36
8.
Max Speed Detect:
Setting for PLC program detection of maximum speed. This setting will not limit
the speed of the VFD. Generally, this setting is useful only when sequencing of multiple devices is
used.
9.
Minimum Speed:
This is the minimum speed that the PLC will send to the VFD. This is active in
Manual Mode and in Auto Mode.
Adjustment Limit:
This is the maximum amount of change in speed per adjustment. If the
Calculated Adjust-
ment
is greater than the
Adjustment Limit
value, the PLC output will only change the amount of the
Adjust-
ment Limit.
If the
Calculated Adjustment
is less than the
Adjustment Limit
value, the PLC output will change
the amount of the
Calculated Adjustment.
The
Adjustment Limit
is used in conjunction with the
Gain
to
prevent target overshooting.
10.
Gain:
This value is factory set to 2.50 but may be set from 0.1 to 99. For VFDs,
Gain
is a multiplica-
tion factor used in a calculation to determine an adjustment to the speed each set interval. This
interval is defined as the
Increase Rate or Decrease Rate.
Factory settings for
Increase Rate and De-
crease Rate
are 2 to 5 seconds.
Manual Button:
Choosing Manual will do the following:
1.
The fan
Output Mode
will remain
Manual Mode
.
2.
Manual Speed:
This setting becomes accessible only when the Manual Button is chosen. Enter the
desired speed (%) for the VFD.
Stop Button:
Choosing Stop will remove the fan from Auto and from Manual. The VFD will ramp down to a stop. Note:
The On/Off status of a VFD is based on a nominal speed feedback from the VFD. Therefore, the
VFD Status
will display “On” until the drive is near zero speed.
Bypass Button:
Choosing Bypass will remove the fan from VFD speed control. The bypass contactor will be used in lieu of
the VFD.
Summary of Contents for VSG & VSSG
Page 1: ...1 VSG VSSG Single Screw Compressor Software Manual Compact Logix PLC ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 14: ...14 ...
Page 21: ...21 Discharge Pressure Control There are three options for the Compressor Control Setpoints ...
Page 22: ...22 Suction Pressure Control ...
Page 23: ...23 Process Temperature Control ...
Page 39: ...39 Instrument Calibration ...
Page 46: ...46 ...
Page 68: ...68 ...
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 79: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ...69 ...