Figure 2-16. Example 1: Rising Alert
Figure 2-17. Example 2: Falling Alert
Field Communicator
To configure the process alerts with a Field Communicator, perform the following
procedure:
1.
From the
HOME
screen, follow the Fast Key sequence,
2 Configure, 1 Guided
Setup, 7 Configure Process Alarms
.
2.
Select
2 for Hi-Hi Alarm
, or
Select
3 for Hi Alarm
, or
Select
4 for LO Alarm
, or
Select
5 for LO-LO Alarm
and press
Enter
.
3.
If the alarm is disabled, select
1 Enable
and press Enter. If the alarm was previously
enabled, select
2 Leave Enabled
and press
Enter
.
4.
Enter the alarm limit and press
Enter
.
5.
Enter the alarm deadband and press
Enter
.
2.10
Remove power module
After the sensor and network have been configured, remove the power module and replace
the transmitter cover. The power module should be inserted only when the device is ready
to be commissioned. Use caution when handling the power module. The power module
may be damaged if dropped from heights in excess of 20 feet.
Deadband
Assigned Value
Alert Set Point
Alert “OFF”
Alert “ON”
Alert “OFF”
Units of Measurement
Time
Deadband
Assigned Value
Alert Set Point
Alert “OFF”
Alert “ON”
Alert “OFF”
Units of Measurement
Time
Summary of Contents for Rosemount X-well 648
Page 2: ......
Page 6: ...vi Reference Manual 00809 0200 4648 Rev BB Title Page July 2016 Title Page ...
Page 10: ...4 Reference Manual 00809 0200 4648 Rev BB Contents July 2016 Contents ...
Page 12: ...2 Reference Manual 00809 0200 4648 Rev BB Introduction July 2016 Introduction ...
Page 36: ...26 Reference Manual 00809 0200 4648 Rev BB Configuration July 2016 Configuration ...
Page 52: ...42 Reference Manual 00809 0200 4648 Rev BB Commissioning July 2016 Commissioning ...
Page 66: ...56 Reference Manual 00809 0200 4648 Rev BB Troubleshooting July 2016 Troubleshooting ...
Page 89: ......