background image

www.enviromaster.com

9

CAC Cassette Evaporator

Fresh Air  

Knockout

 

Branch Duct Knockout

 

Small Unit

Medium & 

Large Units

Notes:

 The number of knock-outs var-

ies depending on unit size.

• Branch duct knock-outs are 5¼” round 

•  Fresh  air  knock-outs  are  1¼”  x  2½” 

rectangular on 12k, and 3” square on 

24-36k

Recommendation:

 

No  more  then 

10’ of branch duct or fresh air duct 

should be installed.

CONDENSATE PIPING

The  unit  can  now  be  piped  up  in  accor-

dance  with  good  refrigeration  and/or 

plumbing practices.

The Cassette is supplied with a 1/2”  

I.D.  fl exible  PVC  hose  for  connection  to 

copper  or  plastic  drain  pipework.  When 

installing the Cassette the following points 

should be remembered:
1.  Maximum pump lift is 36”.
2.  The  highest  point  in  the  condensate 

pipework  should  be  as  close  to  the 

unit as possible. This prevents a large 

volume of water draining back into the 

unit when it is switched off. 

NOTE:

 There is a check valve at the 

pump  discharge  to  prevent  water 

from draining back into the unit. This 

piping technique will minimize any is-

sues should the check valve become 

stuck open from airborne debris.

Correct

Incorrect

Condensate Drain Connection

3.  Condensate  pipework  should  slope 

downwards  in  the  direction  of  water 

fl ow  with  a  minimum  gradient  of  (1” 

per 10’). There must not be any uphill 

gradients other than in the fi rst 36” of 

pipework from the Cassette.

4. When multiple Cassettes are connect-

ed  to  a  common  condensate  drain, 

ensure  the  drain  is  large  enough  to 

handle  the  volume  of  condensate 

from several Cassettes. It is also rec-

ommended to have an air vent in the 

condensate pipe work to prevent any 

air locks.

Duct collars:

 Branch duct and fresh air 

duct  collars  can  be  attached  to  the  Cas-

sette chassis by following the steps below:

1. Locating the knock-out holes.

Summary of Contents for CAC

Page 1: ...6 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company CAC 9 12 Model Shown STRAIGHT COOL N...

Page 2: ...ricaSeries evaporator must be connected only to a properly grounded electrical supply Do not fail to properly ground this unit Turn off the electrical supply before servicing the EMI AmericaSeries eva...

Page 3: ...ire resistant thermal and acoustic foam insulation and light grey high impact ABS fascia A Styro foam drain pan with a tough re retardant thermoplastic liner Air Systems Fans are backward curved impel...

Page 4: ...blanked off DO NOT throw the two polystyrene blanking off pieces out with packaging Electromechanical Operation Stan dard An optional thermostat can be ob tained through EMI or your local distributor...

Page 5: ...e positioned in the fascia discharge slots to direct the air to the ducts Blanking Off Pieces Small Unit Shown Shown The large units have three hinged grills and three lters Medium Unit Shown Large Un...

Page 6: ...the CAC Di mensions section in the back of this IOM for cabinet sizing Small Cabinet Dimension A 12 min Medium Cabinet DimensionA 11 min Large Cabinet Dimension A 13 min Dimension A 1 minimum space a...

Page 7: ...iling will have to be cut to the following sizes Small cabinet 23 x 23 Medium cabinet 33 x 33 Large cabinet 46 x 33 NOTE Make sure the ceiling grid is supported separately from the Cas sette The ceili...

Page 8: ...not pro trude more than 2 below the mounting bracket 2 MAX NOTE If the ceiling is not level or even it is important that the Cas sette is installed level to ensure cor rect pump operation and to main...

Page 9: ...to the unit as possible This prevents a large volume of water draining back into the unit when it is switched off NOTE There is a check valve at the pump discharge to prevent water from draining back...

Page 10: ...pes should be insulated right up to the Cassette chassis The CAC is equipped with a Flo Rater Piston Expansion device Connections are sweat type The suction line large must be insulated the entire len...

Page 11: ...the bolts c Screw the mounting bolt with washer into the chassis leav ing approximately 1 to hang the fascia 4 On 18 36k units connect the vane motor plug by plugging it into the socket con nection on...

Page 12: ...particularly in low Voltage wir ing The correct cable size must be used to ensure a Voltage drop of less than 1 Volt in the control wiring Once the refrigeration pipe work is complete the electrical...

Page 13: ...onnector location terminal block L1 L2 Low Volt Interconnect Wiring Refer to the wiring diagram to connect the low Volt wiring to the appropriate terminals The wiring diagram located on the inside of...

Page 14: ...f via the toggle switch on the side of the electri cal box Toggle Switch NOTE Apply power to the Condens ing Unit s crankcase heater for 24 hours before start up to boil off any liquid that may be pre...

Page 15: ...re 4 ly with condensate pump energized If water does not check the pipe slope or see if there are any pipe restrictions 8 Ensure that all covers panels and l ters are in place and discharge louvers ar...

Page 16: ...nds of tubing and insert into ttings 2 Protect the valves by wrapping with a wet rag heat sink before brazing 3 We recommend the use of a shield can be made from some scrap metal to protect the paint...

Page 17: ...36 56 oz 90 oz R 22 8 Charge to proper weight charge based on your feet of interconnect see below NOTE Charging should be done with a dial a charge or weighed in with a scale TOP DISCHARGE REFRIGERANT...

Page 18: ...at has been satis ed the purge feature al lows the indoor fan to remain on for an additional 60 seconds This increases ef ciency by pulling the remaining energy from the unit Cooling Operation The ele...

Page 19: ...it Performance Data Date Model Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air...

Page 20: ...r by sliding under retainer clips 5 Or use a garden hose Remove the grille and lter and hose off Let lter s and grille s dry before replacing Turn the POWER OFF to the unit be fore servicing or cleani...

Page 21: ...tdoor unit are to be independently connected to the electri cal service panel and protected by sepa rate time delay fuse or HACR breakers See the unit name plate for the correct breaker type and size...

Page 22: ...r condenser from short cycling After the thermostat is satis ed there will be a three minute delay before the condenser is allowed to re start Electric Heat Units with electric heat utilize a control...

Page 23: ...sate pump with a high level safety switch If the condensate reaches a critical level or if power is lost to the indoor unit the safety cir cuit will open and low Volt power to the condenser terminal Y...

Page 24: ...program all designs and speci cations are subject to change without notice INDOOR SOUND LEVELS dBa Model High Speed Medium Speed Low Speed 09 12 41 39 39 18 24 44 42 39 30 36 51 49 44 DISCHARGE AIR VO...

Page 25: ...rator C D E F Control Box Small Cabinet CAC 9 000 12 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 2 1 x 2 C Condensate Discharge 1 D Suctio...

Page 26: ...0 24 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 3 3 x 3 C Condensate Discharge 1 D Suction 1 E Liquid 1 F Condensate Pump Access 1 Contro...

Page 27: ...36 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 3 3 x 3 C Condensate Discharge 1 D Suction 1 E Liquid 1 F Condensate Pump Access 1 B Contr...

Page 28: ...74 22 7 197 28 3 30 S1C Side Discharge CAC CASSETTE SYSTEM MATCHES CAC CAC ELECTRICAL SPECIFICATIONS NOTE Due to EMI s ongoing product development program all designs and speci cations are subject to...

Page 29: ...94 40 600 13 0 82 11 7 R22 CACA12 T3CA999 27 000 13 0 87 11 8 R22 CACA12 T3CA222 36 000 13 0 76 11 8 R22 CACA12 CACA24 T3CA928 39 000 13 0 80 11 7 R22 CACA12 CACA24 T3CA924 43 600 13 0 79 11 7 R22 CAC...

Page 30: ...by others Failure to start due to Voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a conseq...

Page 31: ...EFFICIENCY PRODUCT LINE EVAPORATORS CONDENSERS S1C S1H Single Zone Side Discharge S2C Dual Zone Side Discharge T2C T3C T4C 2 3 4 Zone Top Discharge WLC WLH High Wall Evaporator CAC Cassette Evaporato...

Page 32: ......

Reviews: