Page: 10
Catalog Number
SLN600
SPS850
SLN1000
SLN1500
Topology
Line Interactive
Offline
Line Interactive
Line Interactive
Capacity (VA/W)
600/360
850/510
1000/600
1500/900
Dimensions
Unit (H x W x D) - in.
(mm)
5.6x4.1x11.82
(142x104x300.2)
5.6x4.1x11.82
(142x104x300.2)
7.09x5.12x12.6
(180x130x320)
7.09x5.12x12.6
(180x130x320)
Ship Weight - lbs (kg)
12.13 (5.5) ± 10%
8.16 (3.7) ± 10%
19.62 (8.9) ± 10%
25.35 (11.5) ± 10%
Input Parameters
Voltage
120 Vac
-23% / +29%
120 Vac
-25% / +20%
120 Vac
-23% / +29%
Frequency
50/60 Hz +/- 10% (auto sensing)
Input Power Cord
5 ft. with NEMA 5-15P
Output AC Parameters
Voltage (Battery Mode)
120V±10%
Frequency (On Battery)
50/60 Hz
Auto Voltage
Regulation
(AVR function under
Normal Mode)
V
out
= Input 102 Vac x 118% at
Boost mode
V
out
= Input 138 Vac x 85% at
Buck mode
N/A
V
out
= Input 102 Vac x 118% at Boost mode
V
out
= Input 138 Vac x 85% at Buck mode
Overload
Protection
Line Mode:
1. 110%±5% load for
5 mins. After, the power will
not be provided to the load.
Then, every 10 mins, auto
recovery will be
attempted.
2. 120%±5% load for
10 seconds. After, the power
will not be provided to the
load. Then, every 10 mins,
auto recovery will be
attempted.
3. 130%±5% load for
1.5 seconds. After, the power
will not be provided to the
load. Then, every 10 mins,
auto recovery will be
attempted.
Breaker Protection
Line Mode:
1. 110%±5% load for 5 mins. After, the
power will not be provided to the load.
Then, every 10 mins, auto recovery will be
attempted.
2. 120%±5% load for 10 seconds. After, the
power will not be provided to the load.
Then, every 10 mins, auto recovery will be
attempted.
3. 130%±5% load for 1.5 seconds. After, the
power will not be provided to the load.
Then, every 10 mins, auto recovery will be
attempted.