background image

3

PENBERTHY 

MODEL MGT-362 LEVEL MEASUREMENT TRANSMITTER

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

3.3 Mounting the transmitter (for end 
connected Multiview™)

1.  Measure the distance from the top of the 

indicator on the magnetic level meter to the 
top of the communicating chamber. Record 
this distance. If the mounting clamp does 
not clear the indicator:

2.  Loosen the clamps holding the indicator 

to the communicating chamber. The 
clamps that will be used to mount the 
Model MGT-362 must pass between the 
indicator housing and the communicating 
chamber.

3.  Mount the Model MGT-362 so the bottom 

of the seal-off is four inches above the top 
of the indicator. Use the clamps supplied 
to secure the sensor to the communicating 
chamber. Never clamp directly on the 
sensing tube. If the indicator clamps were 
loosened:

4.  Adjust the position of the indicator so that 

the distance from the top of the housing to 
the top of the communicating chamber is 
the same as in Step 1. Tighten the clamps 
for the indicator.

3.4 Installation

1.  If you are using conduit for the transmitter 

wiring use a conduit seal with a drain or 
a drip-loop to prevent condensate from 
entering the housing. Condensate can cause 
electrical shorts.

The transmitter housing has a ½" NPTF 
connection for the wiring conduit.

3.5 Wiring the transmitter (integral mounted 
units)

The sensor is pre-wired to the electronics 
assembly at the factory. All that is necessary is 
to connect your power supply.
1.  Connect the positive (+) lead from your loop 

power supply to TB2 (+) and the negative 
(-) lead to TB2 (-). (See Figure 2)

3.6 Wiring the transmitter (remote mounted 
units)

1.  Connect the red, green and black sensor 

wires to TB1. (See Figure 2)

2.  Attach the positive (+) lead from your loop 

power supply to TB2 (+) and the negative (-) 
lead to TB2 (-). (see Figure 2)

3.  The cable connecting the sensor and 

transmitter should not exceed 50 feet 
in length. Beldon cable #85240 is 
recommended for connecting the sensor to 
the transmitter.

4 SET-UP

4.1 Calibration

The Model MGT-362 is factory calibrated for 
the corresponding Multiview™ unit. However, 
if necessary the Model MGT-362 may be bench 
calibrated using the float or the calibration 
magnet (supplied). The following procedures 
require that power be applied to the unit with 
the cover removed.

WARNING

'Live' electrical circuits can ignite flammable 
gases. Be sure that the unit is properly grounded 
and that a suitable intrinsically safe barrier has 
been installed between the power supply and this 
unit. Failure to use a barrier can result in severe 
personal injury or property damage.

1.  Turn off power to the unit.
2.  Remove the housing cover and check to see 

that all wires have been properly installed.

3.  Disconnect the positive (+) loop wire from 

TB2. Connect this wire to the positive lead 
of a millimeter. Connect the negative lead of 
your millimeter to TB2 (+). (See Figure 2)

4.  Connect the positive (+) lead of a digital 

voltmeter to TP1 on the circuit board. Connect 
the negative (-) lead of a digital voltmeter to 
TP2 on the circuit board. (See Figure 2)

5.  Lower the liquid level in the vessel to the 

'zero' point. For bench calibration place the 
float or calibration magnet on the sensing 
element at the zero point.

6.  Turn the NULL, SPAN and OFFSET 

potentiometers (R16, R15, and R14) fully 
counter clockwise. (See Figure 2)

7.  Apply power to the unit. The millimeter 

should read 4 mA or less. If not, contact the 
factory. If the millimeter reads over 20 mA 
then the float or calibration magnet may not 
be in proximity to the sensor or the sensor 
wires are not properly connected at TB1. 
Reposition the float or inspect the wiring. 

Summary of Contents for PENBERTHY MGT-362

Page 1: ...n to the Penberthy Model MGT 362 level measurement transmitter The Model MGT 362 consists of a reed switch resistor network encased in a pipe sensor and an electronics assembly The electronics assembly is available in a watertight NEMA 4 and explosion proof NEMA 7 enclosure The Model MGT 362 is available in either integral or remote mount models The remote mount is required when the process temper...

Page 2: ...or Division 1 2 Class I Groups A B C D Class II Groups E F G Class III Type 4 When installed in accordance with control drawings For transmitter 18F52 009 Figure 5 For Model MGT 362R sensor 18J54 009 Figure 6 3 INSTALLATION 3 1 Unpacking Upon receiving the Model MGT 362 level transmitter check all components carefully for damage incurred in shipping If damage is evident or suspected do not attempt...

Page 3: ...ttach the positive lead from your loop power supply to TB2 and the negative lead to TB2 see Figure 2 3 The cable connecting the sensor and transmitter should not exceed 50 feet in length Beldon cable 85240 is recommended for connecting the sensor to the transmitter 4 SET UP 4 1 Calibration The Model MGT 362 is factory calibrated for the corresponding Multiview unit However if necessary the Model M...

Page 4: ...o that the millimeter reads 4mA 0 05mA See Figure 2 10 Raise the liquid level to the highest possible level For bench calibration place the float at the point on the sensing element corresponding to 100 level 11 Turn the SPAN potentiometer R15 clockwise so that the millimeter reads 20mA 0 05mA See Figure 2 12 Lower the float or calibration magnet to the 75 50 and 25 level Verify that the output go...

Page 5: ...you are having difficulty with your Penberthy Model MGT 362 transmitter contact your local Penberthy distributor You may also contact the factory direct at 956 430 2500 and ask for an applications engineer So that we may assist you more effectively please have as much of the following information available as possible when you call Model Name of the company from whom you purchased your transmitter...

Page 6: ... path seal off shall be installed within 18 in of enclosure OR REMOTE MOUNT Hazardous area Non hazardous area Field wiring A flame path seal off shall be installed within 18 in of enclosure If less than 36 seal off shall be installed half way in between enclosures NOTES 1 Case temperature can not exceed 100 C 212 F 2 Wiring to be in accordance with national electrical code NEC pertinent parts of t...

Page 7: ...EGRAL MOUNT REMOTE MOUNT NOTES 1 Equipment supplying intrinsic system must not produce more than 250 V DC or 250 V rms 2 Nominal power supply voltage 25 5 V DC 3 Use only one single or dual channel barrier per transmitter circuit 4 Loop wire distance not to exceed 1500 ft using C leads 60 pF FT L leads 0 20 µH FT For CSA use CSA certified safety barriers use diode return 1 2 s only MANUFACTURER MO...

Page 8: ...r maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user Penberthy is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co All other marks ...

Reviews: