Catalog Number
SLN600
SPS850
SLN1000
SLN1500
Short Circuit
*
OSCP is Output
Short Circuit Protection
1. The Output current continues
over 125% within 60ms to
OSCP* and then goes to
Battery MODE.
2. UPS goes to retry mode every
10 seconds until the Battery
Voltage (V
B
) <11V/cell.
3. The Battery recharges when
the V
B
>12.7V/cell, then UPS
continues retry mode every
10 seconds.
4. UPS goes to auto recovery
mode until the short circuit
disappears then goes back to
LINE Mode.
1. The Output current
continues over
250% within 60ms
to OSCP* and then
goes to
Battery MODE.
2. UPS goes to retry
mode every 10
seconds until the
Battery Voltage (V
B
)
<11V/cell.
3. The Battery recharges
when the V
B
>12.7V/
cell, then UPS
continues retry mode
every 10 seconds.
4. UPS goes to auto
recovery mode until
the short circuit
disappears then goes
back to
LINE Mode.
1. The Output current continues over 125%
within 60ms to OSCP* and then goes to
Battery MODE.
2. UPS goes to retry mode every 10 seconds
until the Battery Voltage (V
B
) <11V/cell.
3. The Battery recharges when the V
B
>12.7V/
cell, then UPS continues retry mode every
10 seconds.
4. UPS goes to auto recovery mode until the
short circuit disappears then goes back to
LINE Mode.
Battery Parameters
Battery Type
VRLA, maintenance free, sealed, lead-acid cells
Transfer Time
Typical: 8ms, max. <10ms@AC mode to backup mode
Typical Recharge Time
8 hours
Environmental
Operating Tempera-
ture
0 to +40°C
Storage Temperature
-15 to +45°C
Relative Humidity
0% to 90% relative humidity, non-condensing
Audible Noise
≤40 dBA without audible alarm beyond 1m at rated load
Standards
EMC
FCC Part 15, Subpart B, Class A; EN62040-2; EN55032; CISPR22
Surge Protection
Meets IEEE C62.41,
Category A & B
Delta: (Line to line: 1kV;
line to earth: 2kV)
Meets IEEE C62.41,
Category A
Meets IEEE C62.41, Category A & B
L-L: 1kV; lL-E: 2kV
Certifications
cULus Listed, UPS Equipment UL 1778, CSA C22.2 No. 107.3