7.3
Process noise profiles
7.3.1
1/f noise
This type of noise has higher amplitudes at lower frequencies, but generally degrades over
increasing frequencies. Potential sources of 1/f noise include chemical mixing and slurry
flow particles rubbing against the electrodes.
7.3.2
Spike noise
This type of noise generally results in a high amplitude signal at specific frequencies which
can vary depending on the source of the noise. Common sources of spike noise include
chemical injections directly upstream of the flowmeter, hydraulic pumps, and slurry flows
with low concentrations of particles in the stream. The particles bounce off of the electrode
generating a “spike” in the electrode signal. An example of this type of flow stream would
be a recycle flow in a paper mill.
7.3.3
White noise
This type of noise results in a high amplitude signal that is relatively constant over the
frequency range. Common sources of white noise include chemical reactions or mixing that
occurs as the fluid passes through the flowmeter and high concentration slurry flows where
the particulates are constantly passing over the electrode head. An example of this type of
flow stream would be a basis weight stream in a paper mill.
7.4
High process noise diagnostic
The transmitter continuously monitors signal amplitudes over a wide range of frequencies.
For the high process noise diagnostic, the transmitter specifically looks at the signal
amplitude at frequencies of 2.5 Hz, 7.5 Hz, 32.5 Hz, and 42.5 Hz. The transmitter uses the
values from 2.5 and 7.5 Hz and calculates an average noise level. This average is compared
to the amplitude of the signal at 5 Hz. If the signal amplitude is not 25 times greater than
the noise level, and the coil drive frequency is set at 5 Hz, the
high process noise diagnostic
will trip indicating that the flow signal may be compromised. The transmitter performs the
same analysis around the 37.5 Hz coil drive frequency using the 32.5 Hz and 42.5 Hz values
to establish a noise level.
Summary of Contents for Rosemount 8750W
Page 2: ......
Page 96: ...84 Reference Manual 00809 0300 4750 Rev CA Operation March 2016 Operation ...
Page 168: ...156 Reference Manual 00809 0300 4750 Rev CA Maintenance March 2016 Maintenance ...
Page 214: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 202 Wiring Diagrams ...
Page 218: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 206 Wiring Diagrams ...
Page 219: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 207 Wiring Diagrams ...
Page 220: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 208 Wiring Diagrams ...
Page 222: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 210 Wiring Diagrams ...
Page 223: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 211 Wiring Diagrams ...
Page 224: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 212 Wiring Diagrams ...
Page 225: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 213 Wiring Diagrams ...
Page 227: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 215 Wiring Diagrams ...
Page 228: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 216 Wiring Diagrams ...
Page 229: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 217 Wiring Diagrams ...
Page 263: ......