11
PACSystems™ RSTi
-EP EPSCPE100 Standalone CPU Quick Start Guide
GFK-3012E
Hardware Installation
Initial Checks
Upon receiving your equipment, carefully inspect all shipping containers for damage.
If any part of the system is damaged, notify the carrier immediately. The damaged
shipping container should be saved as evidence for inspection by carrier.
As the consignee, it is your responsibility to register a claim with the carrier for
damage incurred during shipment. Emerson will fully cooperate with you, however,
should such action be necessary.
After unpacking the equipment, record all serial numbers. Serial numbers are
required if you should need to contact Customer Care during the warranty period. All
shipping containers and all packing material should be saved should it be necessary
to transport or ship any part of the system.
Verify that all components of the system have been received and that they agree with
your order. If the system received does not agree with your order, contact Customer
Care.
Installation and Mounting
As shipped, the CPE100 is intended for mounting on a DIN rail. An optional panel-
mount adaptor is also available (part number: ICMFAACC001-AA). If panel-mounting
is required, replace the DIN-rail adaptor with the panel-mount adaptor using the
screws supplied with that adaptor. Both adaptors attach to the rear of the CPE100
chassis using four M3 screws. Torque newly-installed screws to 5.3 in-Ibs (0.6 Nm)
when installing a new adaptor plate.
Thermal Requirements
When mounting the CPE100, allow a minimum clearance of 50 mm on the left & right
side of the unit and a minimum clearance of 100 mm on the top & bottom sides.