Analog signal on alarm
The transmitter automatically and continuously performs self-diagnostic routines. If a
failure or a measurement error is detected, the analog signal will be driven offscale to alert
the user. High or low failure mode is user-configurable.
Table A-1: Signal on Alarm
Level
Custom levels
NAMUR NE43 (default)
Low
3.5 to 4.0 mA
3.5 mA (NAMUR ≤ 3.6 mA)
High
20.0 to 22.5 mA
21.5 mA (NAMUR ≥ 21.0 mA)
Analog saturation levels
The transmitter will continue to set a current that corresponds to the measurement until
reaching the associated saturation limit (and then freeze).
Table A-2: Saturation Levels
Level
Custom levels
NAMUR NE43 (default)
Low
3.5 to 4.0 mA
3.8 mA
High
20.0 to 22.5 mA
20.5 mA
A.2.5
IO-Link specifications
IO-Link revision
1.1
Transfer type
COM2 (38.4 kBaud)
SIO mode
Yes
IO-Link master port
Class A
Minimum cycle time
6 ms
Reference Manual
Specifications and reference data
00809-0200-4480
May 2021