 WARNING

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result in an explosion, 

fire and/or chemical contamination 

causing property damage and personal 

injury or death.
Max-Flo Series steam trap must be 

installed, operated and maintained 

in accordance with federal, state and 

local codes, rules and regulations and 

Emerson instructions.
If leak develops in the system, service 

to the unit may be required. Failure 

to correct trouble could result in a 

hazardous condition.
Installation, operation and maintenance 

procedures performed by unqualified 

personnel may result in improper 

adjustment and unsafe operation. Either 

condition may result in equipment 

damage or personal injury. Only a 

qualified person shall install or service 

the Max-Flo Series steam trap.

Principle of Operation

On startup, air and non-condensible gases enter 

the trap and are automatically vented through an 

accurate balanced-pressure internal thermostatic air 

vent. As condensate enters the trap, the float and 

lever mechanism is raised, lifting the valve off the 

seat, discharging the condensate. Condensate will 

continue to be discharged at the same rate at which it 

is entering. Any air or non-condensible gas that may 

accumulate will be continually and efficiently passed 

by the thermostatic air vent.

Figure 1

. Max-Flo Series Steam Trap

Installation

 

 WARNING

Personal injury, property damage, 

equipment damage or leakage due 

to escaping steam or bursting of 

pressure containing parts may result 

if this equipment is over pressured or 

is installed where service conditions 

could exceed the limits given in the 

Introduction

Scope of the Manual

This manual provides instructions for installation, 

maintenance and parts ordering for the Max-Flo Series.

Product Description

Max-Flo Series are float and thermostatic steam 

traps. Float actuates the valve via a hinged lever 

and linkage. Air vent is balanced-pressure design 

with stainless steel welded encapsulated bellows 

capable of discharging air and non-condensable gases 

continuously for heavy load process.. Trap is cast iron 

bodied suitable for pressures to 175 psi / 12.1 bar with 

NPT connection.

Instruction Manual

VCIMD-14919

Max-Flo Series

November 2021

Summary of Contents for Spence Max-Flo Series

Page 1: ...ostatic air vent As condensate enters the trap the float and lever mechanism is raised lifting the valve off the seat discharging the condensate Condensate will continue to be discharged at the same rate at which it is entering Any air or non condensible gas that may accumulate will be continually and efficiently passed by the thermostatic air vent Figure 1 Max Flo Series Steam Trap Installation W...

Page 2: ...ed the Max Flo Series Float and Thermostatic Traps will provide optimum performance specifications or where conditions exceed any ratings of the adjacent piping or piping connections To avoid such injury or damage provide pressure relieving or pressure limiting device Max Flo Series should be installed in an accessible position and location for easy servicing The trap seat rating stamped on the na...

Page 3: ...Installation TRAP NPS 2 1 2 DN 65 TRAP NPS 2 DN 50 SUPPLY INLET VALVE EYE HOOK Y STRAINER INLET COVER BOLTS TRAP DIRT POCKET DISCHARGE LINE PIPE SUPPORTS OUTLET DRAIN PLUG SUPPLY INLET VALVE Y STRAINER INLET COVER BOLTS TRAP DIRT POCKET DISCHARGE LINE PIPE SUPPORTS OUTLET DRAIN PLUG SUPPORT FOOT THERMOSTATIC VENT PIPE TO GRAVITY RETURN LINE 2 Remove drain plug to drain condensate from trap body 3 ...

Page 4: ...body assembly on cover 2 Insert and securely tighten drain plug 3 Open supply valve on trap outlet side slowly open the supply valve to the trap inlet 4 Check for leaks and normal operation Parts Ordering When corresponding with your local Sales Office about Max Flo Series always reference the assembly number see Table 1 PART MODEL P N Thermostat All Models WAL5891200 Lever and Valve Kit Includes ...