Product Certifications
Rev 1.6
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in
accordance with the appropriate local, national, and international standards,
codes, and practices. Review this document for any restrictions associated
with a safe installation.
•
Before connecting a Field Communicator in an explosive atmosphere,
ensure the instruments in the loop are installed in accordance with
intrinsically safe or non-incendive field wiring practices.
•
In an Explosion-proof/Flameproof installation, do not remove the
transmitter covers when power is applied to the unit.
WARNING
Conduit/cable entries
•
Unless marked, the conduit/cable entries in the transmitter housing use a
1/2–14 NPT thread form. Entries marked “M20” are M20 x 1.5 thread
form. On devices with multiple conduit entries, all entries will have the
same thread form. Only use plugs, adapters, glands, or conduit with a
compatible thread form when closing these entries.
•
When installing in a hazardous location, use only appropriately listed or Ex
certified plugs, adapters, or glands in cable/conduit entries.
8.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at
Emerson.com/Rosemount
.
8.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
8.3 Installing Equipment in North America
The US National Electrical Code
®
(NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area
September 2018
Quick Start Guide
Quick Start Guide
27
Summary of Contents for Rosemount 4088B MultiVariable
Page 3: ...September 2018 Quick Start Guide Quick Start Guide 3 ...
Page 36: ...8 11 EU Declaration of Conformity September 2018 Quick Start Guide Quick Start Guide 37 ...
Page 38: ...September 2018 Quick Start Guide Quick Start Guide 39 ...
Page 40: ...September 2018 Quick Start Guide Quick Start Guide 41 ...