D.1.1
Ordering information
The part number of the flame simulator kit is FS-HR-975. The kit is supplied in a carry case
that includes:
•
Flame simulator
•
Charger
•
Tool kit
•
Reference manual
D.1.2
Unpacking
Verify that you have received the following contents:
•
Delivery form
•
Flame simulator with integral battery
•
Reference manual
•
Factory acceptance test forms
•
EC declaration
•
Storage case
D.1.3
Simulate a flame
WARNING
Hazardous areas
Do not open the flame simulator to charge the batteries or for any other reason in a
hazardous area.
CAUTION
The following test simulates a real fire condition and may activate the extinguishing
system of other alarms.
If you don't want this to happen, disconnect/inhibit other alarms before the test and
reconnect after the simulation.
Procedure
1. Make sure that you are at the correct distance from the detector according to the
type of detector and the detector sensitivity.
When testing, keep a distance of at least 20 in. (50 cm) from the detector.
2. Press the
Operation
button once.
The flame simulation lasts for fifty seconds. The detector sends an alarm signal
(solid red LED).
Accessories
Reference Manual
June 2021
00809-0100-4976
68
Emerson.com/Rosemount