classification, gas, and temperature class. This information is clearly defined in
the respective codes.
8.4 USA
E5 FM Explosionproof (XP), Dust-Ignitionproof(DIP)
Certificate
FM17US0146X
Standards
FM Class 3600 - 2011, FM 3610 - 2005, FM Class 3615 - 2005,
FM Class 3616 2011, FM 3810 - 2005, ANSI/NEMA 250 - 1991,
ANSI/IEC 60529 - 2004, ANSI/ISA 60079-0:2013, ANSI/ISA
60079-1:2015, ANSI/ISA 60079-26:2017
Markings
XP Class I, Division 1, Groups B, C, D (Ta = –50 to 85 °C); DIP
Class II and Class III, Division 1, Groups E, F, G (Ta = –50 to 85
°C); Class I Zone 0/1 AEx db IIC T5 (Ta = –50 to 80 °C); Enclosure
Type 4X/IP66/IP68; Conduit seal not required for division
installations
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between Class 1, Zone 0 (process connection)
and Class 1, Zone 1 (all other parts of the equipment). The model code
and datasheet are to be consulted for details of the diaphragm
material. Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance shall
be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Appropriate cable, glands, and plugs need to be suitable for a
temperature of 5 °C greater than the maximum specified temperature
for location where installed.
4. The applicable temperature class, ambient temperature range and
process temperature range of the equipment is T4 for –50 ≤ T
a
≤ 80 °C
with T process = –50 to 120 °C.
5. Non-standard paint options (paint options other than Rosemount
Blue) may cause risk from electrostatic discharge. Avoid installation
that could cause electrostatic build-up on painted surfaces, and only
clean the painted surfaces with a damp cloth.
6. Display glass shall be positioned in such a way as to minimize the risk
of mechanical impact.
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)
Certificate
FM17US0263X
Quick Start Guide
September 2018
28
Rosemount 4088B MultiVariable Transmitter Quick Start Guide
Summary of Contents for Rosemount 4088B MultiVariable
Page 3: ...September 2018 Quick Start Guide Quick Start Guide 3 ...
Page 36: ...8 11 EU Declaration of Conformity September 2018 Quick Start Guide Quick Start Guide 37 ...
Page 38: ...September 2018 Quick Start Guide Quick Start Guide 39 ...
Page 40: ...September 2018 Quick Start Guide Quick Start Guide 41 ...