TYPE 829A-832

RELAY

For Use With Low Voltage Thermostats

INSTALLATION INSTRUCTIONS

Operator:  Save these instructions for future use!

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO.   63123
(314) 577-1300, Fax (314) 577-1517

9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625

R

DESCRIPTION

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

Type 829A-832 Relay has double-pole, single-throw
switch action.

This Relay permits the use of a sensitive low voltage
thermostat to control a line voltage heating or cooling
load. It is especially suitable for use on hot water heating
systems, and may be used for boilers with tankless
domestic coil as well as for boilers without a domestic
coil.

DOTTED LINES

INDICATE FIELD

WIRING

Fig. 1

TO MILLIVOLT VALVE OR

LOW VOLTAGE LOAD

RELAY
COIL

HOT

LINE

N

PRECAUTIONS

To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.

If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor, electrician, or someone famil-
iar with basic electricity and wiring.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical
codes and ordinances.

This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.

CAUTION

Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.

WARNING

ELECTRICAL DATA
Switch Action:
 Double-Pole, Single-Throw, normally open
Input Voltage:  Terminals (1 & 2) 120V.A.C., 60Hz
Room Thermostat:

Set adjustable heat anticipator at 0.3 Amps. For fixed
anticipation thermostats, use 0.25 to 0.35 Amp. heater.

Rating:

Terminals X-X millivolt

1 volt D.C. max. 1 amp D.C. max. or
30V.A.C. max. @ 1 amp max.
Terminals (3 & 4)

Motor: 120V.A.C.

8F.L.A.

48L.R.A.

240V.A.C.

4F.L.A.

24L.R.A.

SPECIFICATIONS

PRINCIPLE OF OPERATION

The 829A-832 relay is provided with a self-contained
transformer with a low voltage secondary output for
energizing the relay coil.

Line voltage lines should be connected to terminals
marked “1 & 2” for power to reach the transformer.

Closing the thermostat circuit energizes the relay coil
which in turn closes the circuit between terminals 1 and
3 and 1 and 4, also closing millivolt or low voltage circuit
between X and X.

Opening the thermostat circuit de-energizes the relay
coil, breaking the circuit between terminals 1 and 3 and

1 and 4,  also breaking millivolt or low voltage circuit
between X and X.

Summary of Contents for White-Rodgers 829A-832

Page 1: ...tor electrician or someone famil iar with basic electricity and wiring Do not exceed the specification ratings All wiring must conform to local and national electrical codes and ordinances This control is a precision instrument and should be handled carefully Rough handling or distorting compo nents could cause the control to malfunction CAUTION Do not use on circuits exceeding specified voltages ...

Page 2: ...irculator stops until the circulator control recloses When thermostat is satisfied both burner and circulator stop DIAGRAM FOR BOILER WITHOUT DOMESTIC COIL When the thermostat calls for heat the burner starts The circulator also starts if boiler temperature is above setting of circulator control If excessive boiler temperature causes high limit to open the circulator continues to run but the burne...

Page 3: ...rmateur le circuit à la tension du réseau doit être raccordé sur les bornes 1 et 2 La fermeture du circuit du thermostat met sous tension la bobine du relais ce qui ferme le circuit entre la borne 1 et les bornes 3 et 4 ainsi que le circuit en millivolts ou à basse tension entre les bornes X et X L ouverture du circuit du thermostat met la bobine du relais hors tension ce qui coupe les circuits en...

Page 4: ...estique est maintenue à la température désirée Lorsque le thermostat fait un appel de chaleur le brûleur est mis en marche Le circulateur est aussi mis en marche si les bornes R et W de la commande du circulateur avec limiteur à maximum sont fermées Si la température de la chaudière est trop élevée et ouvre le circuit du limiteur à maximum alors le circulateur continue de fonctionner mais le brûle...

Reviews: