Rosemount 975 HART Communication Manual
.
1.4.4
RS-485 Modbus
®
For more advanced communications, the flame detector has an RS-485 Modbus-
compatible output that provides data communication from a network (up to 247
detectors) to a host computer or universal controller for central monitoring. This feature
allows for reduced installation costs, easy maintenance, and local or remote diagnostic
tools.
1.4.5
Product certifications
The flame detector has the following certifications:
•
•
•
•
•
•
ATEX, IECEx
The flame detector is certified to:
ATEX per SIRA 15ATEX1364X and IECEx per IECEx SIR 15.0138X.
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96 °C Db
(-55 °C ≤ Ta ≤ +75 °C)
or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106 °C Db
(-55 °C ≤ Ta ≤ +85 °C)
The accessories: tilt mount (PN 00975-9000-0001), weather cover (PN 00975-9000-0003
[plastic] and PN 00975-9000-0004 [stainless steel]), duct mount (PN 00975-9000-0002),
and air shield (PN 00975-9000-0005), are included in the approval.
This product is available to use in hazardous zones 1 and 2 with IIC gas group vapors
present and zones 21 and 22 with IIIC dust type present.
Reference Manual
Introduction
00809-0100-4976
June 2021
Rosemount 975HR
13