background image

System Application Guide 

SAG582127000

 

Spec. No. 582127000 (Model 721

NPBB

Issue AF, February 26, 2014 

 

Page 111 of 125 

 

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 

Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 

Wire Size and Lug Selection Tables for Load and Battery Connections 

to TPH Fuses, TPL-B Fuses, and GJ/218 Type Circuit Breakers or Battery Branch Circuits 

Fuse/ 

Circuit 

Breaker 

Amperage 

Recm 90

°

C Wire Size 

(1)

 

6 AWG 

4 AWG 

2 AWG 

1/0 AWG  2/0 AWG  3/0 AWG  4/0 AWG  250 kcmil 

Loop Length (feet) 

(2)

 

70A 

33 

(3)

 

53 

(3, 4)

 

85 

(3, 4)

 

135 

(4)

 

-- 

-- 

-- 

-- 

80A 

-- 

47 

(3, 4)

 

74 

(3, 4)

 

118 

(3, 4)

 

-- 

-- 

-- 

-- 

100A 

-- 

-- 

59 

(3, 4)

 

95 

(3, 4)

 

119 

(3, 4)

 

-- 

-- 

-- 

125A 

-- 

-- 

47 

(3)

 

76 

(3, 4)

 

95 

(3, 4)

 

120 

(4)

 

-- 

-- 

150A 

-- 

-- 

-- 

63 

(3, 4)

 

79 

(3, 4)

 

100 

(3, 4)

 

-- 

-- 

175A 

-- 

-- 

-- 

-- 

68 

(3, 4)

 

86 

(3, 4)

 

108 

(3, 4)

 

-- 

200A 

-- 

-- 

-- 

-- 

-- 

75 

(3, 4)

 

95 

(3, 4)

 

112 

(3, 4)

 

Recommended Crimp Lug 

(5)

 

Lug 

245349900 

245350000 

245348200 

245347100 

245347200 

245347300 

245347400 

245347500 

1

  Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved 

National Fire Protection Association's (NFPA) National Electrical Code (NEC).  Table 310.15 (B) (16) for 

copper wire at 90°C conductor temperature.  For operation in countries where the NEC is not recognized, 

follow applicable codes. 

2

  Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for 

the loop lengths shown.  Loop length is the sum of the lengths of the positive and negative leads. 

3

  Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature. 

4

  Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature. 

5

  Two-hole lug, 3/8" bolt clearance hole, 1" centers.  Refer to drawing 031110100 for lug crimping 

information. 

Table 28 (cont'd on next page) 

Recommended Wire Sizes and Lugs for Load and Battery Connections 

to Various 

TPH Fuses

TPL-B Fuses

, and 

GJ/218-Circuit Breakers 

or 

Battery Branch Circuits

 

Home

 

Summary of Contents for NetSure 721NPBB

Page 1: ...kers The distribution cabinet may be equipped with low voltage load disconnect LVLD low voltage battery disconnect LVBD and manual battery disconnect ACU Advanced Control Unit Plus Controller The controller provides power system control including optional low voltage battery disconnect LVBD and low voltage load disconnect LVLD control rectifier control including a charge control function converter...

Page 2: ... shelves each of which houses rectifier modules and optional DC DC converter modules Refer to Power Data Sheet PD588705300 for more information Rectifier Modules for use in Spec No 588705300 The system contains rectifier modules which provide load power battery float current and battery recharge current during normal operating conditions Refer to the Rectifier Instructions UM1R482000E3 for more in...

Page 3: ...ith 588705000 System Output Capacity System 4000A maximum Bay 2000A 48V DC maximum when used with 588705000 1500A 48V DC and 930A 24V DC maximum when used with 588705300 Distribution Panel 600A maximum 588705000 Shelf Ratings See PD588705000 1R483200 Rectifier Rating See UM1R483500E 1R483200E Rectifier Rating See UM1R483500E 1R483500E Rectifier Rating See UM1R483500E 1C400483500E Converter Rating ...

Page 4: ...Panels Return Bar Panel Other Options List 4 Distribution Only Bay Distribution Cabinet Bottom Rear Cover List 29 Distribution Cabinet Top Shield List 31 Module Mounting Shelf Field Expansion Kit List 90 Battery Shunt 800A List 91 Battery Shunt 2000A List 92 Battery Shunt 2500A List MB Manual Battery Disconnect See Also System Overview Table of Contents List Descriptions Accessory Descriptions Spe...

Page 5: ...Panels Return Bar Panel Other Options List 4 Distribution Only Bay Distribution Cabinet Bottom Rear Cover List 29 Distribution Cabinet Top Shield List 35 Module Mounting Shelf Field Expansion Kit List 90 Battery Shunt 800A List 91 Battery Shunt 2000A List 92 Battery Shunt 2500A List MB Manual Battery Disconnect See Also System Overview Table of Contents List Descriptions Accessory Descriptions Spe...

Page 6: ...stribution Panels Return Bar Panel Other Options List 4 Distribution Only Bay Distribution Cabinet Bottom Rear Cover List 29 Distribution Cabinet Top Shield List 33 Module Mounting Shelf Field Expansion Kit List 90 Battery Shunt 800A List 91 Battery Shunt 2000A List 92 Battery Shunt 2500A List MB Manual Battery Disconnect Optional DC DC Converter Module 1C48241500 See Also System Overview Table of...

Page 7: ...ur Row Distribution Cabinet 20 List 29 Top Shield for Distribution Cabinet 20 List 30 Module Mounting Shelf Interface Components for Spec No 58870500021 58870500022 58870500031 58870500032 20 List 31 Module Mounting Shelf Field Expansion Kit for Spec No 58870500022 58870500031 58870500032 21 List 32 Module Mounting Shelf Interface Components for Spec No 588705300 22 List 33 Module Mounting Shelf F...

Page 8: ... TLS Circuit Breaker Fuse Positions with Return Busbar 39 List DD 48V 24V Distribution Panel 5 48V Bullet TPS TLS Circuit Breaker Fuse Positions with Return Busbar and 16 24V Bullet TPS TLS Circuit Breaker Fuse Positions with Return Busbar 40 Battery Disconnect Distribution Panels 41 List BA Battery Disconnect Distribution Panel with Return Busbar and List BB Battery Disconnect Distribution Panel ...

Page 9: ... Circuit Breaker P N 522786 63 Lug Adapter Busbar Kit for 125A 150A and 200A Bullet Nose Type Circuit Breaker P N 534449 63 Busbar for 250A Bullet Nose Type Circuit Breaker P N 514717 63 Lug Adapter Busbar Kit for 250A Bullet Nose Type Circuit Breaker P N 514714 64 Lug Hardware Kits 64 1 4 20 Hardware Kit P N 541084 64 3 8 16 Hardware Kit P N 548184 64 3 8 16 Hardware Kit P N 548185 64 Battery Bus...

Page 10: ...ten permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited 1 2 Input Ratings 113 1 3 Environmental Ratings 113 1 4 Compliance Information 114 1 5 IB2 and EIB ACU Interface Board Ratings 114 PHYSICAL SIZE INFORMATION 115 Overall Dimensions 115 List 21 One Row Distribution Cabinet 116 List 22 Two Row Distribution Cabinet 117 List 23 Three Row Distribution Cabinet...

Page 11: ...anels battery disconnect panels and or return bar panel as required per Single Voltage Distribution Panel Dual Voltage Distribution Panel Battery Disconnect Distribution Panel and Return Bar Panel under LIST DESCRIPTIONS b Order battery disconnect contactors and low voltage disconnect options as required per Battery Disconnect Contactors and Low Voltage Disconnect Options under LIST DESCRIPTIONS c...

Page 12: ...uired c Order Optional Battery Tray Front Battery Cover Kits as required List 2 1 st Supplemental Bay Common Equipment Power and Distribution or Distribution Only Located In Line with Main Bay Features Provides common equipment for one bussed power and distribution or distribution only bay rated for up to 2000 amperes of distribution Includes interbay power busbars and communications cable Mounts ...

Page 13: ... per List 40 41 or 42 if module mounting shelf 58870500021 ordered or order module mounting shelves with AC line cords or terminal blocks 58870500022 58870500031 58870500032 b Order rectifier modules as required P N 1R483500E 1R483200E or 1R483200 c Order a module mounting position blank cover panel P N 21140440 for each empty module mounting position in the system as desired 4 588705000 Converter...

Page 14: ...isconnect List LL or List LB is to be included the Main Bay List 1 of the system must also have low voltage disconnect List LL or List LB Ordering Notes 1 Order a relay rack or shipping brackets per Relay Racks and Shipping Brackets under ACCESSORY DESCRIPTIONS If required order relay rack transition plates per Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries under ACCESS...

Page 15: ...helf s per PD588705300 a Order the front access AC Input Termination Assembly per List 40 41 or 42 or order module mounting shelves with AC input cable assemblies see PD588705300 b Order rectifier modules as required P N 1R482000E3 c Order optional converter interface components per List 60 d Order optional DC DC converter modules as required P N 1C48241500 6 Order battery trays as required per Li...

Page 16: ...SCRIPTIONS c Order fuses and or circuit breakers as required per Distribution Devices under ACCESSORY DESCRIPTIONS d Order input and load distribution lugs lug adapters and lug hardware kits as required per Wiring Notes under ACCESSORY DESCRIPTIONS e Order a distribution cabinet top shield as required per List 29 f If distribution only order a bottom rear distribution cabinet cover per List 4 g Or...

Page 17: ...n shelves Restrictions When the system is equipped with a List 40 41 42 45 46 or 47 front access Input Termination Assembly refer to the restrictions under these list descriptions Will not accept List 60 converter interface components Will not accept dual voltage distribution panels Order maximum of one 1 List 3 or List 6 per Power System Cannot be used when List 3 is ordered Order List 3 or List ...

Page 18: ...0041 58870500042 b Order converter modules as required P N 1C400483500E c Order a module mounting position blank cover panel P N 21140440 for each empty module mounting position in the system as desired 5 588705300 Rectifier Converter Option Order interface components for module mounting shelf s Spec No 588705300 as required per List 32 Order field expansion module mounting shelf s per List 33 Ord...

Page 19: ...oltage Distribution Panel Battery Disconnect Distribution Panel and Return Bar Panel under LIST DESCRIPTIONS 2 Order fuses and or circuit breakers as required per Distribution Devices under ACCESSORY DESCRIPTIONS 3 Order input and load distribution lugs lug adapters and lug hardware kits as required per Wiring Notes under ACCESSORY DESCRIPTIONS 4 Order battery contactor battery shunt and low volta...

Page 20: ...shield covers all wiring access openings in top of distribution cabinet Individual cutouts can be removed for wiring as required for specific installation Ordering Notes 1 Where closed top cover is required order one 1 List 29 for each List 21 22 23 and 24 ordered List 30 Module Mounting Shelf Interface Components for Spec No 58870500021 58870500022 58870500031 58870500032 Features Provides compon...

Page 21: ...00 4 Order a module mounting position blank cover panel P N 21140440 for each empty module mounting position in the system as desired List 31 Module Mounting Shelf Field Expansion Kit for Spec No 58870500022 58870500031 58870500032 Features Provides busbars and mounting hardware to tie the DC output busbars in a field installed module mounting shelf Spec No 58870500022 58870500031 58870500032 to t...

Page 22: ...41 can be equipped with either two 2 or four 4 mounting shelves see List 33 for expansion shelves Ordering Notes 1 Order one 1 List 32 per module mounting shelf s Spec No 588705300 to be installed in the bay with these interconnect components one to five and specify the number of rows in the distribution cabinet so correct busbars can be provided 2 Order module mounting shelf s as required per PD5...

Page 23: ...talled in the bay with these interconnect components one to five and specify the number of rows in the distribution cabinet so correct busbars can be provided 2 Order module mounting shelf s as required per PD588705000 choices are 58870500040 58870500041 58870500042 58870500040 required when List 45 46 or 47 ordered with the system 3 Order converter modules as required P N 1C400483500E 4 Order a m...

Page 24: ...t terminal blocks See PD588705000 or PD588705300 List 41 Front Access AC Input Termination Assembly 1 AC Feed per 2 Rectifiers Single Phase 2 or 4 Shelves Features Provides AC input terminal blocks for connection of single phase 208 240 volts AC input feeds for all rectifier positions in the bay One 1 AC input feed required per two 2 rectifier positions Refer to AC Input Connections to AC Input Te...

Page 25: ... to List 45 If a field expansion module mounting shelf is added to the system DC inputs MUST be wired directly to the shelf Ordering Notes 1 Order either List 45 46 or 47 for each bay or order module mounting shelves with DC input terminal blocks See PD588705000 List 46 Front Access DC Input Termination Assembly 1 DC Feed per 2 Converters 2 or 4 Shelves Features Provides DC input terminal blocks f...

Page 26: ...00 module mounting shelves Must be installed in main bay only Must be used in conjunction with a dual voltage bus distribution panel Ordering Notes 1 Order List 60 as required Quantity of List 60 must equal the quantity of module mounting shelf s Spec No 588705300 installed in the bay with a maximum of four 4 List 60 Note that if five 5 shelves are in the bay the quantity of List 60 is still four ...

Page 27: ... Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 91 Optional Battery Shunt 2000A Features Provides a 2000A battery shunt Restrictions For use with List 22 only Ordering Notes 1 Order as required List 92 Optional Battery Shunt 2500A Features Provides a 2500A battery shu...

Page 28: ...RIPTIONS section A single battery tray must mount at bottom of relay rack Multiple battery trays must mount starting at bottom of relay rack and working upward Factory spaces battery trays 6RU 7RU or 8RU apart as determined by battery selected If no battery selected factory spaces battery trays 8RU apart Spacing can be increased above that required for the battery selected up to a maximum of 8RU C...

Page 29: ...king to the lowest capacity 125A 150A 175A and 200A circuit breakers occupy two mounting positions 225A and 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mounting position between it and any other overcurrent protective device Maximum lug width 0 625 inches Ordering Notes 1 Specify row for panel location...

Page 30: ...ting of each landing point is 360A Restrictions Can be installed in any bus row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 375 inches For an 800A circuit breaker load must not exceed 600A Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 List AD To terminate load returns within the distribution cabinet order ...

Page 31: ...city Restrictions Can be installed in any row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 88 inches For an 800A fuse load must not exceed 600A Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 To terminate load returns within the distribution cabinet order List GA as required 4 Order fuses as required per Tabl...

Page 32: ...to the SM DU internal to the distribution cabinet Does NOT include a Return Busbar 600A Maximum Capacity Restrictions Can be installed in any row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 88 inches For an 800A fuse load must not exceed 600A Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 To terminate load ...

Page 33: ...sbar 600A Maximum Capacity Restrictions Can be installed in any row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 75 inches Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 To terminate load returns within the distribution cabinet order List GA as required 4 Order fuses as required per Table 15 Order replacemen...

Page 34: ...trimmed and connected to the SM DU internal to the distribution cabinet Does NOT include a Return Busbar 600A Maximum Capacity Restrictions Can be installed in any row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 75 inches Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 To terminate load returns within the di...

Page 35: ...rn Busbar 600A Maximum Capacity Restrictions Can be installed in any row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 50 inches Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 To terminate load returns within the distribution cabinet order List GA as required 4 Order fuses as required per Table 16 Order repla...

Page 36: ... are trimmed and connected to the SM DU internal to the distribution cabinet Does NOT include a Return Busbar 600A Maximum Capacity Restrictions Can be installed in any row 1 4 of a 1 2 3 or 4 row distribution cabinet Maximum lug width 1 50 inches Ordering Notes 1 Specify row for panel location s 2 Order low voltage load disconnect List LL per panel as required 3 To terminate load returns within t...

Page 37: ...n rows 1 to 2 of a 1 2 3 or 4 row distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A 175A and 200A circuit breakers occupy two mounting positions 225A and 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating of 10...

Page 38: ...a 1 2 3 or 4 row distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A 175A and 200A circuit breakers occupy two mounting positions 225A and 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating of 100A or greater SHA...

Page 39: ...a 1 2 3 or 4 row distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A 175A and 200A circuit breakers occupy two mounting positions 225A and 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating of 100A or greater SHA...

Page 40: ...a 1 2 3 or 4 row distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A 175A and 200A circuit breakers occupy two mounting positions 225A and 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating of 100A or greater SHA...

Page 41: ...ibution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A 175A and 200A circuit breakers occupy two mounting positions 225A and 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating of 100A or greater SHALL HAVE an empty mount...

Page 42: ...eturn Busbar List BD does not include a Return Busbar 600A Maximum Capacity Maximum current rating of each landing point is 360A Restrictions Cannot be used with List 21 Must be installed in top row only limit one battery disconnect panel per distribution cabinet Maximum lug width 1 375 inches For an 800A circuit breaker load must not exceed 600A Ordering Notes 1 Order circuit breakers and associa...

Page 43: ...Type Fuses Does NOT include Shunts Does NOT include a Return Busbar 1200A Maximum Capacity Restrictions Cannot be used with List 21 Must be installed in top row only limit one battery disconnect panel per distribution cabinet Maximum lug width 1 88 inches For an 800A fuse load must not exceed 600A Ordering Notes 1 Order fuses as required per Table 15 Order replacement alarm fuses 1 4A per Table 17...

Page 44: ...ng device If the system is equipped with an SM DU the leads are trimmed and connected to the SM DU internal to the distribution cabinet Does NOT include a Return Busbar 1200A Maximum Capacity Restrictions Cannot be used with List 21 Must be installed in top row only limit one battery disconnect panel per distribution cabinet Maximum lug width 1 88 inches For an 800A fuse load must not exceed 600A ...

Page 45: ...tions 70A to 400A TPH Type Fuses Does NOT include Shunts Does NOT include a Return Busbar 1200A Maximum Capacity Restrictions Cannot be used with List 21 Must be installed in top row only limit one battery disconnect panel per distribution cabinet Maximum lug width 1 75 inches Ordering Notes 1 Order fuses as required per Table 15 Order replacement alarm fuses 1 4A per Table 17 2 Order load lugs tw...

Page 46: ...onnection to monitoring device If the system is equipped with an SM DU the leads are trimmed and connected to the SM DU internal to the distribution cabinet Does NOT include a Return Busbar 1200A Maximum Capacity Restrictions Cannot be used with List 21 Must be installed in top row only limit one battery disconnect panel per distribution cabinet Maximum lug width 1 75 inches Ordering Notes 1 Order...

