Emerson White-Rodgers 829A-832 Installation Instructions Download Page 2

2

W

B

R

X

X

T

1

4

3

T

X

X

2

2

WIRING

All wiring should be done in accordance with local and national electrical codes and ordinances.

If the manufacturer of the heating or cooling equipment
has recommended a wiring diagram, follow his
instructions. If none are available, the diagram shown on
this page will suffice for general applications. For hot
water heating, refer to the typical diagrams presented
below.

DIAGRAM FOR BOILER WITH TANKLESS
DOMESTIC COIL

The R-B contacts of the low limit-circulator control maintain
domestic hot water at the desired temperature year-
round.

When the thermostat calls for heat, the burner starts. The
circulator also starts if the R-W contacts of the low limit-
circulator control are closed.

If excessive boiler temperature causes the high limit to
open, the circulator continues to run but the burner shuts
down until the high limit recloses.

If low boiler temperature causes the R-W contacts of the
low-limit circulator control to open, the burner stays on
but the circulator stops until the R-W contacts reclose.

When the thermostat is satisfied, the circulator stops.
The burner also shuts down if the R-B contacts of the low
limit-circulator control are open.

DIAGRAM FOR BOILER WITHOUT DOMESTIC COIL

When the thermostat calls for heat, the burner starts. The
circulator also starts if boiler temperature is above setting
of circulator control.

If excessive boiler temperature causes high limit to open,
the circulator continues to run but the burner shuts down
until the high limit recloses.

When low boiler temperature causes circulator control to
open, the burner stays on but the circulator stops until the
circulator control recloses. When thermostat is satisfied,
both burner and circulator stop.

DIAGRAM FOR BOILER WITHOUT DOMESTIC COIL

When the thermostat calls for heat, the burner starts. The
circulator also starts if boiler temperature is above setting
of circulator control.

If excessive boiler temperature causes high limit to open,
the circulator continues to run but the burner shuts down
until the high limit recloses.

When low boiler temperature causes circulator control to
open, the burner stays on but the circulator stops until the
circulator control recloses. When thermostat is satisfied,
both burner and circulator stop.

X

X

T

1

4

3

T

X

X

2

2

24 VAC

GAS VALVE

X

X

Fig. 3a & 4a Diagram for

Gas-Fired System

HIGH LIMIT

TRANS

.

Fig. 3

Fig. 2

T

1

4

– 2 –

3

T

X

X

LOAD #2

LOAD #1

LOW VOLTAGE

2-WIRE

THERMOSTAT

AUXILIARY TO LOW

OR MILLIVOLTAGE

(POWER PILE) LOAD

FOR 120V. LOADS:  

Connect this line to

neutral (grounded) side of 120V. line

or terminal #2 on relay.

FOR 240V. LOADS: 

Connect load to L2

(hot line of 120/240 3-wire line,

NOT connected to terminal #1).

terminal #2 MUST BE connected to

neutral (ground) line.

INTERNAL

WIRING

IGNITION

TRANS.

BURNER

MOTOR

CIRCULATOR

MOTOR

CIRCULATOR

CONTROL

HIGH
LIMIT

TO AUXILIARY LOAD

(IF USED)

THERMOSTAT

INTERNAL

WIRING

TYPE 668 OIL

BURNER CONTROL

(LINE VOLTAGE)

JUMPER

L1

LINE

N

THERMOSTAT

TO AUXILIARY LOAD

(IF USED)

HIGH
LIMIT

LOW LIMIT

CIRCULATOR

JUMPER

CIRCULATOR

MOTOR

BURNER

MOTOR

IGNITION

TRANS.

TYPE 668 OIL

BURNER CONTROL

(LINE VOLTAGE)

L1

LINE

N

INTERNAL

WIRING

Fig. 4

Fig. 5 Diagram for Millivolt Gas-Fired
System and line voltage circulator

T

1

4

3

T

X

X

2

2

TH

TH PG

PG

TO AUXILIARY LOAD

(IF USED)

CIRCULATOR

CONTROL

CIRCULATOR

MOTOR

L1

LINE

N

750 MV
POWER
GENERATOR

INTERNAL
WIRING

750 MV

GAS VALVE

HIGH LIMIT

THERMOSTAT

N

LINE

L1

MUST BE N.E.C.
CLASS 1
WIRING

Summary of Contents for White-Rodgers 829A-832

Page 1: ...tor electrician or someone famil iar with basic electricity and wiring Do not exceed the specification ratings All wiring must conform to local and national electrical codes and ordinances This control is a precision instrument and should be handled carefully Rough handling or distorting compo nents could cause the control to malfunction CAUTION Do not use on circuits exceeding specified voltages ...

Page 2: ...irculator stops until the circulator control recloses When thermostat is satisfied both burner and circulator stop DIAGRAM FOR BOILER WITHOUT DOMESTIC COIL When the thermostat calls for heat the burner starts The circulator also starts if boiler temperature is above setting of circulator control If excessive boiler temperature causes high limit to open the circulator continues to run but the burne...

Page 3: ...rmateur le circuit à la tension du réseau doit être raccordé sur les bornes 1 et 2 La fermeture du circuit du thermostat met sous tension la bobine du relais ce qui ferme le circuit entre la borne 1 et les bornes 3 et 4 ainsi que le circuit en millivolts ou à basse tension entre les bornes X et X L ouverture du circuit du thermostat met la bobine du relais hors tension ce qui coupe les circuits en...

Page 4: ...estique est maintenue à la température désirée Lorsque le thermostat fait un appel de chaleur le brûleur est mis en marche Le circulateur est aussi mis en marche si les bornes R et W de la commande du circulateur avec limiteur à maximum sont fermées Si la température de la chaudière est trop élevée et ouvre le circuit du limiteur à maximum alors le circulateur continue de fonctionner mais le brûle...

Reviews: