35
Motor Speed Setpoints & Control Screen
VFD SCREEN SETTINGS
Settings:
Auto Button:
Choosing Auto will do the following:
1.
While the fan is off the
Output Mode
will be forced to
Manual Mode
.
2.
When the fan starts, it will remain in
Manual Mode
at the
Initial Speed
for the period defined as
Delay Auto.
3.
After the
Delay Auto
time expires, the
Output Mode
will change to
Auto Mode.
4.
In
Auto Mode
, the VFD is enabled to increase and decrease speed to maintain the temperature set-
tings.
5.
Increase At:
High setting where an increase of speed is desired.
6.
Decrease At:
Low setting where a decrease of speed is desired
7.
Initial Speed:
Desired forced speed to start the fan at as described above. Note: The PLC will auto-
matically keep this value to at least the
Minimum Speed
setting.
Summary of Contents for VSG & VSSG
Page 1: ...1 VSG VSSG Single Screw Compressor Software Manual Compact Logix PLC ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 14: ...14 ...
Page 21: ...21 Discharge Pressure Control There are three options for the Compressor Control Setpoints ...
Page 22: ...22 Suction Pressure Control ...
Page 23: ...23 Process Temperature Control ...
Page 39: ...39 Instrument Calibration ...
Page 46: ...46 ...
Page 68: ...68 ...
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 79: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ...69 ...