Unidrive M / HS Frame 7 to 10 Power Installation Guide
115
Issue Number: 5
S
P
M
E
Te
UL
li
5.2.2
Overall EMC filter dimensions
Table 5-42 Optional external EMC filter dimensions
5.2.3 EMC filter torque settings
Table 5-43 Optional external EMC Filter terminal data
Part Number
Dimensions (mm)
Weight
H
W
D
mm
inch
mm
inch
mm
inch
kg
lb
4200-1132
270
10.63
90
3.54
150
5.90
6
13.2
4200-0672
270
10.63
90
3.54
150
5.90
6.2
13.7
4200-1972
300
11.81
120
4.72
170
6.69
9.6
21.2
4200-1662
300
11.81
120
4.72
170
6.69
9.4
20.7
4200-3021
339
13.3
230
9.06
120
4.72
11
24.3
4200-1660
360
14.2
245
9.6
105
4.13
5.2
11.5
4200-4460
105
4.13
360
14.2
245
9.6
12
26.5
4200-2210
105
4.13
360
14.2
245
9.6
10.3
22.7
CT part
number
Power
connections
Ground
connections
Bar hole diameter
Max cable size
Max torque
Ground stud
size
Max torque
4200-1132
N/A
50 mm
2
(1/0 AWG)
8.0 N m
(6.0lb ft)
M10
18 N m
(13.3 lb ft)
4200-0672
4200-1972
95 mm
2
(3/0 AWG)
20 N m
(14.8 lb ft)
4200-1662
4200-3021
10.8 mm
N/A
30 N m
(22.1 lb ft)
4200-1660
10.8 mm
4200-4460
11 mm
4200-2210
11 mm
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 115 Tuesday, May 24, 2016 11:52 AM