Maintenance
9
Maintenance schedule
9.3
ELDRO-EdEx-Montageanleitung-607338-EN.docx
67
/ 75
9.3
Maintenance schedule
Table 25:
Maintenance log for EdEx thrusters
EdEx type
Serial number
System ID
Classification
according to section
3.1 (table 1)
Low
requirements
Standard
Higher
requirements
Test object
Test interval according to classification
Test
performed
Test
passed
Evaluation /
measured values
Cleaning
as required
as required
as required
Test run
Every six months
Visual checks
Leaks
Annually
Annually
Every six months
Bolt connections
Annually
Annually
Every six months
Terminal box cover
Annually
Annually
Every six months
Cable connections tight
Annually
Annually
Every six months
External damage
Annually
Annually
Every six months
Functional inspection
Motor functions, running
noises
Annually
Annually
max. lifting path
Annually
Annually
Terminal box and cable
infeed leak tightness
Annually
Annually
Position indicator, signals,
adjustment
Annually
Annually
Extended test
Actuating force
measurement
Every 2-3 years
Reset force measurement
Every 2-3 years
Power consumption
measurement
Every 2-3 years
Insulation resistance
measurement
Every 2-3 years
Coil resistance
measurement
Every 2-3 years
Summary of Contents for ELDRO EdEx 125/160