Page 47: ...nels when internal load returns are required 1200A Maximum Capacity Restrictions Cannot be used in a 1 row distribution cabinet Can be installed in any row 1 4 of a 2 3 or 4 row distribution cabinet Maximum lug width 1 38 inches Ordering Notes 1 Specify row for panel location s 2 To terminate load and or battery returns within the distribution cabinet order List GA as required 3 Order lug hardware...

Page 48: ...binet Restrictions Main bay only Must be used with List 90 Must be used with List LB MB or both For use with List 21 only Can only use LVLD or LVBD on List 21 not both Ordering Notes 1 Order as required List CB 1200A Battery Disconnect Contactor Features Provides a battery disconnect contactor which is mounted within the main bay distribution cabinet Restrictions Main bay only Must be used with Li...

Page 49: ...low voltage battery disconnect LVBD is required 2 Can be combined with manual battery disconnect List MB if required List LL Low Voltage Load Disconnect LVLD Features Adds low voltage load disconnect LVLD to a distribution panel Adds LVD Driver circuit card P N 540972 main bay 547702 supplemental bay or LVD Driver Lite circuit card P N 547873 main bay 547874 supplemental bay to a distribution cabi...

Page 50: ...r BD that are equipped with shunted breakers The SM DU is factory wired to the shunts 4 Order up to four 4 optional temperature probes for ambient and battery temperature monitoring as required The temperature probe s may also be used for the battery charge temperature compensation feature and BTRM Battery Thermal Runaway Management Refer to Optional Temperature Probes for additional information 5...

Page 51: ... controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases respectively Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained A temperature probe set to monitor battery temperature can also be used for the BTRM Battery Thermal Runawa...

Page 52: ...ade up to 8 SM Temp modules connecting up to sixty four 64 temperature probes The SM Temp Concentrator is connected at the end of the ACU CAN bus Via the CAN Bus the ACU reads each temperature probe from each SM Temp Concentrator Restrictions Requires ACU version 3 02 or later when SM Temp is connected into the ACU CAN bus Ordering Notes 1 Order SM Temp Temperature Concentrator P N 547490 as requi...

Page 53: ... 1R483200E Features Provides one 1 Model R48 3200e Spec No 1R483200E 3200 watt 48 volt rectifier module Refer to the Rectifier Instructions UM1R483500E for more information Restrictions For use in Spec No 58870500021 58870500022 58870500031 58870500032 rectifier module mounting shelf Ordering Notes 1 Order by P N 1R483200E as required Each Spec No 588705000 rectifier module mounting shelf holds up...

Page 54: ...00040 58870500041 58870500042 module mounting shelf Ordering Notes 1 Order by P N 1C400483500E as required Each Spec No 588705000 module mounting shelf holds up to six 6 converter modules DC DC Converter Module P N 1C48241500 Features Provides one 1 Model C48 24 1500 Spec No 1C48241500 1500 watt 48V to 24V converter module Refer to the Converter Instructions UM1C48241500 for more information Restr...

Page 55: ...ist 60 Converter Option 2 Order up to three 3 converter modules P N 1C48241500 per module mounting shelf Component Part Number Quantity Converter Jumper 556228 Order one 1 per rectifier converter shelf in the system up to a maximum of four 4 24V Busbar 555264 when there are five 5 rectifier converter shelves in the system 555730 when there are four 4 rectifier converter shelves in the system 55573...

Page 56: ...cks and shipping brackets listed in Table 2 Part Number Size Available Mounting Positions 1RU 1 3 4 Notes 509638 509639 Shipping Brackets 22RU 543159 21 625 H x 24 376 W x 15 D 11RU Seismic Notes 1 and 2 543151 25 656 H x 24 376 W x 15 D 13RU Seismic Notes 1 and 2 543152 27 406 H x 24 376 W x 15 D 14RU Seismic Notes 1 and 2 543153 36 156 H x 24 376 W x 15 D 19RU Seismic Notes 1 and 2 543154 39 656...

Page 57: ... relay rack P Ns 543151 543152 543153 543154 543155 or 543156 on top of GNB Absolyte IIP batteries Each kit consists of two transition plates with three hole patterns and hardware 3 8 to mount the plates to the above listed relay racks Customer must supply hardware to mount the transition plates to the battery Restrictions Used with relay rack P Ns 543151 543152 543153 543154 543155 or 543156 only...

Page 58: ...s 12TX105F 100 4 90 x 22 10 x 9 30 6 105 8 528234 528235 Enersys 12V100F 100 4 90 x 22 00 x 9 00 6 104 7 528234 528235 Enersys 12V155FS 122010 155 4 90 x 22 10 x 11 10 7 125 6 528234 528235 Enersys 12V170F 170 4 90 x 22 10 x 12 40 8 147 7 528234 528235 Enersys 12VF105F 107 4 90 x 22 10 x 9 30 6 101 4 528234 528235 Enersys 12VX100F 100 4 90 x 22 00 x 9 00 6 104 7 528234 528235 Enersys SBS 170F 170 ...

Page 59: ...rcuit breaker selected up to 100A and 1 0AWG cables for circuit breaker selected over 100A Ordering Notes 1 For each battery tray order one 1 circuit breaker from Table 4 2 For each double pole circuit breaker ordered order an optional circuit breaker guard P N 548014 if desired to block front access to circuit breaker handle 3 For each battery tray ordered order one 1 battery circuit breaker hous...

Page 60: ... Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Optional Battery Tray Front Battery Cover Kits Features Provides a front battery cover to the List 93 battery tray Restrictions For use in List 93 battery trays Ordering Notes 1 Order one 1 kit per tray from Table 6 as requir...

Page 61: ...nergy Systems North America Inc is strictly prohibited Crimp Lugs Standard Crimp Lug Tables Lead Size Part Number 14 10 AWG 245342300 8 AWG 245390200 6 AWG 245346700 4 AWG 245346800 2 AWG 245346900 Table 7 Crimp Lug Two Hole 1 4 Bolt Clearance Hole 5 8 Centers Lead Size Part Number 6 AWG 245349900 4 AWG 245350000 2 AWG 245348200 1 0 AWG 245347100 2 0 AWG 245347200 3 0 AWG 245347300 4 0 AWG 2453474...

