DESCRIPTION
EMI offers the finest high capacity multiple zone outdoor units
in the ductless split market, the MC2/MH2 High Capacity
Condensing Unit. The MC2/MH2 allows the installation of two
circuits from a single outside location when space or aesthetic
requirements limit the use of locations. Valves are internal for
tamper protection and each zone is independent so no mixing
of refrigerant is required.
When specifying heat pump(s), it is recommended that the
matching evaporator(s) be equipped with electric heat. The
MH2 will operate down to 35°F outdoor temperature, at which
point it will initiate change over to electric heat and shut down
the condenser. All 9,000, 12,000, and 15,000 Btuh units are
equipped with the Duratec Performance Package which
include a large capacity suction accumulator with surge baffles
and enhanced oil management, a factory installed solid core
filter drier and loss of refrigerant charge protection.
NOTE:
The crankcase heater is installed with 9-15K
Btu heat pumps and when the low ambient control
option is selected.
MC2/MH2 DUAL-ZONE
High Efficiency Condensing Unit
Limited Range Heat Pump
REFRIGERANT CHARGE TABLE FOR MC2/MH2
For installation of the indoor unit and start-up of the system,
please refer to the
appropriate installation manual for your
indoor product to complete the installation.
CONDENSER
CAPACITY
EVAPORATOR
PAIRING
LINE
CHG/FT
LINE
LENGTH
LINE
ADJUST
FACTORY CHARGE
SYSTEM TOTAL
MC2
MH2
MC2
MH2
09
CHP 12
FHP 12
WHP 12
TBH 12
CAH 12
CNR 12
.25 OZ.
10
25
50
3 OZ.
6 OZ.
13 OZ.
26.5 OZ.
44 OZ.
29 OZ.
32 OZ.
39 OZ.
47 OZ.
50 OZ.
57 OZ.
12
CHP 12
FHP 12
WHP 12
TBH 12
CAH 12
CNR 12
.25 OZ.
10
25
50
3 OZ.
6 OZ.
13 OZ.
29.5 OZ.
42 OZ.
32 OZ.
35 OZ.
42 OZ.
45 OZ.
48 OZ.
55 OZ.
15
CHP 15
FHP 15
WHP 18
CAH 24
.25 OZ.
10
25
50
3 OZ.
6 OZ.
13 OZ.
43.5 OZ.
52 OZ.
46.5 OZ.
49.5 OZ.
56.5 OZ.
55 OZ.
58 OZ.
65 OZ.
IMPORTANT NOTES:
1. To find the charge adjustment and system charge for any evaporator and tubing length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Line Adjustment
2. Round to the nearest ounce and allow for gauges and hoses.