Conditions for US installations
1. The dimensions of the flameproof joints are other than the relevant minimum or
maximum values required by Table 2 of UL 60079-0:2019 Ed. 7 for IIB + H2, as
detailed below:
Flamepath
description
Type of joint
Minimum width "L"
(mm)
Maximum gap "ic"
(mm)
Cylindrical section of
spigot (both ends of
Ex d compartment)
Cylindrical
15
0.08
30 mm diameter
window fitted
against enclosure
Flanged
10.7
0.02
39.5 mm diameter
window fitted
against enclosure
Flanged
10
0.02
Gaps shall not be machined to be any larger than the values of "ic", and widths shall
not be modified to be any smaller than the values of "L" shown in the table above.
2. Connections to the intrinsically safe (I.S.) port on the side of the detector enclosure
shall be made via equipment which maintains the intrinsically safe levels of
protection.
3. Where Um marked on the associated apparatus is less than 250 V, it shall be
installed in accordance with one of the following:
•
Where Um does not exceed 50 Vac or 120 Vdc, in a SELV or PELV system or
•
Via a safety isolating transformer complying with the requirements of UL 5085-1
or technically equivalent standard or
•
Directly connected to apparatus complying with UL 60950-1, UL 61010-1, or
technically equivalent standard or
•
Fed directly from cells or batteries.
4. The output of the optical radiation source with respect to explosion protection
meets Exception 3 from the scope of UL 60079-28:2017 Ed. 2.
5. Upon installation, remove the plastic transit plug from the cable entry and use a
cable fitting or a conduit fitting with the following specification to connect the
cable to the equipment:
•
Ex marking: Class I Zone 1 AEx eb IIC Gb, Zone 21 AEx tb IIIC Db
•
Temperature rating: -55 °C to +83 °C or better
•
Connecting thread: M25 x 1.5 or
¾
-in. national pipe thread (NPT)
6. Equipment is only to be installed by manufacturer trained personnel.
7. Equipment has only been tested for electrical safety. No evaluation of functional
safety and performance characteristics has been conducted.
Reference Manual
Installation
00809-0100-4036
October 2021
Rosemount 936
39
Summary of Contents for Rosemount 936
Page 4: ...4 ...
Page 8: ...Product overview Reference Manual October 2021 00809 0100 4036 8 Emerson com Rosemount ...
Page 24: ...Operating modes Reference Manual October 2021 00809 0100 4036 24 Emerson com Rosemount ...
Page 30: ...Specifications Reference Manual October 2021 00809 0100 4036 30 Emerson com Rosemount ...
Page 50: ...Installation Reference Manual October 2021 00809 0100 4036 50 Emerson com Rosemount ...
Page 68: ...Wiring configurations Reference Manual October 2021 00809 0100 4036 68 Emerson com Rosemount ...
Page 72: ...Support Reference Manual October 2021 00809 0100 4036 72 Emerson com Rosemount ...
Page 74: ...Short range model Reference Manual October 2021 00809 0100 4036 74 Emerson com Rosemount ...