Page 62: ...gether and provides a crimp type lug which allows distribution wiring up to 350 kcmil size maximum size of wire to be connected to a single position is 2 AWG Designed for use with 125A and larger bullet nose type circuit breakers or TPS TLS type fuses which require at least two mounting positions Restrictions If used with bullet nose type circuit breakers or TPS TLS type fuses smaller than 125A an...

Page 63: ...lt clearance holes on 1 centers Ordering Notes 1 Order one 1 Part No 522786 per 125A 150A and 200A bullet nose circuit breaker ordered as desired See also P Ns 520989 and 534449 in this section Lug Adapter Busbar Kit for 125A 150A and 200A Bullet Nose Type Circuit Breaker P N 534449 Features Includes one 1 busbar that mounts on the two lug landing positions of a 125A 150A or 200A bullet nose circu...

Page 64: ...clearance Holes on 1 centers All busbar and lug mounting hardware is included Ordering Notes 1 Order one 1 Part No 514714 per 250A bullet nose circuit breaker ordered as desired see also Busbar for 250A Bullet Nose Type Circuit Breaker P N 514717 for another option Lug Hardware Kits 1 4 20 Hardware Kit P N 541084 Features Lug hardware kit provides thirty two 32 sets of 1 4 20 hardware for bullet n...

Page 65: ...es 1 Order one 1 kit P N 554541 per bay as required Battery Landing Busbar Kit P N 553584 Features Provides a Battery Landing Busbar Kit that attaches to the distribution cabinet s battery busbars and hangs off the back of the cabinet Six 6 battery landing positions are provided per polarity 1 4 20 x 0 875 studs on 0 625 centers See Battery Input Illustrations on page 104 Restrictions For use with...

Page 66: ... A alarm type fuse which operates open to provide an alarm indication if the associated distribution fuse opens Restrictions For use in Lists AA AB BA BB DA DB DC and DD Load should not exceed 80 of device rating Install distribution devices from left to right starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating of 100A or greater SH...

Page 67: ...e written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home Toggle Handle Bullet Nose Circuit Breaker Bullet Nose Fuseholder Rocker Handle Bullet Nose Circuit Breaker Fuse Carrier Fuseholder Body TPS TLS Fuse Polarizing Keyway Matches Key on Bottom of Fuse Carrier Bullet Nose Fuseholder Assembly Exploded View Bullet Nose Fuseholder Assembly P N 117201...

Page 68: ...283 101607 70 1 1 102284 101608 75 1 1 102285 101609 80 1 1 121996 121995 90 1 1 138887 138888 100 1 2 102286 101610 125 2 3 516991 516838 150 2 3 516993 516839 175 2 3 144883 144884 200 2 3 121831 121832 225 3 4 144885 144886 250 3 4 121835 121836 See Table 27 for recommended load distribution wire sizes and lugs When ordering 125A 150A 175A 200A 225A or 250A circuit breakers associated crimp lug...

Page 69: ...67 142888 50 1 1 142868 142889 60 1 1 142869 142890 70 1 1 142870 142891 75 1 1 142871 142892 80 1 1 142872 142901 100 1 2 142873 142902 125 2 3 142874 142903 150 2 3 142875 142904 200 2 3 142876 142905 250 3 4 142877 142906 See Table 27 for recommended load distribution wire sizes and lugs When ordering 125A 150A 200A or 250A circuit breakers associated crimp lugs may be ordered from Table 9 When...

Page 70: ...Ampere Rating Part Number Bussmann P N Littelfuse P N 3 248230900 TPS 3 TLS003 5 248231000 TPS 5 TLS005 6 248231200 TPS 6 TLS006 10 248231500 TPS 10 TLS010 15 248231800 TPS 15 TLS015 20 248232100 TPS 20 TLS020 25 248232400 TPS 25 TLS025 30 248232700 TPS 30 TLS030 40 248233300 TPS 40 TLS040 50 248233900 TPS 50 TLS050 60 248234200 TPS 60 TLS060 70 248234500 TPS 70 TLS070 80 118413 TLS080 90 118414 T...

Page 71: ... 6 load distribution fuse positions 1 4A to 15A GMT alarm type fuses Single voltage distribution 48V or 24V Mounts in two 2 distribution positions of any bullet nose distribution panel Screw clamp type load and load return terminals provided Includes six 6 dummy fuses equipped with safety fuse covers Restrictions Can be used in a List AA AB DA DB DC and DD distribution panel only Occupies two 2 bu...

Page 72: ...tional Bullet Nose Type 6 Position GMT Distribution Fuse Block P N 550224 is available for additional load distribution Restrictions When used for power distribution load should not exceed 80 of device rating except 10 and 15 amp fuses for which load should not exceed 70 of device rating Ordering Notes 1 Order fuses as required per Table 13 Ampere Rating Part Number Fuse Color 18 100 GMT A 2486103...

Page 73: ...ical Trip 2 with Internal Shunt 25mV full rated load 3 Breaker Mounting Kit with Shunt 100 1 256621700 256621300 503787 123580 516184 513731 125 1 256621600 256621400 503787 123631 516187 513731 150 1 256621800 256622400 503787 123632 516185 513731 175 1 256621900 256622500 503787 123633 516186 513731 200 1 256622200 256622600 503787 123634 516188 513731 225 1 256622900 256622700 503787 123635 516...

Page 74: ...ission of Emerson Network Power Energy Systems North America Inc is strictly prohibited TPH Type Fuses Restrictions For use in Lists AE AF AG AH BE BF BG and BH Load should not exceed 80 of device rating Ordering Notes 1 Order fuses as required per Table 15 2 See Table 28 for recommended load distribution wire sizes and lugs Ampere Rating Part Number 70 119437 80 119438 100 119440 150 119581 200 1...

Page 75: ... Restrictions For use in Lists AJ and AK Load should not exceed 80 of device rating Ordering Notes 1 Order fuses as required per Table 16 2 See Table 28 for recommended load distribution wire sizes and lugs Ampere Rating Part Number 70 248251500 80 248252000 100 248252600 150 248253300 200 248254000 225 248254500 250 248255000 See Table 28 for recommended load distribution wire sizes and lugs Tabl...

Page 76: ...N 117201 FA Fuse Alarm 18 100 Bussmann GMT A 248610301 Safety Fuse Cover GMT X 248898700 TPL B Fuseholders FA Fuse Alarm 18 100 Bussmann GMT A 248610301 Safety Fuse Cover GMT X 248898700 Table 17 Replaceable Alarm Reference and Control Fuses Replacement Assemblies Ordering Notes 1 Refer to the following table Refer to the separate rectifier and converter descriptions in this section for their part...

Page 77: ...gy Systems North America Inc is strictly prohibited Wiring Illustrations and Notes Relay Rack Frame Grounding Requirements For relay rack grounding requirements refer to the current edition of the American National Standards Institute ANSI approved National Fire Protection Association s NPFA National Electrical Code NEC applicable local codes and your specific site requirements A customer s ground...

Page 78: ...roved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 15 B 16 for copper wire at 90 C conductor temperature For operation in countries where the NEC is not recognized follow applicable codes 4 Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system...

Page 79: ...peration in countries where the NEC is not recognized follow applicable codes 4 Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system neutral Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum gr...

Page 80: ...eration in countries where the NEC is not recognized follow applicable codes 4 Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system neutral Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum gro...

Page 81: ...Association s NFPA National Electrical Code NEC Table 310 15 B 16 for copper wire at 90 C conductor temperature For operation in countries where the NEC is not recognized follow applicable codes 3 Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system neutral Equipment grounding co...

Page 82: ...ration in countries where the NEC is not recognized follow applicable codes 4 Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system neutral Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum grou...

Page 83: ...r operation in countries where the NEC is not recognized follow applicable codes 4 Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system neutral Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum...

Page 84: ... 1 PCU 1 AC 2 AC 1 PCU 2 AC 2 AC 1 PCU 3 AC 2 AC 1 PCU 1 AC 2 AC 1 PCU 2 AC 2 AC 1 PCU 3 RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 1 RECTIFIER PCU 208 240VAC 50 60Hz SINGLE PHASE SHELF 3 SHELF 2 AC 2 AC 1 PCU 1 AC 2 AC 1 PCU 2 AC 2 AC 1 PCU 3 AC 2 AC 1 PCU 1 AC 2 AC 1 PCU 2 AC 2 AC 1 PCU 3 RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 1 RECTIFIER PCU 208 240VAC 50 60Hz SINGLE PHASE SHELF 5 SHELF 4 AC 2 AC...

Page 85: ...C 1 PCU 2 AC 2 AC 1 PCU 3 RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 2 RECTIFIERS PCU 208 240VAC 50 60Hz SINGLE PHASE SHELVES 1 AND 2 AC 2 AC 1 PCU 4 AC 2 AC 1 PCU 5 AC 2 AC 1 PCU 6 RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 2 RECTIFIERS PCU 208 240VAC 50 60Hz SINGLE PHASE SHELVES 1 AND 2 AC 2 AC 1 PCU 1 AC 2 AC 1 PCU 2 AC 2 AC 1 PCU 3 RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 2 RECTIFIERS PCU 208 240VAC ...

Page 86: ...0Hz THREE PHASE SHELF 1 PCUs 1 3 A B C RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 3 RECTIFIERS PCU 208 240VAC 50 60Hz THREE PHASE SHELF 3 PCUs 1 3 A B C SHELF 2 PCUs 1 3 A B C RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 3 RECTIFIERS PCU 208 240VAC 50 60Hz THREE PHASE SHELF 5 PCUs 1 3 A B C SHELF 4 PCUs 1 3 C B A RECTIFIER PCU AC INPUT FEEDS 1 FEED PER 3 RECTIFIERS PCU 208 240VAC 50 60Hz THREE PHASE SHELF...

Page 87: ...er wire at 90 C conductor temperature For operation in countries where the NEC is not recognized follow applicable codes 2 Equipment grounding conductors must be provided with the DC input conductors supplied to the shelf Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum grounding conductor is used refer to Tabl...

Page 88: ...6 for copper wire at 90 C conductor temperature For operation in countries where the NEC is not recognized follow applicable codes 2 Equipment grounding conductors must be provided with the DC input conductors supplied to the shelf Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum grounding conductor is used ref...

Page 89: ...be provided with the DC input conductors supplied to the shelf Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum grounding conductor is used refer to Table 250 122 for increased conductor size For operation in countries where the NEC is not recognized follow applicable codes 3 THHN 90 C Wire 4 Maximum over curre...

Page 90: ...View Right Side GND GND GND GND Converter Module Mounting Slots Shelf 1 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Shelf 2 Shelf 3 Shelf 4 Shelf 5 Conv 1 Conv 2 Conv 3 400VDC CONVERTER DC INPUT FEEDS 1 FEED PER 1 CONVERTER SHELF 1 Co...

Page 91: ... Right Side NOTE WIRING TO A FIELD INSTALLED SHELF IS DONE AT THE REAR OF THE SHELF GND GND GND GND DC Wireway Cover DC Wireway Cover DC Input Connector Cover Converter Module Mounting Slots Shelf 1 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Shelf 2 Shelf 3 Shelf 4 Conv 1 Co...

Page 92: ...ver DC Input Connector Cover 400VDC CONVERTER DC INPUT FEEDS 1 FEED PER 3 CONVERTERS SHELF 1 Conv 1 3 400VDC CONVERTER DC INPUT FEEDS 1 FEED PER 3 CONVERTERS SHELF 3 Conv 1 3 SHELF 2 Conv 1 3 Converter Module Mounting Slots Shelf 1 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 Conv 1 Conv 2 Conv 3 Conv 4 Conv 5 Conv 6 ...

Page 93: ...ves Refer to Power Data Sheet PD588705000 or PD588705300 External Alarm Reference Monitoring External Alarm Reference Monitoring and Control Wire Sizes Recommended wire size is 22 AWG for loop lengths up to 200 ft and 18 20 AWG for loop lengths over 200 ft External Alarm Reference Monitoring and Control Illustrations Optional SM DU and Shunt Interface Board 4 Row Cabinet Shown Others Similar Front...

