz         

6 oz        

13 oz

46

49 oz      

52 oz      

59 oz

18000

WLHA24

CAHB24

0.56 oz

10 ft           

25 ft 

 50 ft **

6 oz       

14 oz      

28 oz **

80

86 oz      

94 oz      

108 oz

24000

WLHA24

CAHB24

0.56 oz

10 ft           

25 ft 

 50 ft

6 oz       

14 oz      

28 oz

80

86 oz      

94 oz      

108 oz

** Any 18,000 Btuh circuit with more than 57 feet of tubing (> 112 oz of total refrigerant charge) requires a 25W 

wrap around Crank Case Heater.  

IMPORTANT NOTES:

1. To find the charge adjustment and system charge for any evaporator and 

tubing length:

Line Adjustment = (Line Chg/Ft) x Line Length

System Total = Factory Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

3. Use R22 refrigerant.

Summary of Contents for S2HA

Page 1: ...1 1 04 07 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company S2HA Multi Zone S2HA T2HA HE...

Page 2: ......

Page 3: ...the electric supply to the unit The EMI America Series multi zone heat pump condenser must be con nected only to a properly grounded electrical supply Do not fail to prop erly ground this unit Turn of...

Page 4: ...pad or foundation Refrigerant piping Disconnect switch SITE PREPARATION Place the unit on a at concrete surface or pad if on the ground Roof mounting should use a build up platform Piping is through...

Page 5: ...allows for permanent mounting through the feet This is highly recommended due to the vertical design of the unit S2HA UNIT MOUNTING SECTION 5 Insert lag bolts through the holes in the bottom of the un...

Page 6: ...within 3 feet of the unit 6 From the disconnect box run the power through the 7 8 hole on the side of the unit and into the electrical box and an chor with the strain relief tting 7 Run wires to the h...

Page 7: ...east 18 awg 10 To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel 11 Tighten a...

Page 8: ...irements 3 Use only HACR type breakers or time delay fuses Select the wire size accord ing to the ampacity rating Removethe four screws on the front panel 4 To access wiring diagram a Remove the four...

Page 9: ...wires to the High Volt pigtail in the control box and attach L1 and L2 connections Also run green wire to ground lug T2HA INSTALLATION INSTRUCTIONS 8 Check wiring diagram for the required number of lo...

Page 10: ...Wholesaler or Distributor how ever the trap should be shallow as the 4 elbow con guration Each elbow is approximately 2 equivalent feet One P trap is equal to approximately 8 equivalent feet P TRAP I...

Page 11: ...ing and insert into ttings 7 Attach manifold set 3 The use of a shield is recommend one can be made from some scrap metal to protect the paint 4 Braze tubing into ttings S2C Shown S2HA T2HA REFRIGERAN...

Page 12: ...he Refrig erant Charge Tables for proper weight charge and to the supplied Field Charging Charts for proper system pressures and temperature at different outdoor condi tions Superheat should be used f...

Page 13: ...ning time between charge adjustments for the unit to stabilize The S T series S2HA T2HA T3HA T4HA has manifold access points on each of the service valves for the high and low pressures in cooling mo...

Page 14: ...densing Units MULTI ZONE HEAT PUMP FIELD CHARGING Cooling Cycle 9 000 Btuh Circuit with EMI s WLHA09 or CAHB12 Note Minimum compressor superheat 5 F Cooling Cycle 12 000 Btuh Circuit with EMI s WLHA12...

Page 15: ...ensing Units Cooling Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor superheat 5 F Cooling Cycle 24 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor s...

Page 16: ...nviromaster com 16 Multi zone Heat Pump Condensing Units Heat Cycle 9 000 Btuh Circuit with EMI WLHA09 or CAHB12 Heat Cycle 12 000 Btuh Circuit with EMI WLHA12 or CAHB12 MULTI ZONE HEAT PUMP FIELD CHA...

Page 17: ...romaster com 17 Multi zone Heat Pump Condensing Units MULTI ZONE HEAT PUMP FIELD CHARGING Heat Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Heat Cycle 24 000 Btuh Circuit with EMI s WLHA24 or...

Page 18: ...ines occur on the 12 F superheat line 5 Add charge to obtain 12 F superheat Instructions 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gauge 2 M...

Page 19: ...ci c to the unit being installed or call the factory Anti short cycle protection should be used on systems that use a conventional thermostat Evaporator Entering Air WB Evaporator Leaving Air DB Evapo...

Page 20: ...located in the indoor unit provides 24V low Volt control power to the condenser outdoor unit This can be mea sured across low Volt terminals R and C Heat pump condensers utilize a reversing valve to p...

Page 21: ...ibed in the manual pertaining to the indoor section The S Tseries S2HA T2HA T3HA T4HA will cease compressor operation at 35 F outdoor temperature If in heating mode the electric heat will take over wh...

Page 22: ...230 60 1 1 8 0 33 4 3 27 4 3 27 10 4 11 5 15 9200 208 230 60 1 1 8 0 33 3 4 23 4 3 27 9 5 10 6 15 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh ex Model 9200 consists of one 9 000 Btuh compressor...

Page 23: ...600 13 0 80 12 2 16 000 3 3 2200 WLHA12 WLHA12 22 600 13 0 72 11 9 20 000 3 3 9200 WLHA09 WLHA12 20 600 13 0 76 12 0 18 000 3 3 S2HA CAHB SYSTEM PERFORMANCE DATA MODEL COOLING HEATING S2HA Outdoor Ind...

Page 24: ...Lift Liquid Line OD Suction Line OD 9 000 100 35 1 4 1 2 12 000 100 35 1 4 1 2 18 000 100 35 3 8 5 8 24 000 100 35 3 8 3 4 T2HA T3HA AND T4HA 208 230V 60 HERTZ 1 PHASE CAPACITY FAN MTR COMPRESSOR TOTA...

Page 25: ...5 12 1 40500 3 2 CAHB T2HA SYSTEM PERFORMANCE DATA Model Cooling Heating T2HA Outdoor Condenser Indoor Air Handler Btuh SEER SHR EER Btuh COP 8800 CAHB24 CAHB24 36000 13 0 75 12 6 26400 3 1 8400 CAHB2...

Reviews: