7.2.5
Device memory failure – Restore default settings
Alarm classification
Device status
Failure
Class
Error
Possible cause
Configuration data has been corrupted, for example, due to a power loss during writing.
Recommended actions
1. Restore default settings, restart device, and reconfigure the device.
2. If the condition persists, replace the device.
Related information
Restore to factory settings
Perform a device reset
7.2.6
Simulation active – Check operational mode
Alarm classification
Device status
Functional check
Class
Warning
Possible cause
The device is in simulation mode and is not reporting actual information.
Recommended actions
1. If this behavior is not desired, stop simulation mode.
2. If the condition persists, restart the device.
Related information
Use the simulation mode
Perform a device reset
Service and troubleshooting
Reference Manual
May 2021
00809-0200-4480
42
Rosemount 1408A Level and Flow Transmitter