background image

2

PENBERTHY 

MODEL MGT-362 LEVEL MEASUREMENT TRANSMITTER

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

1.1 System description

The Model MGT-362 level transmitter is 
designed to be used in conjunction with a 
Multiview™ liquid level meter. It measures the 
liquid level in a process vessel by detecting 
the position of the float in the Multiview™ 
communicating chamber. The float's position is 
then relayed by the electronics via a 4 to 20 mA 
output signal.
Specifically, the Model MGT-362 is a loop 
powered level measurement transmitter. As 
the magnet located in the float closes a group 
of reed switches the divided resistance of the 
network changes. The electronics located in the 
transmitter monitor this change in resistance 
and alter the output current proportionally. 
As the float ascends, each reed switch 
encountered will provide a higher voltage 
output than the previous switch. Therefore, 
as the float rises the loop current increases.

2 SPECIFICATIONS/APPROVALS

2.1 Enclosure

Watertight (NEMA 4) and Explosion-proof 
(NEMA 7) cast aluminum housing NBR O-ring.

2.2 Transmitter

Input: 

 11 V DC minimum; 
30 V DC maximum

Output: 

 4 to 20 mA continuous

 

 22 mA maximum (failure 
indication)

Resolution: 

0.375" (10 mm)

Response time: 30 milliseconds
Operating
temperature:   -40°F to 160°F (-40°C to 71°C) 

transmitter

 

 -260°F to 257°F (-162°C to 125°C) 
sensing element

2.3 Approvals

CSA certified Exi d

Explosion-proof for:
Division 1,2;
Class I; Groups B, C, D;
Class II; Groups E, F, G;
Class III, Type 4
When installed in accordance with control 
drawing 18F51-009 (Figure 4)

CSA certified Exi a

Intrinsically safe for:
Division 1,2;
Class I; Groups A, B, C, D;
Class II; Groups E, F, G;
Class III, Type 4
When installed in accordance with control 
drawings:
• For transmitter - 18F52-009 (Figure 5)
•  For Model MGT-362R sensor - 18J54-009 

(Figure 6)

3 INSTALLATION

3.1 Unpacking

Upon receiving the Model MGT-362 level 
transmitter, check all components carefully 
for damage incurred in shipping. If damage 
is evident or suspected, do not attempt 
installation.
Notify the carrier immediately and request a 
damage inspection. Check each item against 
the packing list.

3.2 Mounting the transmitter (for side 
connected Multiview™)

1.  Measure the distance from the top of the 

indicator on the magnetic level meter to the 
top of the communicating chamber. Record 
this distance. If the mounting clamp does 
not clear the indicator:

2.  Loosen the clamps holding the indicator 

to the communicating chamber. The 
clamps that will be used to mount the 
Model MGT-362 must pass between the 
indicator housing and the communicating 
chamber.

3.  Mount the Model MGT-362 so the top of 

the sensor cap is below the bottom side 
connection and the bottom of the seal-off 
is above the upper side connection. For 
optimal installation, make the distance 
between your reference points on the 
Model MGT-362 sensor and the side 
connections the same. Use the clamps 
supplied to secure the sensor to the 
communicating chamber. The upper clamp 
should be above the upper side connection 
and the lower clamp should be below the 
bottom side connection. Never clamp 
directly on the sensing tube. If the indicator 
clamps were loosened:

4.  Adjust the position of the indicator so that 

the distance from the top of the housing to 
the top of the communicating chamber is 
the same as in Step 1. Tighten the clamps 
for the indicator.

FIGURE 1

MGT-362 Standard Mounting Orientation

Summary of Contents for PENBERTHY MGT-362

Page 1: ...n to the Penberthy Model MGT 362 level measurement transmitter The Model MGT 362 consists of a reed switch resistor network encased in a pipe sensor and an electronics assembly The electronics assembly is available in a watertight NEMA 4 and explosion proof NEMA 7 enclosure The Model MGT 362 is available in either integral or remote mount models The remote mount is required when the process temper...

Page 2: ...or Division 1 2 Class I Groups A B C D Class II Groups E F G Class III Type 4 When installed in accordance with control drawings For transmitter 18F52 009 Figure 5 For Model MGT 362R sensor 18J54 009 Figure 6 3 INSTALLATION 3 1 Unpacking Upon receiving the Model MGT 362 level transmitter check all components carefully for damage incurred in shipping If damage is evident or suspected do not attempt...

Page 3: ...ttach the positive lead from your loop power supply to TB2 and the negative lead to TB2 see Figure 2 3 The cable connecting the sensor and transmitter should not exceed 50 feet in length Beldon cable 85240 is recommended for connecting the sensor to the transmitter 4 SET UP 4 1 Calibration The Model MGT 362 is factory calibrated for the corresponding Multiview unit However if necessary the Model M...

Page 4: ...o that the millimeter reads 4mA 0 05mA See Figure 2 10 Raise the liquid level to the highest possible level For bench calibration place the float at the point on the sensing element corresponding to 100 level 11 Turn the SPAN potentiometer R15 clockwise so that the millimeter reads 20mA 0 05mA See Figure 2 12 Lower the float or calibration magnet to the 75 50 and 25 level Verify that the output go...

Page 5: ...you are having difficulty with your Penberthy Model MGT 362 transmitter contact your local Penberthy distributor You may also contact the factory direct at 956 430 2500 and ask for an applications engineer So that we may assist you more effectively please have as much of the following information available as possible when you call Model Name of the company from whom you purchased your transmitter...

Page 6: ... path seal off shall be installed within 18 in of enclosure OR REMOTE MOUNT Hazardous area Non hazardous area Field wiring A flame path seal off shall be installed within 18 in of enclosure If less than 36 seal off shall be installed half way in between enclosures NOTES 1 Case temperature can not exceed 100 C 212 F 2 Wiring to be in accordance with national electrical code NEC pertinent parts of t...

Page 7: ...EGRAL MOUNT REMOTE MOUNT NOTES 1 Equipment supplying intrinsic system must not produce more than 250 V DC or 250 V rms 2 Nominal power supply voltage 25 5 V DC 3 Use only one single or dual channel barrier per transmitter circuit 4 Loop wire distance not to exceed 1500 ft using C leads 60 pF FT L leads 0 20 µH FT For CSA use CSA certified safety barriers use diode return 1 2 s only MANUFACTURER MO...

Page 8: ...r maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user Penberthy is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co All other marks ...

Reviews: