Fuse/
Circuit
Breaker
Amperage
Recm 90
°
C Wire Size
(1)
2/0 AWG 3/0 AWG 4/0 AWG
250
kcmil
300
kcmil
350
kcmil
400
kcmil
500
kcmil
Loop Length (feet)
(2)
225A
--
67
(3)
84
(3, 4)
100
(3, 4)
120
(4)
--
--
--
250A
--
--
76
(3)
90
(3, 4)
108
(3, 4)
126
(4)
--
--
300A
159
(4)
(2) Wires
--
--
--
90
(3)
105
(3, 4)
120
(3, 4)
--
400A
--
75
(3, 4)
(2) Wires
95
(3, 4)
(2) Wires
112
(3, 4)
(2) Wires
--
--
--
--
500A
--
--
76
(3)
(2) Wires
90
(3, 4)
(2) Wires
108
(3, 4)
(2) Wires
126
(4)
(2) Wires
--
--
600A
--
--
--
--
90
(3)
(2) Wires
105
(3, 4)
(2) Wires
157
(4)
(3) Wires
120
(3, 4)
(2) Wires
--
800A
--
--
--
84
(3)
(3) Wires
101
(3, 4)
(3) Wires
118
(3, 4)
(3) Wires
135
(3, 4)
(3) Wires
--
Recommended Crimp Lug
(5)
Lug
245347200
(per cable)
245347300
(per cable)
245347400
(per cable)
245347500
(per cable)
245347600
(per cable)
245347700
(per cable)
245347800
(per cable)
245347900
(per cable)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for
copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized,
follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
Table 28 (cont'd from previous page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various
TPH Fuses
,
TPL-B Fuses
,
GJ/218-Circuit Breakers
or