Mapping for Non-DD Based Integration with Host Systems
July 2016
Reference Manual
00809-0200-4648, Rev BB
75
Mapping for Non-DD Based Integration with Host Systems
Appendix C
Mapping for Non-DD Based
Integration with Host
Systems
Alert message mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 75
Mapping of device variables index numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 77
C.1
Alert message mapping
This outlines the most important alerts in the HART
®
command 48 Additional Status Field
for the Rosemount
™
648 Wireless Temperature Transmitter. The information in this section
can be used by DeltaV
™
for alert monitoring, and in the Rosemount 1420 Smart Wireless
Gateway for Additional Status mapping in Modbus
®
, OPC, etc.
A complete list of Additional Status bits is available in the Rosemount 1420
shows a list of the most important alert messages that may display in
the AMS
™
Wireless Configurator and Field Communicator together with the location of the
Alert in the HART command 48 Additional Status field. For recommended actions refer to
.
To view Active Alerts, from the
Home
screen, go to
Service Tools>Active Alerts
.
Table C-1. Failure Alerts (F:)
Message
Additional status
(1)
1.
Location of the Alert in the HART command 48 Status field.
Description
Electronics Failure
Byte 0 :: Bit 0
Byte 0 :: Bit 1
Byte 0 :: Bit 3
Byte 0 :: Bit 6
Byte 0 :: Bit 7
Byte 8 :: Bit 1
Byte 8 :: Bit 2
Byte 8 :: Bit 6
An electronics error that could impact the
device measurement reading has
occurred
Terminal Block Failure
Byte 3 :: Bit 2
Byte 3 :: Bit 3
Byte 3 :: Bit 6
A critical failure has occurred in the
transmitter's terminal block
Sensor Failure
Byte 3 :: Bit 7
The device has detected an open, short,
or too much resistance for this sensor
Radio Failure
Byte 1 :: Bit 1
Byte 1 :: Bit 7
The wireless radio has detected a failure
or stopped communicating
Supply Voltage Failure
Byte 1 :: Bit 4
Byte 5 :: Bit 2
The supply voltage is too low for the
device to broadcast
Summary of Contents for Rosemount X-well 648
Page 2: ......
Page 6: ...vi Reference Manual 00809 0200 4648 Rev BB Title Page July 2016 Title Page ...
Page 10: ...4 Reference Manual 00809 0200 4648 Rev BB Contents July 2016 Contents ...
Page 12: ...2 Reference Manual 00809 0200 4648 Rev BB Introduction July 2016 Introduction ...
Page 36: ...26 Reference Manual 00809 0200 4648 Rev BB Configuration July 2016 Configuration ...
Page 52: ...42 Reference Manual 00809 0200 4648 Rev BB Commissioning July 2016 Commissioning ...
Page 66: ...56 Reference Manual 00809 0200 4648 Rev BB Troubleshooting July 2016 Troubleshooting ...
Page 89: ......