background image

9

TROUBLESHOOTING 

Reset Operation

If a voltage spike or static discharge blanks out the display 
or causes erratic thermostat operation, reset the thermostat 
by pressing the 

 and TIME buttons simultaneously. 

If the thermostat has power, has been reset and still does not 
function correctly contact your heating/cooling service person 
or place of purchase. 

Symptom

Possible Cause

Corrective Action

No Heat/No Cool/No Fan
(common problems)

1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or  
    panel loose or not properly installed.

Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety 
interlock or door switch.

No Heat

1. System Switch not set to Heat.

2. Loose connection to thermostat or 
    system
3. Heating System requires service or 
    thermostat requires replacement.

Set System Switch to Heat and raise setpoint above room 
temperature.
Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Heat and raise the 
setpoint above room temperature. Within a fi ve minutes 
the thermostat should make a soft slick sound. This sound 
usually indicates the thermostat is operating properly. If 
the thermostat does not click, try the reset operation listed 
above. If the thermostat does not click after being reset 
contact your heating and cooling service person or place 
of purchase for a replacement. If the thermostat clicks, 
contact the furnace manufacturer or a service person to 
verify the heating system is operating correctly.

No Cool

1. System Switch not set to Cool.

2. Loose connection to thermostat or 
    system.
3. Cooling System requires service or 
    thermostat requires replacement

Set System Switch to Cool and lower setpoint below room 
temperature.
Verify thermostat and system wires are securely attached.
Same procedures as diagnostic for No Heat condition 
except set the thermostat to Cool and lower the setpoint 
below the room temperature. There may be up to a fi ve 
minute delay before the thermostat clicks in Cooling if the 
compressor lock-out option is selected in the confi guration 
menu (Item 6). 

Heat, Cool or Fan Runs 
Constantly

1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in Heat/Cool/Fan 
    system.
4. Fan Switch set to Fan On.

Check each wire connection to verify they are not shorted 
or touching together. No bare wire should stick out from 
under terminal screws. Try resetting the thermostat as 
described below. If the condition persists, the manufacturer 
of your system or service person can instruct you on how 
to test the Heat/Cool/ system for correct operation. If the 
system operates correctly, replace the thermostat.

Furnace Cycles Too Fast or 
Too Slow 
Cooling Cycles Too Fast 
or Too  Slow 
(narrow or wide 
temperature swing)

1. The location of the thermostat and/or 
    the size of the Heating or Cooling 
    System may be infl uencing the cycle 
    rate.

Item 3 (CR Heat) or 4 (CR Cool) in the Confi guration 
Menu is the adjustment that controls the cycle rate. If an 
acceptable cycle rate is not achieved using the FA (Fast) 
or SL (Slow) adjustment contact a local service person for 
additional suggestions.

Thermostat Setting and 
Thermometer Disagree

1. Thermostat thermometer setting 
    requires adjustment.

The thermometer can be ad/- degrees as listed in 
item 8 of the Confi guration Menu. No other adjustment is 
possible.

Clock Loses or Gains 
Time

1. Loss of power to thermostat.

The thermostat will maintain its program in memory even 
with no power but the clock time will be incorrect when 
power is restored. See No Heat/No Cool /No Fan (common 
problems) above for items to check in the system. 

Heat or Cool Starts Early

1. EMR activated.

See Confi guration Menu (Item 3)

Thermostat Does Not 
Follow Program

1. AM or PM set incorrectly in program.
2. AM or PM set incorrectly on the     
    clock.
3. Voltage spike or static discharge.
4. See “Heat or Cool Starts Early” 
    above.

Check current clock and program settings including the AM 
or PM designations for each time period. If a voltage spike 
or static discharge occurs use the Reset Operation listed 
above.

Blank Display and/or 
Keypad Not Responding

1. Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the Reset 
Operation listed above.

Summary of Contents for White Rodgers 1F80-0224

Page 1: ...Programming Choices 1F80 0224 24 hour Programmable SPECIFICATIONS Electrical Rating Battery Power mV to 30 VAC 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 90 F 7 to 32 C Differential Single Stage Heat 0 6 F Cool 1 2 F adjustable Differential Heat Pump Heat 1 2 F Cool 1 2 F adjustable Operating Ambient 32 to 10...

Page 2: ...e O B switch on this thermostat is factory set to the O position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay in HEAT the O B switch must be moved to the B position Mounting Hole M...

Page 3: ...ning of the next program period To deactivate the EMR function see the Configuration menu on Page 5 The thermostat will then wait until the programmed time to start the system for a temperature change INSTALLATION WIRING DIAGRAMS R C 24 VAC 120 VAC Hot Neutral THERMOSTAT SYSTEM G W Figure 2 Typical wiring diagram for single transformer single stage systems TRANSFORMER Class II Current Limited Chan...

Page 4: ...ce the cover line up the cover with the base and press until the cover snaps onto the base The Thermostat Buttons and Switches 1 Raises temperature setting 2 Lowers temperature setting 3 TIME button 4 SYSTEM switch COOL OFF HEAT EMER 5 PRGM program button 6 FAN switch ON AUTO 7 RUN HOLD program button The Display 8 Indicates days of the week 9 Indicates setpoint temperature This is blank when syst...

Page 5: ...ATION MENU 1 System Configuration Selects SS Single Stage or HP Heat Pump operating mode Default configuration is SS For Heat Pump operation choose HP 2 Select CS Cool Savings With Cool Savings enabled the thermostat will make small adjustments to the Setpoint temperature during periods of high demand to reduce cooling system running time and save energy When the cooling system has been running fo...

Page 6: ...lect F or C Readout Changes the display readout to Celsius or Fahrenheit as required 10 Select Filter Replacement Reminder and Set Run Time Select the Change Filter reminder On or OFF If selected On press RUN HOLD to select the time period from 25 to 1975 hours in 25 hour increments In a typical application 200 hours default of run time is approximately 30 days After the selected time of blower op...

Page 7: ...n AM begins at midnight PM begins at noon 3 Press TIME once again The display window will show the minutes only EXAMPLE 4 Press and hold either or until you reach the correct minutes 5 Press TIME once again The display will show the day of the week 6 Press or until you reach the current day of the week 7 Press RUN HOLD once The display will show the correct time day room temperature and set point ...

Page 8: ...amage CAUTION CHECK YOUR PROGRAMMING Follow these steps to check your thermostat programming one final time before beginning thermostat operation 1 Move SYSTEM switch to HEAT position 2 Press PRGM to view the 1st weekday heating period time and temperature Each time you press PRGM the next heating period time and temperature will be displayed in sequence for weekday then Saturday and Sunday progra...

Page 9: ...rmostat clicks in Cooling if the compressor lock out option is selected in the configuration menu Item 6 Heat Cool or Fan Runs Constantly 1 Possible short in wiring 2 Possible short in thermostat 3 Possible short in Heat Cool Fan system 4 Fan Switch set to Fan On Check each wire connection to verify they are not shorted or touching together No bare wire should stick out from under terminal screws ...

Page 10: ...10 NOTES ...

Page 11: ...11 NOTES ...

Page 12: ...www white rodgers com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 ...

Reviews: