112
Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Table 5-35 Size 8 emission compliance (400 V drives)
Table 5-36 Size 8 emission compliance (575 V and 690 V drives)
Table 5-37 Size 9 and 10 emission compliance (200 V drives)
Table 5-38 Size 9 and 10 emission compliance (400 V drives)
Table 5-39 Size 9 and 10 emission compliance (575 V and 690 V drives)
Motor cable length (m)
Switching Frequency (kHz)
2
3
4
6
8
12
16
Using internal filter:
0 – 10
C3
C3
C3
C3
C3
C3
C3
Using external filter:
0 – 20
C2
C2
C2
C2
C2
C2
C2
20 – 100
C2
C2
C3
C3
C3
C3
C3
Motor cable length (m)
Switching Frequency (kHz)
2
3
4
6
8
12
16
Using internal filter:
0 – 100
C4
C4
C4
C4
C4
C4
C4
Using external filter:
0 – 20
C2
C2
C2
C2
C2
C2
C2
20 – 100
C2
C2
C3
C3
C3
C3
C3
Motor cable length (m)
Switching Frequency (kHz)
2
3
4
6
8
12
16
Using internal filter:
0 – 100
C3
C3
C3
C3
C3
C3
C3
Using external filter:
0 – 20
C2
C2
C2
C2
C2
C2
C2
20 – 100
C2
C2
C3
C3
C3
C3
C3
Motor cable length (m)
Switching Frequency (kHz)
2
3
4
6
8
12
16
Using internal filter:
0 – 100
C3
C3
C3
C3
C3
C3
C3
Using external filter:
0 – 20
C2
C2
C2
C2
C2
C2
C2
20 – 100
C2
C2
C3
C3
C3
C3
C3
Motor cable length (m)
Switching Frequency (kHz)
2
3
4
6
8
12
16
Using internal filter:
0 - 50
C3
C3
C3
C3
C3
C3
C3
Using external filter:
0 – 20
C2
C2
C2
C2
C2
C2
C2
20 – 100
C2
C2
C3
C3
C3
C3
C3
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 112 Tuesday, May 24, 2016 11:52 AM