Page 94: ...or not No Battery Pwr Battery Pwr External Internal J8 J10 1 2 3 7 8 9 J10 Main Bay Only Battery Monitoring External Internal see TB1 4 and TB1 5 for external monitoring points J5 CAN TP3 and TP4 Bay Load Shunt Monitoring TP1 and TP2 Bay Voltage Monitoring TB1 1 Battery Tray FA TB1 2 External Battery FA TB1 3 External System FA TB1 4 External Battery Monitoring TB1 5 External Battery Monitoring 1 ...

Page 95: ...e contacts between the C and NC terminals Not all I O points are available for customer connection some are used for factory system connections J3 J9 Wire Size Capacity 16 26 AWG Recommended Torque 2 2 in lbs MA4C5U31 IB2 DI1 DI1 DI2 DI2 DI3 DI3 J3 J4 J5 J6 J7 J8 J9 DI4 DI4 DI5 DI5 DI6 DI6 DI7 DI7 DI8 DI8 DO1_NC DO2_NC DO1_COM DO2_COM DO1_NO DO2_NO DO3_NC DO4_NC DO3_COM DO4_COM DO3_NO DO4_NO DO5_N...

Page 96: ...hibited Home Optional EIB ACU Extended Interface Board located on inside side panel of Main Bay MA455U41 EIB SH1 SH1 SH2 SH2 SH3 SH3 J5 J6 J7 J8 J9 DCV1 DCV2 DCV3 DCV4 DCV5 DCV6 DCV7 DO5_NC DCV8 DO5_COM DO1_NC DO2_NC DO1_COM DO2_COM DO1_NO DO2_NO DO3_NC DO4_NC DO3_COM DO4_COM DO3_NO DO4_NO J3 1 J3 2 J3 3 J4 1 J4 2 J4 3 2 4 3 1 J2 DO5_NO 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 S...

Page 97: ... 541127 SHUNT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J2 SHUNT25 SHUNT25 SHUNT24 SHUNT24 SHUNT23 SHUNT23 SHUNT22 SHUNT22 SHUNT21 SHUNT21 SHUNT20 SHUNT20 SHUNT19 SHUNT19 SHUNT18 SHUNT18 SHUNT17 SHUNT17 SHUNT16 SHUNT16 SHUNT15 SHUNT15 SHUNT14 SHUNT14 TB2 25A 25B 24A 24B 23A 23B 22A 22B 21A 21B 20A 20...

Page 98: ... Inc is strictly prohibited Home Optional LVD Driver Circuit Card LVD Inhibit Switch Momentary UP Middle Down Momentary UP Position Closes all LVD Contactors inhibit mode Middle Position OFF ACU DOES NOT control LVD s inhibit mode DOWN Position ON ACU controls LVD s LVD Inhibit Active Indicator Notes 1 Connects up to 4 LVLD and 1 LVBD contactors 2 Switch and indicator located on circuit card insta...

Page 99: ...VD Inhibit Active Indicator Momentary UP Middle Down Momentary UP Position Closes all LVD Contactors inhibit mode Middle Position OFF ACU DOES NOT control LVD s inhibit mode DOWN Position ON ACU controls LVD s J1 J3 J2 Notes 1 Connects up to 2 LVD contactors rated at 600A or less 2 Only one 1 contactor per level can be accommodated J2 and J3 are on Level 2 only one 1 of these connectors can be use...

Page 100: ...ower Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home Optional Manual Battery Disconnect Circuit Card Main Bay Only Momentary UP Middle Momentary Down Momentary UP Postion Closes Battery Disconnect Contactor Middle Position Normal Operation Momentary DOWN Postion...

Page 101: ...or available lug adapter busbars 514714 514717 522786 and 534449 Use Table 8 and Table 28 when using the lug adapters The separate return busbar if furnished provides 3 8 16 captive nuts for installation of customer provided two hole lugs that have 1 inch centers and 3 8 inch bolt clearance holes Customer must provide or order lug mounting bolts and hardware The separate return busbar if furnished...

Page 102: ...n Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Load Distribution Distribution Panels Illustrations Refer to the illustrations located under the Distribution Panel List descriptions in this document Load Distribution Wiring Optional Bullet Nose 6 Posi...

Page 103: ...lt clearance holes Customer must provide or order lug mounting bolts and hardware The separate return busbar if furnished are designed to accommodate the lugs listed in Table 8 Use Table 28 to select recommended load distribution wire sizes and lugs for various loop lengths per fuse circuit breaker ampere rating b When Distribution Panels Using GJ 218 Circuit Breakers TPH Fuses or TPL B Fuses are ...

Page 104: ...o Lists 21 through 24 Distribution Cabinets 4 Row Cabinet Shown Others Similar Battery Return Side Busbar Battery Return Side Busbar Battery Load Side Busbar Battery Load Side Busbar GND RTN 48V SUPPLY BATTERY AND BATTERY RETURN CONNECTIONS 7 landings per polarity 3 8 16 Captive Nuts on 1 Centers Customer must supply additional hardware Maximum Lug Width 1 88 inches unless otherwise noted Maximum ...

Page 105: ...ten permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited c Connections to Interbay Busbars P O List 2 and List 3 RECTIFIER AND RECTIFIER RETURN CONNECTIONS CAN ONLY BE USED FOR BATTERY CONNECTIONS IF THE SYSTEM DOES NOT CONTAIN A BATTERY SHUNT OR BATTERY DISCONNECT CONTACTOR 3 8 16 Captive Nuts on 1 Centers Customer must supply additional hardware Maximum Lug...

Page 106: ...en permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited d Connections to Optional Battery Busbar Extension Kit P N 554541 Installed in Lists 21 through 24 Distribution Cabinets Note See Battery Busbar Extension Kit P N 554541 under ACCESSORY DESCRIPTIONS for description Front View One Row Cabinet Shown Others Similar Battery Return Side Busbar Battery Load Si...

Page 107: ...ritten permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited e Connections to Optional Battery Landing Busbar Kit P N 553584 Installed in List 21 Distribution Cabinet Note See Battery Busbar Extension Kit P N 553584 under ACCESSORY DESCRIPTIONS for description Rear View GND RTN 48V SUPPLY Plastic Shield Up to Six 6 Battery Leads per polarity 1 4 20 x 0 875 Stu...

Page 108: ...Systems North America Inc is strictly prohibited f Connections to Optional Battery Landing Busbar Kit P N 555478 Installed in Lists 22 through 24 Distribution Cabinets Note See Battery Busbar Extension Kit P N 555478 under ACCESSORY DESCRIPTIONS for description 1 4 20 x 0 875 Studs on 0 625 Centers 16 Places Customer must supply additional hardware Two Row Cabinet Shown Others Similar Rear View GN...

Page 109: ...135 4 75A 31 3 50 3 4 79 3 4 126 4 80A 47 3 4 74 3 4 118 3 4 Recommended Crimp Lug 5 Lug 245342300 245342300 245342300 245390200 245346700 245346800 245346900 245393500 6 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 15 B 16 for copper wire at 90 C conductor tempera...

Page 110: ...al Fire Protection Association s NFPA National Electrical Code NEC Table 310 15 B 16 for copper wire at 90 C conductor temperature For operation in countries where the NEC is not recognized follow applicable codes 2 Recommended wire sizes are sufficient to restrict voltage drop to 1 0 volt or less at listed branch current for the loop lengths shown Loop length is the sum of the lengths of the posi...

Page 111: ...3 4 95 3 4 112 3 4 Recommended Crimp Lug 5 Lug 245349900 245350000 245348200 245347100 245347200 245347300 245347400 245347500 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 15 B 16 for copper wire at 90 C conductor temperature For operation in countries where the NE...

Page 112: ...mp Lug 5 Lug 245347200 per cable 245347300 per cable 245347400 per cable 245347500 per cable 245347600 per cable 245347700 per cable 245347800 per cable 245347900 per cable 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 15 B 16 for copper wire at 90 C conductor tempe...

Page 113: ...e located in a controlled environment with access to crafts persons only This product is intended for installation in network telecommunication facilities CO vault hut or other environmentally controlled electronic equipment enclosure This product is intended to be connected to the common bonding network in a network telecommunication facility CO vault hut or other environmentally controlled elect...

Page 114: ...for Communications Equipment 1 4 2 NEBS Compliance pending when equipped with C400 48 3500e Compliance verified by a Nationally Recognized Testing Laboratory NRTL per GR 1089 CORE and GR 63 CORE Contact Emerson Network Power for NEBS compliance reports Rectifier Modules In order to remain compliant during a fan failure condition the backup battery connection must be utilized to provide sufficient ...

Page 115: ...ary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited PHYSICAL SIZE INFORMATION Overall Dimensions Refer to PD588705000 for module mounting shelf dimensions Refer to PD588705300 for module mounting shelf dimensions Refer to Ta...

Page 116: ... Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 21 One Row Distribution Cabinet Top View 11 09 12 25 7U 9 00 20 09 24 75 typical Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Textured Gray Refer to PD588705000 for rectifier module mounting shelf dimensions Refer to P...

Page 117: ... of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home List 22 Two Row Distribution Cabinet Top View Refer to PD588705000 for rectifier module mounting shelf dimensions Refer to PD588705300 for rectifier converter module mounting shelf dimensions Left Side View Front View Right Side View 11 09 3 25 9 00 20 09 19 25 11U 24 75 typi...

Page 118: ...of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home List 23 Three Row Distribution Cabinet Top View Refer to PD588705000 for rectifier module mounting shelf dimensions Refer to PD588705300 for rectifier converter module mounting shelf dimensions Left Side View Front View Right Side View 11 09 9 00 20 09 26 25 15U 24 75 typical ...

Page 119: ... of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 24 Four Row Distribution Cabinet Top View Refer to PD588705000 for rectifier module mounting shelf dimensions Refer to PD588705300 for rectifier converter module mounting shelf dimensions Left Side View Front View Right Side View 11 09 9 00 20 09 33 25 19U 24 75 typical Notes...

Page 120: ...e or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 93 Battery Tray Front View Right Side View ISO View Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Textured Gray 3 Maximum trays available per rack is four 4 9 781 22 500 12 25 or 14 00 as ordered 12 25 or 14 00 as ordered 12 25 or 14 ...

Page 121: ...ibution Cabinets 58212700021 55 Distribution Cabinet 1 Row 58212700022 76 Distribution Cabinet 2 Rows 58212700023 98 Distribution Cabinet 3 Rows 58212700024 126 Distribution Cabinet 4 Rows Module Mounting Shelf 588705000 58870500021 17 Module Mounting Shelf 58870500040 17 Module Mounting Shelf 1R483500E 1R483200E 1R483200 7 Rectifier Module 1C400483500E 8 Converter Module Module Mounting Shelf 588...

Page 122: ...ect 582127000BA 16 Distribution Panel 582127000BB 12 Distribution Panel 582127000BC 10 Distribution Panel 582127000BD 8 Distribution Panel 582127000BE 17 Distribution Panel 582127000BF 20 Distribution Panel 582127000BG 20 Distribution Panel 582127000BH 25 Distribution Panel Battery Disconnect Contactors 582127000CA 7 600 Amp Battery Disconnect Contactor 582127000CB 6 1200 Amp Battery Disconnect Co...

Page 123: ...Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List Number or Part Number Net Weight lbs each Description 543152 36 Relay Rack 543153 42 Relay Rack 543154 44 Relay Rack 543155 46 Relay Rack 543156 51 Relay Rack 543157 63 Relay Rack 543161 103 Relay Rack 543162 113 Relay Ra...

Page 124: ...tions UM1R482000E3 Converter Instructions UM1C48241500 Main Schematic Diagrams SD582127000 System SD588705000 Module Mounting Shelf SD588705300 Module Mounting Shelf Main Wiring Diagrams T582127000 System T588705000 Module Mounting Shelf T588705300 Module Mounting Shelf Load and Battery 031110100 Lug Detail Drawings 031110200 031110300 BATTERY MANUFACTURER INFORMATION Some equipment described in t...

Page 125: ... part number added to battery table Battery busbar extension kit P N 554541 added 09 18 2012 John Jasko AD LLP217758 Replaced P N 541371 with P N 553584 and added reference to Central Office Ground to battery connections section 12 14 2012 Shanon Ravacio AE LLP218149 Added 588705300 R48 2000e3 and C48 24 1500 Added P N 556155 and P N 556154 Temp Probe Components Replaced P N 550265 with P N 555478...

Reviews: