background image

27

Reference Manual 

00809-0300-4750, Rev CA

Quick Installation and Start-Up

March 2016

Quick Installation and Start-Up

Figure 2-27. Field Mount Transmitter Analog Loop Load Limitations

R

max

 = 31.25 (V

ps

 — 10.8)

V

ps

    = Power supply voltage (Volts)

R

max

 = Maximum loop resistance (Ohms)

Wall mount transmitter

The analog output signal is a 4—20mA current loop. The loop can be powered internally or 
externally via a hardware switch. The switch is set to internal power when shipped from the 
factory. 

For HART Communication a minimum resistance of 250 ohms is required. It is 
recommended to use individually shielded twisted pair cable. The minimum conductor size 
is 0.51 mm diameter (number 24 AWG) for cable runs less than 5,000 ft. (1,500 m) and 
0.81 mm diameter (number 20 AWG) for longer distances. 

Internal power 

The 4—20mA analog signal is a 24 VDC active output. 

Maximum allowable loop resistance is 500 ohms.

External power

The 4—20 mA analog signal is powered from an external power source. HART multidrop 
installations require a 10—30 VDC external analog power source.

Figure 2-28. Wall Mount Transmitter Analog Wiring

A. +4–20 mA
B. -4–20 mA 

600

400

200

0

10.8

30

Operating 

region

Power supply (Volts)

Load (Ohms)

A B

Summary of Contents for Rosemount 8750W

Page 1: ...Reference Manual 00809 0300 4750 Rev CA March 2016 Rosemount 8750W Magnetic Flowmeter Platform for Utility Water and Wastewater Applications ...

Page 2: ......

Page 3: ...2 5 5 Environmental considerations 9 2 6 Handling and lifting 10 2 7 Mounting 11 2 7 1 Upstream downstream piping 11 2 7 2 Flow direction 11 2 8 Sensor location 12 2 8 1 Electrode orientation 12 2 9 Sensor installation 13 2 9 1 Flanged sensors 13 2 9 2 Flange bolts 13 2 10 Process reference connection 17 2 11 Wiring the transmitter 19 2 11 1 Conduit entries and connections 20 2 11 2 Conduit requir...

Page 4: ...ct discrete input 46 3 5 Process reference connection 48 3 6 Coil housing configuration 48 4Section 4 Operation 4 1 Introduction 49 4 2 Field mount transmitter local operator interface LOI 49 4 2 1 Basic features 50 4 2 2 Data entry 50 4 2 3 Data entry examples 51 4 2 4 Totalizer functionality 52 4 2 5 Display lock 52 4 2 6 Diagnostic messages 53 4 2 7 Display symbols 53 4 3 Wall mount transmitter...

Page 5: ...gure HART 101 5 3 1 Variable mapping 101 5 3 2 Poll address 103 5 3 3 Burst mode 103 5 3 4 Configure LOI 104 5 4 Additional parameters 106 5 4 1 Coil drive frequency 106 5 4 2 Process density 107 5 4 3 Reverse flow 107 5 4 4 Low flow cutoff 107 5 4 5 PV damping 108 5 4 6 Signal processing 108 5 5 Configure special units 110 5 5 1 Base volume unit 110 5 5 2 Conversion factor 110 5 5 3 Base time uni...

Page 6: ...ated electrode parameters 121 6 8 4 20 mA loop verification 123 6 8 1 Initiating 4 20 mA loop verification 123 6 8 2 4 20 mA loop verification parameters 123 6 9 SMART Meter Verification 124 6 9 1 Sensor baseline signature parameters 125 6 9 2 Establishing the sensor baseline signature 126 6 9 3 SMART Meter Verification test criteria 127 6 10 Run manual SMART Meter Verification 128 6 10 1 Test con...

Page 7: ...t 8750W Transmitter electronics stack 149 8 4 1 Field mount transmitter 149 8 5 Replacing the terminal block 151 8 5 1 Removing the terminal block 151 8 5 2 Installing the terminal block 151 8 6 Trims 152 8 6 1 D A trim 152 8 6 2 Scaled D A trim 153 8 6 3 Digital trim 153 8 6 4 Universal trim 155 8 7 Review 155 9Section 9 Troubleshooting 9 1 Introduction 157 9 2 Safety messages 157 9 3 Installatio...

Page 8: ... 182 A 1 6 Analog output effects 182 A 1 7 Physical specifications 183 A 2 Wall mount transmitter specifications 183 A 2 1 Functional specifications 183 A 2 2 Advanced diagnostics capabilities 185 A 2 3 Output signals 185 A 2 4 Sensor compensation 186 A 2 5 Performance specifications 186 A 2 6 Analog output effects 186 A 2 7 Physical specifications 187 A 3 Sensor specifications 187 A 3 1 Functiona...

Page 9: ...Endress and Hauser Sensors 229 D 4 1 Endress and Hauser Sensor to Rosemount 8750W Transmitter 229 D 5 Fischer and Porter Sensors 230 D 5 1 Model 10D1418 Sensor to Rosemount 8750W Transmitter 230 D 5 2 Model 10D1419 Sensor to Rosemount 8750W Transmitter 231 D 5 3 Model 10D1430 Sensor Remote to Rosemount 8750W Transmitter 232 D 5 4 Model 10D1430 Sensor Integral to Rosemount 8750W Transmitter 233 D 5...

Page 10: ... Taylor Sensors 243 D 10 1 Series 1100 Sensor to Rosemount 8750W Transmitter 243 D 10 2 Taylor Sensor to Rosemount 8750W Transmitter 244 D 11 Yamatake Honeywell Sensors 245 D 11 1 Yamatake Honeywell Sensor to Rosemount 8750W Transmitter 245 D 12 Yokogawa Sensors 246 D 12 1 Yokogawa Sensor to Rosemount 8750W Transmitter 246 D 13 Generic manufacturer sensors 247 D 13 1 Identify the terminals 247 D 1...

Page 11: ...n an explosive atmosphere Follow national local and plant standards to properly earth ground the transmitter and sensor The earth ground must be separate from the process reference ground Rosemount Magnetic Flowmeters ordered with non standard paint options or non metallic labels may be subject to electrostatic discharge To avoid electrostatic charge build up do not rub the flowmeter with a dry cl...

Page 12: ...ment are NOT designed for nuclear qualified applications Using non nuclear qualified products in applications that require nuclear qualified hardware or products may cause inaccurate readings For information on Rosemount nuclear qualified products contact your local Emerson Process Management Sales Representative ...

Page 13: ...Rosemount 8750W Magnetic Flowmeter System consists of a sensor and a transmitter The sensor is installed in line with the process piping the transmitter can be remotely mounted or integrally mounted to the sensor Figure 1 1 Field Mount Transmitter Figure 1 2 Wall Mount Transmitter Figure 1 3 Flanged Sensor Integral Remote Remote ...

Page 14: ...th the liquid The transmitter energizes the coils and creates a magnetic field A conductive liquid moving through the magnetic field generates an induced voltage at the electrodes This voltage is proportional to the flow velocity The transmitter converts the voltage detected by the electrodes into a flow reading 1 2 Product recycling disposal Recycling of equipment and packaging should be taken in...

Page 15: ... 32 2 1 Introduction This section covers the steps required to physically install the magnetic flowmeter Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations Refer to the following safety messages before performing any operation in this section 2 2 Safety messages This section provides basic installation guideli...

Page 16: ...te from the process reference ground Rosemount Magnetic Flowmeters ordered with non standard paint options or non metallic labels may be subject to electrostatic discharge To avoid electrostatic charge build up do not rub the flowmeter with a dry cloth or clean with solvents NOTICE The sensor liner is vulnerable to handling damage Never place anything through the sensor for the purpose of lifting ...

Page 17: ... and electrode connections Other applications may require one or more of the following configurations or options Pulse Output Discrete Output Discrete Input HART Multidrop Configuration Hardware switches The Rosemount 8750W electronics stack is equipped with user selectable hardware switches These switches set the Alarm mode Internal external analog power Inter nal external pulse power and Transmi...

Page 18: ...er installations a mounting bracket is provided for use on a 2 in pipe or a flat surface see Figure 2 1 for field mount and Figure 2 3 for wall mount Note If the transmitter is mounted separately from the sensor it may not be subject to limitations that might apply to the sensor Rotate integral mount transmitter housing or remote junction box The transmitter housing can be rotated on the sensor in...

Page 19: ... Mount Transmitter A 1 2 in 14 NPT or M20 conduit entry B LOI cover C 2 in pipe bracket D Ground lug Dimensions are in inches millimeters Figure 2 2 Rosemount 8750W Integral Field Mount Transmitter 7 49 189 8 6 48 164 6 1 94 49 3 A B C A D 5 77 146 4 7 64 194 0 8 86 225 1 3 07 78 0 2 22 56 4 3 00 76 2 5 00 127 0 10 29 261 3 2 81 71 4 5 00 127 0 1 80 45 7 10 18 258 6 5 82 147 8 ...

Page 20: ...ndard Cover A Ground lug B 1 2 in 14 NPT conduit connection 4 places Dimensions in inches millimeters Figure 2 4 Rosemount 8750W Wall Mount Transmitter with LOI Cover A LOI keypad cover Note Default conduit entries are 1 2 in NPT If an alternate thread connection is required thread adapters must be used 4 31 109 2 96 75 9 01 229 2 81 71 3 11 79 0 44 12 02 305 11 15 283 A B A ...

Page 21: ...ote mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and to provide easy access for configuration or service Table 2 1 Electrical Data Field mount transmitter Power input 90 250 VAC 0 45 A 40 VA 12 42 VDC 1 2 A 15 W Pulsed circuit Internally powered Active Outputs up to 12 VDC 12 1 mA 73 mW Externally powered Passive Input up to 28 VDC...

Page 22: ... no additional support attached to the sensor Additional safety recommendations for mechanical handling Use proper PPE Personal Protection Equipment should include safety glasses and steel toed shoes Do not drop the device from any height Do not lift the meter by holding the electronics housing or junction box The sensor liner is vulnerable to handling damage Never place anything through the senso...

Page 23: ...downstream from the electrode plane see Figure 2 6 Figure 2 6 Upstream and Downstream Straight Pipe Diameters A five pipe diameters B two pipe diameters Installations with reduced upstream and downstream straight runs are possible In reduced straight run installations the meter may not meet absolute accuracy specifications Reported flow rates will still be highly repeatable 2 7 2 Flow direction Th...

Page 24: ...orizontal installation should be restricted to low piping sections that are normally full Figure 2 8 Sensor Orientation 2 8 1 Electrode orientation The electrodes in the sensor are properly oriented when the two measurement electrodes are in the 3 and 9 o clock positions or within 45 from the horizontal as shown on the left in Figure 2 9 Avoid any mounting orientation that positions the top of the...

Page 25: ...lectrode require only one gasket on each process connection Note Metallic or spiral wound gaskets should not be used as they will damage the liner face of the sensor Figure 2 10 Flanged Gasket Placement A Grounding ring and gasket optional B Customer supplied gasket 2 9 2 Flange bolts Note Do not bolt one side at a time Tighten both sides simultaneously Example 1 Snug upstream 2 Snug downstream 3 ...

Page 26: ...he suggested torque values the bolts can be tightened in additional 10 increments until the joint stops leaking or until the measured torque value reaches the maximum torque value of the bolts Practical consideration for the integrity of the liner often leads the user to distinct torque values to stop leakage due to the unique combinations of flanges bolts gaskets and sensor liner material Check f...

Page 27: ...150 mm 45 50 30 37 080 8 in 200 mm 60 82 42 55 100 10 in 250 mm 55 80 40 70 120 12 in 300 mm 65 125 55 105 140 14 in 350 mm 85 110 70 95 160 16 in 400 mm 85 160 65 140 180 18 in 450 mm 120 170 95 150 200 20 in 500 mm 110 175 90 150 240 24 in 600 mm 165 280 140 250 Table 2 4 Flange Bolt Torque and Load Specifications EN 1092 1 Size code Line size Fluoropolymer liners PN10 Newton meter PN 16 V Newto...

Page 28: ... 2 in 50 mm N A N A N A 40 025 2 5 in 65 mm N A N A N A 35 030 3 in 80 mm N A N A N A 30 040 4 in 100 mm N A 40 N A 50 050 5 in 125 mm N A 50 N A 70 060 6 in 150 mm N A 60 N A 90 080 8 in 200 mm 90 60 90 110 100 10 in 250 mm 70 80 130 170 120 12 in 300 mm 80 110 130 180 140 14 in 350 mm 110 150 210 280 160 16 in 400 mm 150 190 280 410 180 18 in 450 mm 130 230 220 280 200 20 in 500 mm 150 260 300 3...

Page 29: ...r Line Sizes AWWA C207 Size code Line size Fluoropolymer liners Class D pound feet Class E pound feet Class F pound feet 300 30 in 750 mm 195 195 195 360 36 in 900 mm 280 280 280 Resilient liners 300 30 in 750 mm 165 165 165 360 36 in 900 mm 245 245 245 400 40 in 1000 mm 757 757 N A 420 42 in 1050 mm 839 839 N A 480 48 in 1200 mm 872 872 N A Table 2 6 Flange Bolt Torque and Load Specifications Lar...

Page 30: ...ounding with Grounding Rings in Conductive Pipe A Grounding rings Table 2 7 Process Reference Installation Process reference options Type of pipe Grounding straps Grounding rings Reference electrode Lining protectors Conductive unlined pipe See Figure 2 12 See Figure 2 13 1 1 Grounding ring reference electrode and lining protectors are not required for process reference Grounding straps per Figure...

Page 31: ...r Line Sizes 10 in and Larger 2 11 Wiring the transmitter This wiring section covers the wiring between the transmitter and sensor the 4 20 mA output and supplying power to the transmitter Follow the conduit information cable requirements and disconnect requirements in the sections below For sensor wiring diagrams see Electrical Drawing 8750W 1504 in Appendix C Wiring Diagrams For information on c...

Page 32: ...nts For installations with an intrinsically safe electrode circuit a separate conduit for the coil cable and the electrode cable may be required See drawing 08732 2062 Electrode cables should not be run together and should not be in the same cable tray with power cables Output cables should not be run together with power cables Select conduit size appropriate to feed cables through to the flowmete...

Page 33: ...es Coil Electrode Coil Electrode 518243 518245 08732 0065 0002 meters Kit Component cables Std temp includes Coil Electrode Coil Electrode 518243 518245 08732 0065 0003 feet Kit Component cables Std temp includes Coil I S Electrode Coil Intrinsically Safe Blue Electrode 518243 518245 08732 0065 0004 meters Kit Component cables Std temp includes Coil I S Electrode Coil Intrinsically Safe Blue Elect...

Page 34: ...g the combination coil drive electrode cable see Figure 2 20 Combination cable lengths should be limited to less than 330 feet 100 m Figure 2 19 Individual Component Cables Table 2 9 Combination Cable Kits Coil Electrode cable 20 C to 80 C Cablekit number Description 08732 0065 2001 feet Kit Combination cable Standard 08732 0065 2002 meters 08732 0065 3001 feet Kit Combination cable Submersible 80...

Page 35: ...trode cables as shown in Figure 2 21 Limit the unshielded wire length to less than one inch on both the coil drive and electrode cables Any length of unsheathed conductor should be insulated Excessive removal of insulation may result in an unwanted electrical short to the transmitter housing or other wire connections Excessive unshielded lead length or failure to connect cable shields properly may...

Page 36: ...ss the terminal block See Figure 2 23 for terminal identification To connect pulse output and or discrete input output consult the comprehensive product manual Installations with intrinsically safe outputs should reference the hazardous location installation drawings in Appendix B Product Certifica tions Figure 2 23 Field Mount Transmitter Terminal Block Connections Shock Hazard Potential shock ha...

Page 37: ...tput signal is a 4 20 mA current loop The loop can be powered internally or externally via a hardware switch located on the front of the electronics stack The switch is set to internal power when shipped from the factory For units with a display the LOI must be removed to change switch position For HART communication a minimum loop resistance of 250 ohms is required It is recommended to use indivi...

Page 38: ... externally powered External power The 4 20mA analog signal is passive and must be powered from an external power source Power at the transmitter terminals must be 10 8 30 VDC Wire terminal 1 and terminal 2 See Figure 2 26 Figure 2 26 Field Mount Transmitter Analog Wiring External Power A Power supply Analog loop load limitations Maximum loop resistance is determined by the voltage level of the ex...

Page 39: ...unication a minimum resistance of 250 ohms is required It is recommended to use individually shielded twisted pair cable The minimum conductor size is 0 51 mm diameter number 24 AWG for cable runs less than 5 000 ft 1 500 m and 0 81 mm diameter number 20 AWG for longer distances Internal power The 4 20mA analog signal is a 24 VDC active output Maximum allowable loop resistance is 500 ohms External...

Page 40: ...igned to be powered by 90 250 VAC 50 60 Hz The DC powered transmitter is designed to be powered by 12 42 VDC Before connecting power to the transmitter be sure to have the proper power supply conduit and other accessories Wire the transmitter according to national local and plant electrical requirements for the supply voltage See Figure 2 30 through Figure 2 33 Figure 2 30 Field Mount Transmitter ...

Page 41: ... inrush is 35 7 A at 250 VAC supply lasting approximately 1ms Inrush for other supply voltages can be estimated with Inrush Amps Supply Volts 7 0 Supply current Amps Power supply VDC 0 8 1 2 1 0 0 6 0 4 0 2 18 12 24 30 36 42 Supply current Amps Apparent power VA Power supply VAC Power supply VAC 0 22 0 18 0 16 0 12 0 24 0 14 0 10 0 26 0 20 90 170 230 150 130 210 190 110 250 18 20 22 24 26 28 30 32...

Page 42: ...d for 194 F 90 C For DC powered transmitters with extended cable lengths verify that there is a minimum of 12 VDC at the terminals of the transmitter with the device under load Disconnects Connect the device through an external disconnect or circuit breaker per national and local electrical code Installation category The installation category for the Rosemount 8750W is OVERVOLTAGE CAT II Supply cu...

Page 43: ...erminal 10 DC DC powered units may draw up to 1 2A Wall mount transmitter power terminals See Figure 2 24 for field mount terminal connections For AC powered transmitter 90 250 VAC 50 60 Hz Connect AC Neutral to terminal N and AC Line to terminal L1 For DC powered transmitter Connect DC to terminal N and DC to terminal L1 Table 2 10 Field Mount Transmitter Fuse Requirements Input voltage Fuse rati...

Page 44: ... cannot be removed 2 13 Basic configuration Once the magnetic flowmeter is installed and power has been supplied the transmitter must be configured through the basic setup The basic setup parameters can be configured through either a local operator interface LOI or a HART Communication device For instructions on operation of the LOI or HART Communication device refer to Section 4 If configuration ...

Page 45: ...39 3 ft s to 39 3 ft s 12 m s to 12 m s There must be at least 1 ft s 0 3 m s span between the URV and LRV LRV Lower Range Value The lower range value LRV sets the 4 mA point for the analog output This value is typically set to zero flow The units that appear will be the same as those selected under the flow units parameter The LRV may be set between 39 3 ft s to 39 3 ft s 12 m s to 12 m s There m...

Page 46: ...ctuations in output LOI menu path Field Mount Basic Setup Cal Number Wall Mount TUBE CAL NO Traditional Fast Keys 1 3 1 Device dashboard 2 2 1 4 1 LOI menu path Field Mount Basic Setup PV Damping Wall Mount DAMPING Traditional Fast Keys 1 3 1 Device dashboard 2 2 1 3 4 Table 2 12 Available Flow Units Volumetric units Mass units gal sec lbs sec gal min lbs min gal hr lbs hr gal day lbs day L sec kg...

Page 47: ... barrel 31 5 gallons Table 2 13 Available Sensor Sizes Sensor size 0 10 in 2 5 mm 18 in 450 mm 0 15 in 4 mm 20 in 500 mm 0 25 in 6 mm 24 in 600 mm 0 30 in 8 mm 28 in 700 mm 0 50 in 15 mm 30 in 750 mm 0 75 in 20 mm 32 in 800 mm 1 0 in 25 mm 36 in 900 mm 1 5 in 40 mm 40 in 1000 mm 2 0 in 50 mm 42 in 1050 mm 2 5 in 65 mm 44 in 1100 mm 3 0 in 80 mm 48 in 1200 mm 4 0 in 100 mm 54 in 1350 mm 5 0 in 125 ...

Page 48: ...36 Reference Manual 00809 0300 4750 Rev BA Quick Installation and Start Up March 2016 Quick Installation and Start Up ...

Page 49: ...c sensitive components 3 3 Hardware switches The electronics are equipped with four user selectable hardware switches These switches set the Alarm Mode Internal External Analog Power Transmitter Security and Inter nal External Pulse Power Definitions of these switches and their functions are provided below To change the settings see below 3 3 1 Alarm mode If an event occurs that would trigger an a...

Page 50: ...rmation on 4 20 mA external power see Analog output on page 25 3 3 4 Internal external pulse power 1 The Rosemount 8750W pulse loop may be powered internally or by an external power supply The internal external pulse power is only available on the Field Mount Transmitter The internal external power supply switch determines the source of the pulse loop power Transmitters are shipped from the factor...

Page 51: ... the electronics compartment cover If the cover has a cover jam screw this must be tightened to comply with installation requirements See Field mount transmitter cover jam screw on page 32 for details on the cover jam screw 8 Return power to the transmitter and verify the flow measurement is correct 9 Return the control loop to automatic control Figure 3 1 Field Mount Transmitter Electronics Stack...

Page 52: ... The signal is typically used in conjunction with an external totalizer or control system The default position of the internal external pulse power switch is in the EXTERNAL position The user selectable power switch is located on the electronics board External For transmitters with the internal external pulse power switch set in the EXTERNAL position the following requirements apply Supply voltage...

Page 53: ... steps to connect an external power supply 1 Ensure the power source and connecting cable meet the requirements outlined previously 2 Turn off the transmitter and pulse output power sources 3 Run the power cable to the transmitter 4 Connect DC to terminal 3 5 Connect DC to terminal 4 Refer to Figure 3 4 and Figure 3 5 10000 1000 100 10 100 1000 500 Ω 1 KΩ 2 5 KΩ 5 KΩ 10 KΩ Cable length feet Freque...

Page 54: ...power supply C Electro mechanical counter Note Total loop impedance must be sufficient to keep loop current below maximum rating A resistor can be added in the loop to raise impedance Figure 3 5 Field Mount Transmitter Connecting to an Electronic Totalizer Counter with External Power Supply A Schematic showing FET between terminal 3 and 4 B 5 24 V DC power supply C Electronic counter Note Total lo...

Page 55: ... Mount Transmitter Connecting to an Electronic Totalizer Counter with Internal Power Supply A Schematic showing FET between terminal 3 and 4 B Electronic counter Wall mount transmitter The pulse output function provides an isolated switch closure frequency signal that is proportional to the flow through the sensor The Wall Mount Transmitter is only available with an externally powered pulse output...

Page 56: ...talizer Counter A 5 28 VDC power supply B Electronic counter C 1k to 100k typical 5k 3 4 2 Connect discrete output The discrete output control function can be configured to drive an external signal to indicate zero flow reverse flow empty pipe diagnostic status flow limit or transmitter status The following requirements apply Supply Voltage 5 to 28 VDC Maximum Voltage Field Mount 28 VDC at 240 mA ...

Page 57: ...er sources 3 Run the power cable to the transmitter 4 Connect channel 1 a For Field Mount connect DC to terminal 5 b For Field Mount connect DC to terminal 6 OR a For Wall Mount connect DC to terminal 10 b For Wall Mount connect DC to terminal 9 5 Connect channel 2 a For Field Mount connect DC to terminal 7 b For Field Mount connect DC to terminal 8 OR a For Wall Mount connect DC to terminal 20 b ...

Page 58: ...ive zero return PZR or net totalizer reset The following requirements apply Supply Voltage 5 to 28 VDC Control Current 1 5 20 mA Input Impedance 2 5 kΩ plus 1 2 V Diode drop See Figure 3 12 To connect the discrete input complete the following steps 1 Ensure the power source and connecting cable meet the requirements outlined previously 2 Turn off the transmitter and discrete power sources 3 Run th...

Page 59: ...nnect Discrete Input A Relay contact or control system output B 5 28 V DC power supply Figure 3 12 Discrete Input Operating Range Figure 3 13 Wall Mount Transmitter Connect Discrete Input A Fuse B Control relay or input A B 0 5 10 15 20 25 30 2 5 5 7 5 10 12 5 15 0 Digital input operating range Supply Voltage Series Resistance Ωin Ωext Kohms A DC DC B ...

Page 60: ...er installation Note Consult factory for installations requiring cathodic protection or situations where there are high electrical currents or high electrical potentials present in the process 3 6 Coil housing configuration The coil housing provides physical protection of the coils and other internal components from contamination and physical damage that might occur in an industrial environment Th...

Page 61: ...nged at any time specific instructions are provided through on screen instructions This section covers the basic features of the LOI optional and provides general instructions on how to navigate the configuration menus using the optical buttons on the Field Mount Transmitter The section also covers the use of a Field Communicator and provides menu trees to access each function For detailed LOI con...

Page 62: ... to navigate the menu structure Figure 4 2 and Figure 4 3 in order to access the appropriate alphanumeric parameter 2 Select the UP DOWN or RIGHT arrow key to begin editing the parameter Use the LEFT arrow key to go back without changing the value For numerical data toggle through the digits 0 9 decimal point and dash For alphabetical data toggle through the letters of the alphabet A Z digits 0 9 ...

Page 63: ...ccess the menu See Figure 4 2 2 Using the arrow keys select line size from the basic setup menu 3 Select the UP DOWN arrow to increase decrease the sensor size to the next value 4 When you reach the desired sensor size select E the left arrow 5 Set the loop to manual if necessary and select E again After a moment the LOI will display VALUE STORED SUCCESSFULLY and then display the selected value Se...

Page 64: ...he lower right hand corner indicating that the meter has stopped totalizing Reset totalizer To reset the totalizer select the DOWN arrow to display the totalizer screen and follow the procedure above to stop totalization Once totalization has stopped select the RIGHT arrow key to reset the NET total value to zero To reset the GROSS FORWARD and REVERSE total values you must change the line size See...

Page 65: ...w 6 Set the loop to manual if necessary and select E again After a moment the LOI will display VALUE STORED SUCCESSFULLY and then display the selected value 4 2 6 Diagnostic messages Diagnostic messages may appear on the LOI See Table 6 1 on page 113 Table 6 2 on page 132 and Table 6 3 on page 132 for a complete list of messages potential causes and corrective actions for these messages 4 2 7 Disp...

Page 66: ...ify View Results License Status License Key EC Current Val EC Max Value Manual Results Continual Results Manual Results Continual Res Valves Reset Baseline Recall Values No Flow Flowing Full Empty Pipe Continual Manual Measure Continual Meas Process Noise Ground Wiring Elec Coating Meter Verif DI DO Device ID Software Rev License Key Test Condition Test Criteria MV Results Sim Velocity ActualVeloc...

Page 67: ... Limit Cont Meter Ver DI O 1 Control DI 1 DO 1 Reverse Flow Zero Flow XMTR Fault Empty Pipe Flow Limit 1 Flow Limit 2 Diag Alert Total Limit 1 Control 1 Mode 1 High Limit 1 Low Limit 1 Hysteresis Control 2 Mode 2 High Limit 2 Low Limit 2 Hysteresis Total Control Total Mode Tot Hi Limit Tot Low Limit Hysteresis Elec Failure Coil Open Ckt Empty Pipe Reverse Flow Ground Wiring Process Noise Elect Tem...

Page 68: ...er the selected value Transmitter parameter keys The transmitter parameter keys provide direct access to the most common transmitter parameters and stepped access to the advanced functions of the 8750W through the Aux Function key Figure 4 4 Local Operator Interface Keypad 4 3 2 Data entry The LOI keypad does not have numerical keys Numerical data is entered by the following procedure 1 Access the...

Page 69: ...es are parameters such as units that are available from a predefined list Select values Select values are parameters that consist of a user created number or character string such as calibration number values are entered one character at a time using the data entry keys Table value example Setting the sensor line size 1 Select TUBE SIZE 2 Select SHIFT or INCR to increase incrementally the size to ...

Page 70: ...t totalizer To reset the totalizer select the TOTALIZE button If totalizer is running select START STOP to stop the totalization and then select READ RESET button to reset net totalization If totalizer is stopped select READ RESET button to reset net totalization To reset the GROSS FORWARD and REVERSE total values you must change the line size See Basic configuration on page 32 for details on how ...

Page 71: ...No Construction Materials 1 Universal Rev 2 Transmitter Rev 3 Software Rev 4 Final Assembly 1 Status 2 Samples 3 Limit 4 Time Limit 1 D A Trim 2 Scaled D A Trim 3 Digital Trim 4 Auto Zero 5 Universal Trim 1 8714i Cal Verification 2 Licensing 1 Run 8714i Verification 2 8714i Results 3 Flowtube Signature 4 Set Pass Fail Criteria 5 Measurements 1 Signature Values 2 Re Signature Meter 3 Recall Last Sa...

Page 72: ...evice driver uses conditional formatting menus If the diagnostic is not active the diagnostic will not be displayed as a menu item in the Field Communicator The Fast Key sequence and menu trees will be resequenced accordingly There are two styles of interface available for Field Communicators The traditional interface is shown in Figure 4 6 The device dashboard interface is shown in Figure 4 7 Fig...

Page 73: ...1 3 Totalizer Setup 1 1 4 Totalizer Units 1 1 4 1 Gross Total 1 1 4 2 Net Total 1 1 4 3 Reverse Total 1 1 4 4 Start Totalizer 1 1 4 5 Stop Totalizer 1 1 4 6 Reset Totalizer 1 1 4 7 Pulse Output 1 1 5 Diagnostics 1 2 Diag Controls 1 2 1 Diagnostic Controls 1 2 1 1 Empty Pipe 1 2 1 1 1 Process Noise 1 2 1 1 1 Grounding Wiring 1 2 1 1 1 Electrode Coating 1 2 1 1 1 Electronics Temp 1 2 1 1 1 Reverse F...

Page 74: ...rol 2 1 2 2 7 1 Mode 2 1 2 2 7 2 High Limit 2 1 2 2 7 3 Low Limit 2 1 2 2 7 4 Flow Limit Hysteresis 1 2 2 7 5 Total Limit 1 2 2 8 Total Control 1 2 2 8 1 Total Mode 1 2 2 8 2 Total High Limit 1 2 2 8 3 Total Low Limit 1 2 2 8 4 Total Limit Hysteresis 1 2 2 8 5 Advanced Diagnostics 1 2 3 Electrode Coat 1 2 3 1 EC Value 1 2 3 1 1 EC Level 1 Limit 1 2 3 1 2 EC Level 2 Limit 1 2 3 1 3 Max EC Value 1 2...

Page 75: ...mulated Velocity 1 2 3 2 2 2 2 Actual Velocity 1 2 3 2 2 2 3 Velocity Deviation 1 2 3 2 2 2 4 Coil Signature 1 2 3 2 2 2 5 Sensor Cal Deviation 1 2 3 2 2 2 6 Coil Resistance 1 2 3 2 2 2 7 Electrode Resistance 1 2 3 2 2 2 8 mA Expected 1 2 3 2 2 2 9 mA Actual 2 1 2 3 2 2 2 10 mA Deviation 2 1 2 3 2 2 2 11 Sensor Signature 1 2 3 2 3 Signature Values 1 2 3 2 3 1 Coil Resistance 1 2 3 2 3 1 1 Coil Sig...

Page 76: ...A Verify 1 2 3 3 4 20 mA Verification 1 2 3 3 1 View Results 1 2 3 3 2 Licensing 1 2 3 4 License Status 1 2 3 4 1 Process Noise Detect 1 2 3 4 1 1 1 Line Noise Detection 1 2 3 4 1 2 1 Electrode Coating 1 2 3 4 1 3 1 8714i 1 2 3 4 1 4 1 Digital I O 1 2 3 4 1 5 1 License Key 1 2 3 4 2 Device ID 1 2 3 4 2 1 License Key 1 2 3 4 2 2 Diagnostic Variables 1 2 4 EP Value 1 2 4 1 Electronics Temp 1 2 4 2 L...

Page 77: ... 2 1 2 4 8 1 11 Continual Results 1 2 4 8 2 Continuous Limit 1 2 4 8 2 1 Simulated Velocity 1 2 4 8 2 2 Actual Velocity 1 2 4 8 2 3 Velocity Deviation 1 2 4 8 2 4 Coil Signature 1 2 4 8 2 5 Sensor Cal Deviation 1 2 4 8 2 6 Coil Resistance 1 2 4 8 2 7 Electrode Resistance 1 2 4 8 2 8 mA Expected 1 2 4 8 2 9 mA Actual 2 1 2 4 8 2 10 mA Deviation 2 1 2 4 8 2 11 Auto Zero Offset 1 2 4 9 Trims 1 2 5 D ...

Page 78: ...ency 1 4 1 1 Density Value 1 4 1 2 PV USL 1 4 1 3 PV LSL 1 4 1 4 PV Minimum Span 1 4 1 5 Configure Output 1 4 2 Analog Output 1 4 2 1 PV URV 1 4 2 1 1 PV LRV 1 4 2 1 2 PV Loop Current 1 4 2 1 3 AO Alarm Type PV Alrm typ 1 4 2 1 4 AO Loop Test 1 4 2 1 5 D A Trim 1 4 2 1 6 Scaled D A Trim 1 4 2 1 7 Alarm Level 1 4 2 1 8 AO Diagnostic Alarm 1 4 2 1 9 Empty Pipe 1 4 2 1 9 1 1 Reverse Flow 1 4 2 1 9 2 ...

Page 79: ...1 4 2 3 1 1 1 Output 1 4 2 3 1 1 2 Not Available Off 1 4 2 3 1 1 3 DIO 1 Control 1 4 2 3 1 2 Digital Input 1 1 4 2 3 1 3 Digital Output 1 1 4 2 3 1 4 DO 2 1 4 2 3 2 Flow Limit 1 1 4 2 3 3 Control 1 1 4 2 3 3 1 Mode 1 1 4 2 3 3 2 High Limit 1 1 4 2 3 3 3 Low Limit 1 1 4 2 3 3 4 Flow Limit Hysteresis 1 4 2 3 3 5 Flow Limit 2 1 4 2 3 4 Control 2 1 4 2 3 4 1 Mode 2 1 4 2 3 4 2 High Limit 2 1 4 2 3 4 3...

Page 80: ...2 1 4 2 3 6 1 Cont Meter Verification 1 4 2 3 6 1 Coil Over Current N A Sensor Electrode Saturated N A Coil Power Limit N A Reverse Flow 1 4 2 4 Totalizer Setup 1 4 2 5 Totalizer Units 1 4 2 5 1 Gross Total 1 4 2 5 2 Net Total 1 4 2 5 3 Reverse Total 1 4 2 5 4 Start Totalizer 1 4 2 5 5 Stop Totalizer 1 4 2 5 6 Reset Totalizer 1 4 2 5 7 Alarm Levels 1 4 2 6 Alarm Level 1 4 2 6 1 Hi Alarm 1 4 2 6 2 ...

Page 81: ...isplay 1 4 3 2 Totalizer Display 1 4 3 3 Display Lock 1 4 3 4 Meter type 1 4 3 5 LOI Error Mask 1 4 3 6 Signal Processing 1 4 4 Operating Mode 1 4 4 1 Man Config DSP 1 4 4 2 Status 1 4 4 2 1 Samples 1 4 4 2 2 Limit 1 4 4 2 3 Time Limit 1 4 4 2 4 Coil Drive Freq 1 4 4 3 Low Flow Cutoff 1 4 4 4 PV Damping 1 4 4 5 Universal Trim 1 4 5 Device Info 1 4 6 Manufacturer 1 4 6 1 Tag 1 4 6 2 Descriptor 1 4 ...

Page 82: ...ce Reset 1 4 7 Review 1 5 1 These items are in a list format without numeric labels 2 To access these features you must scroll to this option in the HART Field Communicator Table 4 2 Device Dashboard Fast Keys Function Fast Keys Overview 1 Device Status 1 1 Flow Rate 1 2 Analog Output Value 1 3 Upper Range Value 1 4 Lower Range Value 1 5 Run Meter Verification 1 6 Meter Verification Results 1 7 De...

Page 83: ...t 1 8 3 6 Minimum Span 1 8 3 7 Liner Material 1 8 3 8 1 Electrode Type 1 8 3 8 2 Electrode Material 1 8 3 8 3 Flange Type 1 8 3 8 4 Flange Material 1 8 3 8 5 Write Protect 1 8 4 1 Alarm Direction 1 8 4 2 Alarm Type 1 8 4 3 High Alarm 1 8 4 4 High Saturation 1 8 4 5 Low Saturation 1 8 4 6 Low Alarm 1 8 4 7 Licenses 1 8 5 Configure 2 Guided Setup 2 1 Initial Setup 2 1 1 Basic Setup 2 1 1 1 Configure...

Page 84: ...guration 2 1 4 1 Analog Alarm Configuration 2 1 4 2 Optimize Signal Processing 2 1 5 Manual Setup 2 2 Flow Units 2 2 1 2 Lower Range Value 2 2 1 3 2 Upper Range Value 2 2 1 3 3 Damping 2 2 1 3 4 Calibration Number 2 2 1 4 1 Line Size 2 2 1 4 2 Language 2 2 1 5 1 Flow Display 2 2 1 5 2 Totalizer Display 2 2 1 5 3 Display Lock 2 2 1 5 4 Density 2 2 2 1 6 Pulse Mode 2 2 2 2 2 Pulse Scaling 2 2 2 2 3 ...

Page 85: ...Alert 2 2 4 3 4 Flow Limit 2 2 2 4 4 High Limit 2 2 2 4 4 1 Low Limit 2 2 2 4 4 2 Limit 2 Control 2 2 4 4 3 Limit 2 Status Alert 2 2 4 4 4 Flow Hysteresis 2 2 4 6 Totalizer Limit 2 2 4 5 Totalizer High Limit 2 2 4 5 1 Totalizer Low Limit 2 2 4 5 2 Totalizer Limit Control 2 2 4 5 3 Totalizer Limit Status Alert 2 2 4 5 4 Totalizer Hysteresis 2 2 4 7 Diagnostics Status Alert 2 2 4 8 Enable Diagnostic...

Page 86: ... 2 6 4 2 2 Transmitter 2 2 6 4 2 3 Analog Output Continuous Meter Verification 2 2 6 4 2 4 Coil Drive Frequency 2 2 8 3 Auto Zero 2 2 8 4 Digital Signal Processing DSP Operation 2 2 8 5 DSP Control 2 2 8 6 1 Number of Samples 2 2 8 6 2 Percent of Rate 2 2 8 6 3 Time Limit 2 2 8 6 4 Tag 2 2 9 1 1 Date 2 2 9 3 1 Description 2 2 9 3 2 Message 2 2 9 3 3 Sensor Serial Number 2 2 9 4 1 Sensor Tag 2 2 9 ...

Page 87: ...s Temperature 3 2 2 2 Coil Current 3 2 2 3 Line Noise 3 2 3 1 Electrode Coating Value 3 2 3 2 5 Hz Signal to Noise Ratio 3 2 3 3 1 37 Hz Signal to Noise Ratio 3 2 3 3 2 Signal Power 3 2 3 3 3 Continuous Meter Verification 3 2 4 Baseline Coil Resistance 3 2 4 1 1 Baseline Coil Inductance 3 2 4 1 2 Baseline Electrode Resistance 3 2 4 1 3 Continuous Sensor Measurements 3 2 4 2 Continuous Measured Coi...

Page 88: ...nd 3 3 7 Coil Resistance Trend 3 3 8 Electrode Resistance Trend 3 3 9 Maintenance 3 4 Re Baseline Sensor 3 4 1 1 4 Recall Last Baseline 3 4 1 1 5 No Flow Limit 3 4 1 2 1 Flowing Limit 3 4 1 2 2 Empty Pipe Limit 3 4 1 2 3 Manual Sensor Measurements 3 4 1 3 Manual Measured Coil Resistance 3 4 1 3 1 Manual Measured Coil Inductance 3 4 1 3 2 Manual Measured Electrode Resistance 3 4 1 3 3 Run Manual Me...

Page 89: ...ls 3 4 2 3 1 Electrodes 3 4 2 3 2 Transmitter 3 4 2 3 3 Analog Output Continuous Meter Verification 3 4 2 3 4 4 20 mA Verification 3 4 3 Run Manual 4 20 mA Verification 3 4 3 1 4 mA Measurement 3 4 3 2 12 mA Measurement 3 4 3 3 20 mA Measurement 3 4 3 4 Low Alarm Measurement 3 4 3 5 High Alarm Measurement 3 4 3 6 Analog D A Trim 3 4 4 5 Scaled Analog D A Trim 3 4 4 6 Electronics Digital Trim 3 4 5...

Page 90: ... 2 Totalizer Limit 1 Flow Limit 1 Flow Limit 2 Cont Meter Verification DI DO 1 1 Configure I O 1 2 DIO 1 Control 3 Digital Input 1 4 Digital Output 1 Flow Limit 1 1 Control 1 2 Mode 1 3 High Limit 1 4 Low Limit 1 5 Flow Limit Hysteresis Flow Limit 2 1 Control 2 2 Mode 2 3 High Limit 2 4 Low Limit 2 5 Flow Limit Hysteresis 2 Total Limit 1 Total Control 2 Total Mode 3 Total Hi Limit 4 Total Low Limi...

Page 91: ...lated Velocity 5 Actual Velocity 6 Velocity Deviation 7 Xmter Cal Test Result 8 Sensor Cal Deviation 9 Sensor Cal Test Result Coil Circuit Test Result Electrode Circuit Test Continual Results 1 Continuous Limit 2 Simulated Velocity 3 Actual Velocity 4 Velocity Deviation 5 Coil Signature 6 Sensor Cal Deviation 7 Coil Resistance 8 Electrode Resistance 9 mA Expected mA Actual mA Deviation View Result...

Page 92: ...80 Reference Manual 00809 0300 4750 Rev CA Operation March 2016 Operation Figure 4 10 Field Communicator Dashboard Menu Tree Overview and Configuring Guided Manual Setup ...

Page 93: ...81 Reference Manual 00809 0300 4750 Rev CA Operation March 2016 Operation Figure 4 11 Field Communicator Dashboard Menu Tree Configuring Alert Setup and Service Tools ...

Page 94: ...l min the percent of range is 50 percent Analog output The analog output variable provides the analog value for the flow rate The analog output refers to the industry standard output in the 4 20 mA range The analog output and 4 20 mA loop can be verified using the Analog Feedback diagnostic capability internal to the transmitter See 4 20 mA loop verification on page 123 Pulse output The pulse outp...

Page 95: ...nalog output displays the mA output of the transmitter corresponding to the measured flow rate 4 5 4 Pulse output The pulse output displays the value of the pulse signal LOI menu path N A Traditional Fast Keys 1 1 3 Device dashboard 1 3 LOI menu path N A Traditional Fast Keys 1 1 5 Device dashboard 3 2 1 2 ...

Page 96: ...84 Reference Manual 00809 0300 4750 Rev CA Operation March 2016 Operation ...

Page 97: ...ce Manager ProLink III or through a control system Before operating the Rosemount 8750W in an actual installation you should review all of the factory set configuration data to ensure that they reflect the current application 5 2 Configure outputs The configure outputs functionality is used to configure advanced features that control the analog pulse auxiliary and totalizer outputs of the transmit...

Page 98: ...ar will be the same as those selected under the units parameter The LRV may be set between 39 3 ft s to 39 3 ft s 12 m s to 12 m s or the equivalent range based on the selected flow units There must be at least 1 ft s 0 3 m s span or equivalent between the URV and LRV Alarm type The analog output alarm type displays the position of the alarm switch on the electronics board There are two available ...

Page 99: ...stic alarms that can be configured to drive an analog alarm see Table 5 3 LOI menu path Field Mount Detailed Setup Output Config Analog Alarm Level Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 2 1 8 or 1 4 2 6 Device dashboard 2 2 9 5 2 Table 5 1 Rosemount Values Level 4 20 mA saturation 4 20 mA alarm Low 3 9 mA 3 75 mA High 20 8 mA 22 5 mA Table 5 2 NAMUR Values Level 4 20 mA saturation 4 20...

Page 100: ...o an alarm state when thetotalizervalueexceedsthe parameters set in the total izer limit configuration see page 5 x for more details on this functionality Flow Limit 1 Detailed Setup Output Config Analog AO Diag Alarm Flow Limit 1 1 4 2 1 9 8 Drive to an alarm state when the flow rate exceeds the parameters set in the flow limit 1 configuration see page 5 x for more details on this functionality F...

Page 101: ...cond by 10 000Hz Note The maximum pulse scaling frequency for transmitters with an intrinsically safe output output option code B is 5000 Hz When selecting pulse output scaling the maximum pulse rate is 10 000Hz With the 110 percent over range capability the absolute limit is 11 000Hz For example if you want the Rosemount 8750W to pulse every time 0 01 gallons pass through the sensor and the flow ...

Page 102: ...se the transmitter will limit the pulse output See example below Figure 5 1 Pulse Output Example If pulse width is set to 100 ms the maximum output is 5 Hz for a pulse width of 0 5 ms the maximum output would be 1000 Hz at the maximum frequency output there is a 50 duty cycle To achieve the greatest maximum frequency output set the pulse width to the lowest value that is consistent with the requir...

Page 103: ...gpm and pulse is set for one gallon Assuming the pulse width is 0 5 ms the maximum frequency output is 5 833Hz Frequency Frequency Frequency 5 833 Hz Example The upper range value 20 mA is 3000 gpm To obtain the highest resolution of the pulse output 10 000 Hz is scaled to the full scale analog reading Pulse Scaling Pulse Scaling Pulse Scaling 0 005 1 pulse 0 005 gal 10 000 gpm 60 s min 10 000Hz g...

Page 104: ...e total will only increment with reverse flow if reverse flow is enabled The maximum value for the totalizers is based on 4 294 967 296 232 ft or corresponding unit equivalent If a totalizer reaches this value it will automatically reset to zero and then continue counting The gross forward and reverse totalizers can be reset by manually changing the line size Totalizer units Totalizer units is use...

Page 105: ...enance operations Reset totalizer Reset totalizer resets the net totalizer value to zero The totalizer must be stopped before resetting LOI menu path Field Mount Detailed Setup Output Config Totalizer Setup Total Display Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 3 3 Device dashboard 2 2 1 5 3 LOI menu path Field Mount On totalizer screen press E Wall Mount START STOP Traditional Fast Keys ...

Page 106: ...ransmitter will force the output to zero flow Net Total Reset When conditions are met to activate the input the transmitter will reset the net total value to zero Digital output options Reverse Flow The output will activate when the transmitter detects a reverse flow condition Zero Flow The output will activate when a no flow condition is detected Transmitter Fault The output will activate when a ...

Page 107: ... list above for available discrete output functions Channel 2 Channel 2 is only available as discrete output only Discrete output 2 This parameter displays the configuration for channel 2 Refer to the list above for available discrete output functions LOI menu path Field Mount Detailed Setup Output Config DI DO Config DI O 1 DI O Control Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 2 3 1 1 De...

Page 108: ...e Mode on page 97 Control This parameter turns the flow limit HART alert ON or OFF ON The transmitter will generate a HART alert when the defined conditions are met If a discrete output is configured for flow limit the discrete output will activate when the conditions for mode are met OFF The transmitter will not generate a HART alert for the flow limit Flow 1 Flow 2 LOI menu path Field Mount Deta...

Page 109: ...rt will activate when the measured flow rate exceeds the high limit set point or falls below the low limit set point High limit Set the flow rate value that corresponds to the high limit set point for the flow limit alert Flow 1 Flow 2 LOI menu path Field Mount Detailed Setup Out put Config DI DO Config Flow Limit 1 Mode 1 Wall Mount AUX FUNCTION Field Mount Detailed Setup Out put Config DI DO Con...

Page 110: ...ers for one channel will cause it to also change in the other channel Flow 1 Flow 2 LOI menu path Field Mount Detailed Setup Output Config DI DO Config Flow Limit 1 Low Limit 1 Wall Mount AUX FUNCTION Field Mount Detailed Setup Output Config DI DO Config Flow Limit 2 Low Limit 2 Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 2 3 3 4 1 4 2 3 4 4 Device dashboard 2 2 4 3 2 2 2 4 4 2 Flow 1 Flow 2...

Page 111: ...al mode parameter sets the conditions under which the total limit HART alert will activate High and low limits exist for each channel and can be configured independently High limit The HART alert will activate when the totalizer value exceeds the high limit set point Low limit The HART alert will activate when the totalizer value falls below the low limit set point In range The HART alert will act...

Page 112: ...will activate when a transmitter detects a diagnostic designated as ON OFF The diagnostic status alert will not activate when diagnostics designated as OFF are detected LOI menu path Field Mount Detailed Setup Output Config Totalizer Total Limit Tot Hi Limit Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 2 3 5 3 Device dashboard 2 2 4 5 1 LOI menu path Field Mount Detailed Setup Output Config T...

Page 113: ...ariables The primary variable is fixed to output flow and cannot be configured Primary variable PV The primary variable is configured for flow This variable is fixed and cannot be configured The primary variable is tied to the analog output Electronics Failure Coil Open Circuit Empty Pipe Reverse Flow Ground Wiring Fault High Process Noise Electronics Temperature Out of Range Electrode Coat Limit ...

Page 114: ... variable maps the fourth variable of the transmitter This variable is a HART only variable and can be read from the HART signal with a HART enabled input card or can be burst for use with a HART Tri Loop to convert the HART signal to an analog output Options available for mapping to this variable can be found in Table 5 4 and Table 5 5 LOI menu path Field Mount Detailed Setup Output Config Hart V...

Page 115: ...al 5 3 3 Burst mode The Rosemount 8750W includes a burst mode function that can be enabled to broadcast the primary variable or all dynamic variables approximately three to four times per second Burst mode is a specialized function used in very specific applications The burst mode function enables you to select the variables that are broadcast while in the burst mode Burst mode enables you to set ...

Page 116: ... the number of preambles required by the Rosemount 8750W for HART communications Response preambles Response preambles is the number of preambles sent by the Rosemount 8750W in response to any host request 5 3 4 Configure LOI The LOI configuration contains functionality to configure the display of the transmitter LOI menu path Field Mount Detailed Setup Output Config HART Burst Command Wall Mount ...

Page 117: ...r screen has two lines of information Choose one of the following options Forward Total and Reverse Total Net Total and Gross Total Language Use language to configure the display language shown on the LOI Select one of the following options English 1 Spanish Portuguese German French LOI menu path Field Mount Detailed Setup LOI Config Flow Display Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 3...

Page 118: ...lse rate of the coils Choose one of the following options 5 Hz The standard coil drive frequency is 5 Hz which is sufficient for nearly all applications 37 Hz If the process fluid causes a noisy or unstable output increase the coil drive frequency to 37 5 Hz The 37 Hz coil drive frequency should only be used for sensor sizes 16 in and smaller If the 37 Hz mode is selected perform the auto zero fun...

Page 119: ... to count in the reverse direction 5 4 4 Low flow cutoff Low flow cutoff allows the user to set a low flow limit to be specified The analog output signal is driven to 4mA for flow rates below the set point For the Field Mount Transmitter the low flow cutoff units are the same as the PV units and cannot be changed For the Wall Mount Transmitter the low flow cutoff units are feet per second and cann...

Page 120: ...nt 8750W microprocessor can actually scrutinize each input based on three user defined parameters to reject the noise specific to the application See Section 7 for the detailed description of how the signal processing works Operating mode The operating mode function can be set to normal mode or filter mode If set to normal mode and the signal is noisy and provides an unstable flow reading switch t...

Page 121: ...r an integer value between 0 and 125 The default value is 90 samples Percent rate This parameter will set the tolerance band on either side of the running average referring to percent deviation from the average flow rate Values within the limit are accepted while values outside the limit are scrutinized to determine if they are a noise spike or an actual flow change This parameter can be configure...

Page 122: ...6 seconds The default value is two seconds 5 5 Configure special units Special units are used when the application requires units that are not included in the flow units available from the device Refer to Table 2 12 on page 34 for a complete list of the available units 5 5 1 Base volume unit Base volume unit is the unit from which the conversion is being made Set this variable to the appropriate o...

Page 123: ...ble The actual special units setting you define will not appear Four characters are available to store the new units designation The Rosemount 8750W LOI will display the four character designation as configured Example To display flow in acre feet per day and acre foot is equal to 43560 cubic feet the procedure would be 1 Set the volume unit to ACFT 2 Set the base volume unit to ft3 3 Set the conv...

Page 124: ...112 Reference Manual 00809 0300 4750 Rev CA Advanced Configuration Functionality March 2016 Advanced Configuration Functionality ...

Page 125: ... 137 6 1 Introduction Rosemount Magnetic Flowmeters provide device diagnostics that detect and warn of abnormal situations throughout the life of the meter from Installation to Maintenance and Meter Verification With flowmeter diagnostics enabled plant availability and throughput can be improved and costs through simplified installation maintenance and troubleshoot ing can be reduced Table 6 1 Dia...

Page 126: ... SMART Meter Verification store the results and print a report that can be filed or submitted as proof of verification 6 2 Licensing and enabling All advanced diagnostics are licensed by ordering option code DA1 DA2 or both In the event that a diagnostic option is not ordered advanced diagnostics can be licensed in the field through the use of a license key Each transmitter has a unique license ke...

Page 127: ...ant in batching applications where the pipe may run empty with some regularity If the pipe is empty this diagnostic will activate set the flow rate to zero and deliver an alert LOI menu path Field Mount Detailed Setup Device Info Revision Num Wall Mount AUX FUNCTION Traditional Fast Keys 1 4 6 10 1 1 This item is in a list format without numeric labels Device dashboard 1 8 2 LOI menu path Field Mo...

Page 128: ...iables such as sensor type line size process fluid properties and wiring If the empty pipe value exceeds the empty pipe trigger level for a specified number of updates then the empty pipe diagnostic alert will activate Empty pipe EP trigger level Limits 3 to 2000 Empty pipe trigger level is the threshold limit that the empty pipe value must exceed before the empty pipe diagnostic alert activates T...

Page 129: ... the empty pipe value with an empty pipe condition Example Empty reading 80 0 3 Set the empty pipe trigger level to a value between the full and empty readings For increased sensitivity to empty pipe conditions set the trigger level to a value closer to the full pipe value Example Set the trigger level to 25 0 4 Set the empty pipe counts to a value corresponding to the desired sensitivity level fo...

Page 130: ...nd 60 Hz which are the common AC cycle frequencies found throughout the world If the amplitude of the signal at either of these frequencies exceeds 5 mV that is an indication that there is a ground or wiring issue and that stray electrical signals are getting into the transmitter The diagnostic alert will activate indicating that the ground and wiring of the installation should be carefully review...

Page 131: ... 5 mV then the ground wiring fault diagnostic alert will activate 6 6 High process noise detection The high process noise diagnostic detects if there is a process condition causing an unstable or noisy reading that is not an actual flow variation A common cause of high process noise is slurry flow like pulp stock or mining slurries Other conditions that cause this diagnostic to activate are high l...

Page 132: ...tive to the amount of process noise If the transmitter is operating in 5 Hz mode and the signal to noise ratio remains below 25 for one minute then the high process noise diagnostic alert will activate 37 Hz signal to noise ratio SNR This parameter shows the current value of the signal to noise ratio at the coil drive frequency of 37 Hz This is a read only value This number is a measure of the sig...

Page 133: ...7 1 Turning coated electrode detection on off The coated electrode detection diagnostic can be turned on or off as required by the application If the advanced diagnostics suite 1 DA1 option was ordered then the coated electrode detection diagnostic will be turned on If DA1 was not ordered or licensed this diagnostic is not available 6 7 2 Coated electrode parameters The coated electrode detection ...

Page 134: ...g EC The maximum electrode coating value reads the maximum value of the coated electrode detection diagnostic since the last maximum value reset Clear maximum electrode value Use this method to reset the maximum electrode coating value LOI menu path Field Mount Diagnostics Advanced Diag Elec Coat EC Limit 1 Wall Mount N A Traditional Fast Keys 1 2 3 1 2 Device dashboard 2 2 5 6 2 LOI menu path Fie...

Page 135: ... mA 20 mA Low alarm level High alarm level 6 8 1 Initiating 4 20 mA loop verification The 4 20 mA loop verification diagnostic can be initiated as required by the application If the advanced diagnostics suite 2 DA2 Option was ordered then the 4 20 mA loop verification diagnostic will be available If DA2 was not ordered or licensed this diagnostic is not available 6 8 2 4 20 mA loop verification pa...

Page 136: ...n test High alarm measurement Shows the measured value of the high alarm verification test 6 9 SMART Meter Verification The SMART Meter Verification diagnostic provides a means of verifying the flowmeter is within calibration without removing the sensor from the process This diagnostic test LOI menu path N A Traditional Fast Keys N A Device dashboard 3 4 3 2 LOI menu path N A Traditional Fast Keys...

Page 137: ...nal to the magnetic field strength Thus any changes in the magnetic field will result in a calibration shift of the sensor Having the transmitter take an initial sensor signature when first installed will provide the baseline for the verification tests that are done in the future There are three specific measurements that are stored in the transmitter s non volatile memory that are used when perfo...

Page 138: ...here is flow in the line is permissible but this may introduce some noise into the electrode circuit resistance measurement If an empty pipe condition exists then the sensor signature should only be run for the coils Once the sensor signature process is complete the measurements taken during this procedure are stored in non volatile memory to prevent loss in the event of a power interruption to th...

Page 139: ...or this value is set to five percent with limits configurable between one and ten percent This parameter applies to manually initiated tests only Empty pipe limit Set the test criteria for the empty pipe condition The factory default for this value is set to five percent with limits configurable between one and ten percent This parameter applies to manually initiated test only LOI menu path Field ...

Page 140: ...and no flow in the line Running the SMART Meter Verification test under this condition provides the most accurate results and the best indication of magnetic flowmeter health Flowing full Run the SMART Meter Verification test with a full pipe and flow in the line Running the SMART Meter Verification test under this condition provides the ability to verify the magnetic flowmeter health without shut...

Page 141: ...the test criteria selected when the verification test was initiated This setting applies to manually initiated tests only Sensor Run the SMART Meter Verification test on the sensor only This results in the verification test checking the sensor calibration to the limits of the test criteria selected when the SMART Meter Verification test was initiated verifying the coil circuit health and the elect...

Page 142: ... monitor the analog output signal by enabling this continuous SMART Meter Verification parameter LOI menu path Field Mount Diagnostics Diag Controls Cont Meter Ver Coils Wall Mount N A Traditional Fast Keys 1 2 1 3 1 Device dashboard 2 2 6 4 2 1 LOI menu path Field Mount Diagnostics Diag Controls Cont Meter Ver Electrodes Wall Mount N A Traditional Fast Keys 1 2 1 3 2 Device dashboard 2 2 6 4 2 2 ...

Page 143: ...ters are viewed as a method using the left arrow key to cycle through the results In AMS Device Manager the Calibration Verification Report on page 137 is populated with the necessary data eliminating the need to manually complete the report When using AMS Device Manager there are two possible methods that can be used to print the report Method one involves using the print functionality within the...

Page 144: ...Circuit Test Result Coil Circuit 1 2 3 2 2 1 1 3 4 1 5 1 3 11 Electrode Circuit Test Result Electrode Ckt 1 2 3 2 2 1 1 3 4 1 5 1 6 Table 6 3 Continuous Smart Meter Verification Test Result Parameters 1 1 Only available on Field Mount Transmitter Parameter Field mount LOI menu path Diagnostics Variables MV Results Continual Res Traditional Fast Keys Device Dashboard Fast Keys 1 Continuous Limit Te...

Page 145: ...nuously monitored using continuous SMART Meter Verification Coil signature The coil signature is a measurement of the magnetic field strength This value is compared to the coil signature baseline measurement taken during the sensor signature process to determine sensor calibration deviation This value can be continuously monitored using continuous SMART Meter Verification Manual Continuous LOI men...

Page 146: ...ter calibration verification test This value can be continuously monitored using continuous SMART Meter Verification Manual Continuous LOI menu path Field Mount Diagnostics Advanced Diag Meter Verify Measurements Manual Measure Electrode Res Wall Mount XMTR INFO Field Mount Diagnostics Advanced Diag Meter Verify Measurements Continual Meas Electrode Res Wall Mount N A Traditional Fast Keys 1 2 3 2...

Page 147: ...alog output verification test This value can be continuously monitored using continuous SMART Meter Verification Manual Continuous LOI menu path Field Mount Diagnostics Advanced Diag 4 20 mA Verify View Results Wall Mount N A Field Mount Diagnostics Advanced Diag Meter Verify Measurements Continual Meas 4 20 mA Expect Wall Mount N A Traditional Fast Keys 1 2 3 3 2 1 2 3 2 5 2 5 Device dashboard N ...

Page 148: ...o comply with the necessary plant standards Example A food and beverage company requires an annual calibration of a meter on a product line The plant standard calls for the accuracy to be three percent or better They manufacture this product in batches and the measurement cannot be interrupted when a batch is in process When the batch is complete the line goes empty Since there is no means of perf...

Page 149: ...______________________________ PV Damping _____________________________________________________ Transmitter calibration verification results Sensor calibration verification results Simulated Velocity ___________________________ Sensor Deviation ________________________________________________ Actual Velocity ______________________________ Sensor Test PASS FAIL NOT TESTED Deviation ________________...

Page 150: ...138 Reference Manual 00809 0300 4750 Rev CA Advanced Diagnostics Configuration March 2016 Advanced Diagnostics Configuration ...

Page 151: ...ides a detailed description of the digital signal processing functionality 7 2 Safety messages Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations Read the following safety messages before performing any operation described in this section Explosions could result in death or serious injury Verify the operating ...

Page 152: ... that is relatively constant over the frequency range Common sources of white noise include chemical reactions or mixing that occurs as the fluid passes through the flowmeter and high concentration slurry flows where the particulates are constantly passing over the electrode head An example of this type of flow stream would be a basis weight stream in a paper mill 7 4 High process noise diagnostic...

Page 153: ...ome cases the effects of process noise may be sharply reduced by elevating the coil drive frequency above the 15 Hz region The Rosemount 8750W coil drive mode is selectable between the standard 5 Hz and the noise reducing 37 Hz The 37 Hz coil drive frequency should only be used on sensor sizes 16 in and smaller 7 5 1 Coil drive frequency This parameter changes the pulse rate of the magnetic coils ...

Page 154: ...The Rosemount 8750W contains several advanced functions that can be used to stabilize erratic outputs caused by process noise The signal processing menu contains this functionality If the 37 Hz coil drive frequency has been set and the output is still unstable the damping and signal processing function should be used It is important to set the coil drive frequency to 37 Hz to increase the flow sam...

Page 155: ...ts Signal processing is a software algorithm that examines the quality of the electrode signal against user specified tolerances The three parameters that make up signal processing number of samples maximum percent limit and time limit are described below Number of samples The number of samples sets the amount of time that inputs are collected and used to calculate the average value Each second is...

Page 156: ...length of the running average If the number of samples selected is 100 then the response time of the system is 10 seconds In some cases this may be unacceptable Setting the time limit forces the Rosemount 8750W to clear the value of the running average and re establish the output and average at the new flow rate once the time limit has elapsed This parameter limits the response time added to the l...

Page 157: ...tside the tolerance band and therefore is held in memory until the next input can be evaluated The running average is provided as the output 3 The previous signal currently held in memory is simply rejected as a noise spike since the next flow input signal is back within the tolerance band This results in complete rejection of noise spikes rather than allowing them to be averaged with the good sig...

Page 158: ...146 Reference Manual 00809 0300 4750 Rev CA Digital Signal Processing March 2016 Digital Signal Processing ...

Page 159: ...ppropriate throughout this section 8 2 Safety information Failure to follow these guidelines could result in death or serious injury Installation and servicing instructions are for use by qualified personnel only Do not perform any servicing other than that contained in the operating instructions unless qualified Verify the operating environment of the sensor and transmitter is consistent with the...

Page 160: ...k of the LOI into the receptacle on the electronics stack The LOI can be rotated in 90 degree increments to provide the best viewing position Rotate the LOI to the desired orientation taking care to not exceed 360 degrees of rotation Exceeding 360 degrees of rotation could damage the LOI cable and or connector 6 Once the serial connector is installed on the electronics stack and the LOI is oriente...

Page 161: ...50WM Transmitter Follow the steps below to confirm the transmitter housing is compatible with this electronics kit 1 Verify the model number is Rosemount 8750WM If the transmitter model is not Rosemount 8750WM then these electronics are not compatible See Figure 8 2 for the location of the model number Consult the Rosemount 8750W Product Data Sheet document number 00813 0100 4750 for details on or...

Page 162: ...oard pictured then the electronics are not compatible Figure 8 3 Field Mount Transmitter Housing Electronics Board Identification A Key indicators 3 Confirm the electronics stack is for an Rosemount 8750W Transmitter Refer to the picture on the left in Figure 8 4 Figure 8 4 Field Mount Electronics Stack Identification Rosemount 8732EM housing Correct Rosemount 8732ES housing Incorrect Rosemount 87...

Page 163: ...ng screws and the two divider mounting screws if applicable 3 Remove the coil and electrode wire clips 8 5 2 Installing the terminal block 1 Connect the coil and electrode clips to the new terminal block 2 Press the terminal block into its keyed position and tighten the two mounting screws Install the divider with the two mounting screws if applicable 3 Reconnect remote cabling and replace junctio...

Page 164: ...lete the output trim function 1 Set the loop to manual if necessary 2 Connect a precision ammeter in the 4 20mA loop 3 Initiate the D A trim function 4 Enter the 4mA meter value when prompted to do so 5 Enter the 20mA meter value when prompted to do so 6 Return the loop to automatic control if necessary The 4 20mA trim is now complete The D A trim can be repeated to check the results Alternatively...

Page 165: ...he voltmeter 8 6 3 Digital trim Digital trim is the function by which the factory calibrates the transmitter This procedure is rarely needed by users It is only necessary if the Rosemount 8750W is suspected to be no longer accurate A Rosemount 8714D Calibration Standard is required to complete a digital trim Attempting a digital trim without a Rosemount 8714D Calibration Standard may result in an ...

Page 166: ... URV and PV LRV are located in Basic setup on page 32 Instructions for changing the coil drive frequency can be found on Coil drive frequency on page 106 Set the loop to manual if necessary and then complete the following steps 1 Power down the transmitter 2 Connect the transmitter to a Rosemount 8714D Calibration Standard 3 Power up the transmitter with the Rosemount 8714D connected and read the ...

Page 167: ...ounting the revolutions of a centrifugal pump or by performing a bucket test to determine how fast a given volume is filled by the process fluid 2 Complete the universal auto trim function When the routine is completed the sensor is ready for use 8 7 Review The 8750W includes a capability to review the configuration variable settings The flowmeter configuration parameters set at the factory should...

Page 168: ...156 Reference Manual 00809 0300 4750 Rev CA Maintenance March 2016 Maintenance ...

Page 169: ...hroughout this section The Rosemount 8750W performs self diagnostics on the entire magnetic flowmeter system the transmitter the sensor and the interconnecting wiring By sequentially trouble shooting each individual piece of the magmeter system it becomes easier to identify the problem and make the appropriate adjustments If there are problems with a new magmeter installation see Installation chec...

Page 170: ... is listed on the sensor nameplate 4 Verify the analog range of the transmitter matches the analog range in the control system 5 Verify the forced analog output and forced pulse output of the transmitter produces the correct output at the control system 6 If desired use a Rosemount 8714D to verify the transmitter calibration 9 3 2 Sensor Be sure that power to magnetic flowmeter system is removed b...

Page 171: ...cable wiring 5 Verify there is minimal exposed wiring and shielding Less than 1 in 25 mm is recommended 6 The single conduit that houses both the electrode signal and coil drive cables should not contain any other wires This includes wires from other magmeters Note For installations requiring intrinsically safe electrodes the signal and coil drive cables must be run in Individual conduits 9 3 4 Pr...

Page 172: ...factory for fuse replacement Auto Zero Failure Flow is not set to zero Force flow to zero perform auto zero trim Unshielded cable in use Change wire to shielded cable Moisture problems See Table 9 8 on page 175 Auto Trim Failure No flow in pipe while performing Universal Auto Trim Establish a known flow rate and perform universal auto trim calibration Wiring error Check that wiring matches appropr...

Page 173: ... greater than 43 ft sec Lower flow velocity increase pipe diameter Improper wiring Check coil drive wiring and sensor coils Perform sensor tests see Table 9 8 on page 175 Digital Trim Failure Cycle power to clear messages no changes were made The calibrator 8714B C D is not connected properly Review calibrator connections Incorrect calibration number entered into transmitter Replace sensor calibra...

Page 174: ...ross the analog output terminals Disable message using LOI Error Mask parameter Transmitter failure Replace the electronics stack Electrode Saturation 1 Improper wiring See Wiring the transmitter on page 19 Improper process reference See Process reference connection on page 17 Improper earth grounding Verify earth ground connections see Wiring the transmitter on page 19 Application requires specia...

Page 175: ...lection Guide document number 00816 0100 3033 Gas air in line Move the sensor to another location in the process line to ensure that it is full under all conditions Electrode coating Enable coated electrode detection diagnostic Use bullet nose electrodes Downsize sensor to increase flowrate above 3 ft s 1 m s Periodically clean sensor Styrofoam or other insulating particles Complete the possible s...

Page 176: ...rent loop Transmitter failure Perform transmitter self test Perform manual analog loop test and D A trim if necessary Replace the electronics board Continuous Meter Verification Error 1 Transmitter calibration verification test failed Verify pass fail criteria Run manual SMART Meter Verification 8714i under no flow conditions Verify calibration using 8714D Calibration Standard Perform digital trim...

Page 177: ...block of the sensor or shorted coil Perform sensor tests see Table 9 8 on page 175 If the problem persists replace the sensor Coil Signature Out of Spec 1 Moisture in the terminal block of the sensor or shorted coil Perform sensor tests see Table 9 8 on page 175 If the problem persists replace the sensor Calibration shift caused by heat cycling or vibration Perform sensor tests see Table 9 8 on pa...

Page 178: ...ed properly Shielding should be stripped back less than 10 in 25 mm 5 Use separate shielded twisted pairs for wiring between sensor and transmitter 6 Properly connect the wiring between the sensor and the transmitter Corresponding terminal block numbers in the sensor and transmitter must be connected 9 4 3 Troubleshooting high process noise The transmitter detected high levels of process noise If ...

Page 179: ...on The Rosemount High Signal system is comprised of the 8707 sensor which has modified coils and magnetics and the 8712H High Signal transmitter Note In applications where very high levels of noise are a concern it is recommended that a dual calibrated Rosemount High Signal 8707 sensor be used These sensors can be calibrated to run at lower coil drive current supplied by the standard Rosemount tra...

Page 180: ...ating is starting to build up on the electrode and may interfere with the flow measurement signal Process fluid conductivity has decreased to a level close to operational limits of the meter Verify process fluid conductivity Schedule maintenance to clean the electrodes Use bullet nose electrodes Replace the meter with a smaller diameter meter to increase the flow velocity to above 3 ft s 1 m s Ele...

Page 181: ...ter drift Faulty electronics Rerun SMART Meter Verification 8714i under No Flow conditions Check the transmitter calibration with the 8714D Calibration Standard Perform a digital trim Replace the electronics stack Sensor Calibration Verification Moisture in the sensor terminal block Calibration shift caused by heat cycling or vibration Rerun SMART Meter Verification 8714i Perform the sensor checks...

Page 182: ...ssary Output at 4 mA Transmitter in multidrop mode Configure Poll Address to 0 to take transmitter out of multidrop mode Low Flow Cutoff set too high Configure Low Flow Cutoff to a lower setting or increase flow to a value above the low flow cutoff PZR Activated Open PZR switch at terminals 5 and 6 to deactivate the PZR Flow is in reverse direction Enable Reverse Flow function Shorted coil Coil ch...

Page 183: ...failure Verify transmitter operation with an 8714D Calibration Standard or replace the electronics stack Pulse output incorrectly configured Review configuration and correct as necessary Communication problems with the Field Communicator 4 20 mA output configuration Check analog power switch internal external The Field Communicator requires a 4 20 mA output to function Communication interface wiri...

Page 184: ...nsor to a new location with five pipe diameters upstream and two pipe diameters downstream if possible Cables for multiple magmeters run through same conduit Use dedicated conduit run for each sensor and transmitter Improper wiring If electrode shield and electrode signal wires are switched flow indication will be about half of what is expected Check wiring diagrams Flow rate is below 1 ft s speci...

Page 185: ...ium to low conductivity fluids 10 25 microsiemens cm combined with cable vibration or 60 Hz interference Eliminate cable vibration Move cable to lower vibration run Tie down cable mechanically Use an integral mount Trim electrode and coil wires see Cable preparation on page 23 Route cable line away from other equipment powered by 60 Hz Use component cable see Table 2 12 on page 34 Electrode incomp...

Page 186: ...the health of individual components The tests will require the use of a digital multimeter capable of measuring conductance in nanosiemens and an LCR meter A sensor circuit diagram is shown in Figure 9 1 The tests described below will check for continuity or isolation of the internal components of the sensor Figure 9 1 Sensor Circuit Diagram Simplified A Electrodes B Coils c Sensor housing A B C ...

Page 187: ...lue Potential cause Corrective action A Sensor coil Installed or uninstalled Multimeter 1 and 2 R 2 Ω R 18 Ω Open or shorted coil Remove and replace sensor B Shields to case Installed or uninstalled Multimeter 17 and 3 3 and case ground 17 and case ground 0 3 Ω Moisture in terminal block Leaky electrode Process behind liner Clean terminal block Remove sensor C Coil to coil shield Installed or unin...

Page 188: ...test the sensor a multimeter capable of measuring conductance in nanosiemens is preferred Conductance is the reciprocal of resistance Or 1 nanosiemens 1 nanosiemens Figure 9 2 Coil and Electrode Lead Wire Clips A Electrode lead wire B Coil lead wire C Open slot 1 1gigaohm 1 1 10 9 ohm A B C ...

Page 189: ...eter If you cannot determine the front of the meter measure both electrodes One electrode should result in an open reading while the other electrode should be less than 1 1Ω Shorted electrode Open electrode Coated electrode Replace sensor Remove coating from sensor wall B Terminal to back electrode Uninstalled Multimeter 19 and electrode 19 1 1Ω Shorted electrode Open electrode Coated electrode Re...

Page 190: ...the product being returned was exposed to a hazardous substance as defined by OSHA a copy of the required Material Safety Data Sheet MSDS for each hazardous substance identified must be included with the returned goods The North American Response Center will detail the additional information and procedures necessary to return goods exposed to hazardous substances North and South America Europe and...

Page 191: ... limits Process liquid must have a conductivity of 5 microsiemens cm 5 micromhos cm or greater Power supply 90 250 VAC 50 60 Hz or 12 42 VDC Line power fuses 90 250 VAC systems 1A 250V I2t 1 5 A2s Rating Fast Acting Bussman AGC 1 Littelfuse 31201 5HXP 12 42 VDC systems 3 Amp 250V I2t 14 A2s Rating Fast Acting Bel Fuse 3AG 3 R Littelfuse 312003P Schurter 0034 5135 Power consumption 15 W maximum DC ...

Page 192: ...urst currents IEC 61000 4 5 for surge currents IEC 611185 2 2000 Class 3 up to 2 kV and up to 2 kA protection Turn on time Five minutes to rated accuracy from power up Five seconds from power interruption Start up time 50ms from zero flow Low flow cut off Adjustable between 0 01 and 38 37 ft s 0 003 and 11 7 m s Below selected value output is driven to the zero flow rate signal level Overrange cap...

Page 193: ...owered Input 5 28 VDC Output testing Analog output test Transmitter may be commanded to supply a specified current between 3 5 and 23 mA Pulse output test Transmitter may be commanded to supply a specified frequency between 1 and 10 000 Hz Optional discrete output function AX option Externally powered at 5 28 VDC 240 mA max solid state switch closure to indicate either Reverse flow Activates switc...

Page 194: ...hout calculations or a compromise in standard accuracy Rosemount 8750W transmitters and other manufacturers sensors can be calibrated at known process conditions or at the Rosemount NIST Traceable Flow Facility Transmitters calibrated on site require a two step procedure to match a known flow rate This procedure can be found in the operations manual A 1 5 Performance specifications System specific...

Page 195: ...um approximately 7 lbs 3 2 kg Add 1 pound 0 5 kg for display option code M4 or M5 A 2 Wall mount transmitter specifications A 2 1 Functional specifications Transmitter coil drive current 500 mA Flow rate range Capable of processing signals from fluids that are traveling between 0 04 and 39 ft s 0 01 to 12 m s for both forward and reverse flow in all sensor sizes Full scale continuously adjustable ...

Page 196: ...t protection rating Built in transient protection that conforms to IEC 61000 4 4 for burst currents IEC 61000 4 5 for surge currents Turn on time Five minutes to rated accuracy from power up Five seconds from power interruption Start up time 50ms from zero flow Low flow cut off Adjustable between 0 01 and 38 37 ft s 0 003 and 11 7 m s Below selected value output is driven to the zero flow rate sig...

Page 197: ... signal is superimposed on the 4 20 mA signal and is available for the control system interface A minimum of 250 Ohms loop resistance is required for HART communications Scalable pulse frequency adjustment 0 10 000 Hz switch selectable as internally or externally powered Pulse value can be set to equal desired volume in selected engineering units Pulse width adjustable from 0 1 to 650 ms Internall...

Page 198: ...ty of sensors without calculations or a compromise in standard accuracy Rosemount 8750W transmitters and other manufacturers sensors can be calibrated at known process conditions or at the Rosemount NIST Traceable Flow Facility Transmitters calibrated on site require a two step procedure to match a known flow rate This procedure can be found in the operations manual A 2 5 Performance specification...

Page 199: ...imately 9 lbs 4 0 kg Add 1 pound 0 5 kg for display option code M4 or M5 A 3 Sensor specifications A 3 1 Functional specifications Service Utility water and wastewater fluids Line sizes 1 2 in to 48 in 15 mm to 1200 mm Sensor coil resistance 9 17 Ω Interchangeability Rosemount 8750W Sensors are interchangeable with Rosemount 8750W Transmitters System accuracy is maintained regardless of line size ...

Page 200: ...red Sensor temperature vs pressure limits for ASME B16 5 Class Flanges 1 2 to 24 in line sizes Flange material Flange rating Pressure 20 to 100 F 29 to 38 C 200 F 93 C 300 F 149 C Carbon Steel Class 150 285 psi 260 psi 230 psi Class 300 740 psi 675 psi 655 psi 304 Stainless Steel Class 150 275 psi 235 psi 205 psi Class 300 720 psi 600 psi 530 psi Table A 2 Temperature vs Pressure Limits for AS2129...

Page 201: ...mm 900 mm 1000 mm PN 25 8 in to 24 in 200 mm to 600 mm PN40 1 2 in to 24 in 15 mm to 600 mm AS2129 Table D and E 1 2 in to 40 in 48 in 15 mm to 1000 mm 1200 mm AS4087 PN16 PN21 2 in to 40 in 48 in 8 in excluded 50 mm to 1000 mm 1200 mm PN35 2 in to 36 in 8 in excluded 50 mm to 900 mm GB T9119 PN10 8 in to 24 in 36 in 40 in 48 in 200 mm to 600 mm 900 mm 1000 mm 1200 mm PN16 4 in to 24 in 36 in 40 i...

Page 202: ...arly to the measurement electrodes through the sensor lining on Rosemount 8750W sensors It will be made of the same material as the measurement electrodes Grounding rings optional Grounding rings can be installed between the flange and the sensor face on both ends of the sensor Single ground rings can be installed on either end of the sensor They have an I D slightly larger than the sensor I D and...

Page 203: ...stom Union Russia Belarus and Kazakhstan FM 3030548 FM or 70030489 CSA Z1 ATEX Non Sparking and Dust for Non Flammable Fluids EU DEKRA 15ATEX0003 X ND ATEX Dust EU DEKRA 15ATEX0003 X Z2 InMetro Non Sparking and Dust for Non Flammable Fluids Brazil PENDING 3 3 Planned submittal or in process with Agency PENDING Z3 NEPSI Non Sparking and Dust for Non Flammable Fluids China NEPSI GYJ15 1228X Z5 DIP D...

Page 204: ... standards FM Approved United States Compliance with the applicable ANSI standards CSA US United States C Canada Indicates that the product was tested and has met the applicable certification requirements for the noted countries Eurasian Conformity EAC Eurasian Customs Union Russia Belarus and Kazakhstan Compliance with all of the applicable technical regulations of the EAC Customs Union INMETRO B...

Page 205: ...ctice SEP Flowtubes that are SEP are outside the scope of PED and cannot be marked for compliance with PED B 2 Certifications B 2 1 Factory Mutual FM Ordinary Location Certification for FM Approvals As standard the transmitter and flowtube have been examined and tested to determine that the design meets basic electrical mechanical and fire protection requirements by FM Approvals a nationally recog...

Page 206: ...Groups ABCD T4 Dust Ignition Proof for Class II III Division 1 Groups EFG T4 29 C Ta 60 C Transmitter mount codes T or R 29 C Ta 40 C Transmitter mount code W Enclosure Type 4X IP66 68 69K 1 Install per drawing 8750W 1051 Special Condition for Safe Use X 1 Flowtube to be used only in a non flammable process 1 The transmitter is rated IP66 when integral or remote mounted it is not IP68 nor IP69K ra...

Page 207: ...195 Product Certifications Product Certifications March 2016 Reference Manual 00809 0300 4750 Rev CA Figure B 1 Rosemount 8750W Declaration of Conformity ...

Page 208: ...Product Certifications March 2016 Reference Manual 00809 0300 4750 Rev CA 196 Product Certifications ...

Page 209: ...197 Product Certifications Product Certifications March 2016 Reference Manual 00809 0300 4750 Rev CA ...

Page 210: ...is must be taken into account upon installation 3 Conduit entries must be installed to maintain the enclosure ingress rating of IP66 Transmitter and Flow Tube IP68 or IP69K Flow Tube as applicable 4 The flow tube and transmitter are not allowed to be thermally insulated e Where necessary the essential characteristics of tools which may be fitted to the equipment i No proprietary tools required f L...

Page 211: ...th IEC 61010 1 0 Spare transmitter no flow tube VII Line size 005 to 480 1 2 in NPS 15 mm to 48 in NPS 1200 mm 000 Spare transmitter no flow tube VIII Safety approvals Z1 ATEX II 3 GEx nA ic IIC T4 Gc 1 II 3 GEx nA ic IIC T5 T4 Gc 2 II 3 DEx tc IIIC T80 C T130 C Dc 3 Z7 IECEx Ex nA ic IIC T4 Gc 1 Ex nA ic IIC T5 T4 Gc 2 Ex tc IIIC T80 C T130 C Dc 3 ND ATEX II 3 DEx tc IIIC T80 C T130 C Dc 3 NF IEC...

Page 212: ...Product Certifications March 2016 Reference Manual 00809 0300 4750 Rev CA 200 Product Certifications ...

Page 213: ... 2016 Reference Manual 00809 0300 4750 Rev CA 201 Wiring Diagrams Appendix C Wiring Diagrams Figure C 1 Rosemount 8750W Transmitter Installation and Wiring ronic Master PRINTED COPIES ARE UNCONTROLLED Rosemount Proprietary ...

Page 214: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 202 Wiring Diagrams ...

Page 215: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 203 Wiring Diagrams Electronic Master PRINTED COPIES ARE UNCONTROLLED Rosemount Proprietary ...

Page 216: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 204 Wiring Diagrams ctronic Master PRINTED COPIES ARE UNCONTROLLED Rosemount Proprietary ...

Page 217: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 205 Wiring Diagrams Figure C 2 FM Hazardous Location Installation ...

Page 218: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 206 Wiring Diagrams ...

Page 219: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 207 Wiring Diagrams ...

Page 220: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 208 Wiring Diagrams ...

Page 221: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 209 Wiring Diagrams Figure C 3 IEC EC and ATEX Hazardous Area Installation ...

Page 222: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 210 Wiring Diagrams ...

Page 223: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 211 Wiring Diagrams ...

Page 224: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 212 Wiring Diagrams ...

Page 225: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 213 Wiring Diagrams ...

Page 226: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 214 Wiring Diagrams Figure C 4 CSA Hazardous Area Installation ...

Page 227: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 215 Wiring Diagrams ...

Page 228: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 216 Wiring Diagrams ...

Page 229: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 217 Wiring Diagrams ...

Page 230: ...al Analog Power Wiring guide Red to XMTR pin 1 Black to XMTR pin 2 and 250 Ω Yellow to 250 Ω Green to XMTR housing White no connection A AC neutral or DC B AC line or DC C Transmitter power D 250 Ω E THUM Adapter Wiring guide White to XMTR pin 1 Yellow to XMTR pin 2 Red to 250 Ω to 4 20 mA Black to 4 20 mA Green to XMTR housing A AC neutral or DC B AC line or DC C Transmitter power D 250 Ω E 4 20 ...

Page 231: ...anual 00809 0300 4750 Rev CA 219 Wiring Diagrams C 2 475 Field Communicator Figure C 7 475 Field Communicator with Field Mount Internal Analog Power A AC neutral or DC B AC line or DC C Transmitter power D 475 Field Communicator A B C RL D ...

Page 232: ...ence Manual 00809 0300 4750 Rev CA 220 Wiring Diagrams Figure C 8 475 Field Communicator with Field Mount External Analog Power A AC neutral or DC B AC line or DC C Transmitter power D 475 Field Communicator E 24 VDC A B C E D D RL or ...

Page 233: ...section D 1 1 Universal capability The Rosemount 8750W Transmitter has the ability to drive other manufacturers sensors and report a flow rate In addition to providing a flow measurement all of the diagnostic functionality is also available in a universal application This capability can provide additional information into the installation process and meter health in addition to enabling a common m...

Page 234: ...m process In addition to the universal trim there are two other methodologies for determining a calibration number for the sensor Method 1 Have the sensor sent to a Rosemount service center for determination of a calibration number compatible with the universal transmitter This is the most accurate method for determining the calibration number and will provide a 0 5 of rate measurement accuracy fr...

Page 235: ...o that manufacturer s sensors is provided If the manufacturer for the existing sensor is not included see the drawing for generic connections Any trademarked names used herein regarding sensors not manufactured by Rosemount are owned by the particular manufacturer of the sensor Table D 1 Transmitter and Sensor Reference Rosemount transmitter Sensor manufacturer Page number Rosemount Rosemount 8750...

Page 236: ...eneric Wiring for Sensors page 241 Krohne Rosemount 8750W Generic Wiring for Sensors page 242 Taylor Rosemount 8750W Series 1100 page 244 Rosemount 8750W Generic Wiring for Sensors page 244 Yamatake Honeywell Rosemount 8750W Generic Wiring for Sensors page 245 Yokogawa Rosemount 8750W Generic Wiring for Sensors page 246 Generic manufacturer wiring Rosemount 8750W Generic Wiring for Sensors page 24...

Page 237: ... transmitter Connect coil drive and electrode cables as shown in Figure D 1 on page 225 Figure D 1 Wiring to a Rosemount 8750W Transmitter Table D 2 Rosemount 875W Sensor Wiring Connections Rosemount 8750W Transmitters Rosemount 8750W Sensors 1 1 2 2 3 3 17 17 18 18 19 19 Do not connect mains or line power to the magnetic flowtube sensor or to the transmitter coil excitation circuit ...

Page 238: ...configured for series connection Other manufacturers sensors may be wired in either a series or parallel circuit All Rosemount magnetic sensors are wired in a series circuit Other manufacturers AC sensors AC coils wired for 220 V operation are typically wired in parallel and must be rewired in series 7 Verify the sensor is in good working condition Use the manufacturer s recommended test procedure...

Page 239: ...mitter Figure D 2 Wiring for Brooks Sensor Model 5000 and Rosemount 8750W A Brooks model 5000 B Rosemount 8750W Transmitter Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Table D 3 Brooks Model 5000 Sensor Wiring Connections Rosemount 8750W Brooks Sensors model 5000 1 1 2 2 3 3 17 17 18 18 19 19 Do not connect mains or line power to the magnetic flowtube sensor or ...

Page 240: ...g for Brooks Sensor Model 7400 and Rosemount 8750W A Brooks model 7400 B Rosemount 8750W Transmitter Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Table D 4 Brooks Model 7400 Sensor Wiring Connections Rosemount 8750W Brooks Sensors model 7400 1 Coils 2 Coils 3 3 17 Shield 18 Electrode 19 Electrode Do not connect mains or line power to the magnetic flowtube sensor ...

Page 241: ...ure D 4 Wiring for Endress and Hauser Sensors and Rosemount 8750W A Coils B Electrodes Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Endress andHauser sensors Rosemount 8750W Transmitter Table D 5 Endress and Hauser Sensor Wiring Connections Rosemount 8750W Endress and Hauser Sensors 1 41 2 42 3 14 17 4 18 5 19 7 Do not connect mains or line power to the magnetic ...

Page 242: ...r Sensor Model 10D1418 and Rosemount 8750W A Electrode connections B Coil connections Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Rosemount 8750W Transmitter Table D 6 Fischer and Porter Model 10D1418 Sensor Wiring Connections Rosemount 8750W Fischer and Porter Model 10D1418 Sensors 1 L1 2 L2 3 Chassis ground 17 3 18 1 19 2 Do not connect mains or line power to ...

Page 243: ...sor Model 10D1419 and Rosemount 8750W A Electrode connections B Coil connections Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Rosemount 8750W Transmitter Table D 7 Fischer and Porter Model 10D1419 Sensor Wiring Connections Rosemount 8750W Fischer and Porter Model 10D1419 Sensors 1 L1 2 L2 3 3 17 3 18 1 19 2 Do not connect mains or line power to the magnetic flowt...

Page 244: ... Model 10D1430 Remote and Rosemount 8750W A Electrode connections B Coil connections Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Rosemount 8750W Transmitter Table D 8 Fischer and Porter Model 10D1430 Remote Sensor Wiring Connections Rosemount 8750W Fischer and Porter Model 10D1430 Remote Sensors 1 L1 2 8 3 G 17 3 18 1 19 2 Do not connect mains or line power to t...

Page 245: ... A Electrode connections B Coil connections Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Rosemount 8750W Transmitter Table D 9 Fischer and Porter Model 10D1430 Integral Sensor Wiring Connections Rosemount 8750W Fischer and Porter Model 10D1430 Integral Sensors 1 L1 2 L2 3 G 17 3 18 1 19 2 Do not connect mains or line power to the magnetic flowtube sensor or to th...

Page 246: ...odel 10D1475 Integral and Rosemount 8750W A Electrode connections B Disconnect C Coil connections Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Rosemount 8750W Transmitter Table D 10 Fischer and Porter Model 10D1465 and 10D1475 Sensor Wiring Connections Rosemount 8750W Fischer and Porter Model 10D1465 and 10D1475 Sensors 1 MR 2 M1 3 3 17 3 18 1 19 2 Do not connect...

Page 247: ...orter Sensors and Rosemount 8750W A Electrodes B Coils C Chassis ground Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Fischer and Porter Sensors Rosemount 8750W Transmitter Table D 11 Fischer and Porter Generic Sensor Wiring Connections Rosemount 8750W Fischer and Porter Sensors 1 M1 2 M2 3 Chassis ground 17 3 18 1 19 2 Do not connect mains or line power to the ma...

Page 248: ...800 Sensor Rosemount 8750W Transmitter A Electrode connections B Coil connections C Outer shield D Inner shield E White lead F White shield G Black lead H Black shield Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Table D 12 Foxboro Series1800 Sensor Wiring Connections Rosemount 8750W Foxboro Series 1800 Sensors 1 L1 2 L2 3 Chassis ground 17 Any shield 18 Black 19...

Page 249: ...xboro Series 1800 Sensor Version 2 Rosemount 8750W Transmitter A Electrode connections B Coil connections C Chassis ground D Shield Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Table D 13 Foxboro Series 1800 Version 2 Sensor Wiring Connections Rosemount 8750W Foxboro Series 1800 Sensors 1 L1 2 L2 3 Chassis ground 17 Any shield 18 Black 19 White Do not connect mai...

Page 250: ...itter A Electrode connections B Coil connections C Outer shield D Inner shield E White lead F White shield H Black lead I Black shield J Any shield Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Table D 14 Foxboro Series 2800 Sensor Wiring Connections Rosemount 8750W Foxboro Series 2800 Sensors 1 L1 2 L2 3 Chassis ground 17 Any shield 18 Black 19 White Do not conne...

Page 251: ...Rosemount 8750W Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Foxboro Sensor Rosemount 8750W Transmitter A Electrodes B Coils C Any shield D Chassis ground Table D 15 Foxboro Generic Sensor Wiring Connections Rosemount 8750W Foxboro Sensors 1 L1 2 L2 3 Chassis ground 17 Any shield 18 Black 19 White Do not connect mains or line power to the magnetic flowtube sensor...

Page 252: ... Rosemount 8750W A Electrode connections B Coil connections Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Kent Veriflux VTC Sensor Rosemount 8750W Transmitter Table D 16 Kent Veriflux VTC Sensor Wiring Connections Rosemount 8750W Kent Veriflux VTC Sensors 1 2 2 1 3 SCR OUT 17 SCR OUT 18 SIG1 19 SIG2 Do not connect mains or line power to the magnetic flowtube senso...

Page 253: ... Generic Wiring for Kent Sensors and Rosemount 8750W A Electrodes B Coils Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Kent Sensors Rosemount 8750W Transmitter Table D 17 Kent Sensor Wiring Connections Rosemount 8750W Kent Sensors 1 1 2 2 3 SCR OUT 17 SCR OUT 18 SIG1 19 SIG2 Do not connect mains or line power to the magnetic flowtube sensor or to the transmitter ...

Page 254: ...ng for Krohne Sensors and Rosemount 8750W Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Krohne Sensors Rosemount 8750W Transmitter A Electrodes B Coils C Electrode shield D Coil shield Table D 18 Krohne Sensor Wiring Connections Rosemount 8750W Krohne Sensors 1 8 2 7 3 Coil shield 17 Electrode shield 18 2 19 3 Do not connect mains or line power to the magnetic flo...

Page 255: ...rs and Rosemount 8750W Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Taylor Series 1100 Sensor Rosemount 8750W Transmitter A Electrode connections B Coil connections Table D 19 Taylor Series 1100 Sensor Wiring Connections Rosemount 8750W Taylor Series 1100 Sensors 1 Black 2 White 3 Green 17 S1 and S2 18 E1 19 E2 Do not connect mains or line power to the magnetic f...

Page 256: ... for Taylor Sensors and Rosemount 8750W Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Taylor Sensors Rosemount 8750W Transmitter A Electrodes B Coils Table D 20 Taylor Sensor Wiring Connections Rosemount 8750W Taylor Sensors 1 Black 2 White 3 Green 17 S1 and S2 18 E1 19 E2 Do not connect mains or line power to the magnetic flowtube sensor or to the transmitter coi...

Page 257: ...iring for Yamatake Honeywell Sensors and Rosemount 8750W Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Yamatake Honeywell Sensors Rosemount 8750W Transmitter D Chassis ground E Electrodes F Coils Table D 21 Yamatake Honeywell Sensor Wiring Connections Rosemount 8750W Yamatake Honeywell Sensors 1 X 2 Y 3 Chassis ground 17 C 18 B 19 A Do not connect mains or line po...

Page 258: ...ric Wiring for Yokogawa Sensors and Rosemount 8750W Refer to Figure D 1 on page 225 for actual terminal block configuration drawing Yokogawa Sensors Rosemount 8750W Transmitter D Chassis ground E Electrodes F Coils Table D 22 Yokogawa Sensor Wiring Connections Rosemount 8750W Yokogawa sensors 1 EX1 2 EX2 3 Chassis ground 17 C 18 B 19 A Do not connect mains or line power to the magnetic flowtube se...

Page 259: ...tance of approximately 3 300 ohms Electrode terminals will have an open circuit Identify a chassis ground 1 Touch one probe of an ohmmeter to the sensor chassis 2 Touch the other probe to the each sensor terminal and the record the results for each terminal The chassis ground will have a resistance value of one ohm or less D 13 2 Wiring connections Connect the electrode terminals to Rosemount 8750...

Page 260: ...Implementing a Universal Transmitter March 2016 Reference Manual 00809 0300 4750 Rev CA 248 Implementing a Universal Transmitter ...

Page 261: ...18 222 Foxboro Series 1800 228 Generic Flowtube 239 Kent Flowtubes 233 Kent Veriflux VTC 232 Krohne Flowtubes 234 Taylor Series 1100 235 Yamatake Honeywell Flowtubes 237 Yokogawa Flowtubes 238 G Gaskets 13 Grounding Grounding Electrodes 18 Grounding Rings 18 Lining Protectors 18 I Installation mechanical considerations 5 Procedures 5 Safety Messages 3 L Lining Protectors Grounding 18 Local Operato...

Page 262: ...ions 187 process temperature limits 185 process wetted materials 187 service 185 upper range limit 185 vacuum limits 186 weight 188 Specifications and Reference Data Functional Specifications Output Signals 179 183 Output Testing 179 183 T Tag 32 Temperature Model 8705 8707 185 U Upper Range Value URV 33 W Weight Model 8705 8707 188 Wiring Diagrams Brooks Model 5000 219 Endress and Hauser Models 2...

Page 263: ......

Page 264: ... 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 APFlow Support Emerson com Middle East and Africa Regional Office Emerson Process Management Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 4 8865465 FlowTechnicalSupport Emerson com Linkedin com company Emerson Process Management Twitter com Rosemount_News Facebook com Rosemount Youtu...

Reviews: