4 Chapter 2 Installation Instruction
NetSure 211 C45 Embedded Power Supply System User Manual
Table 2-3 Load cable CSA selection
Load route rated
current
Max. output
current
Min. cable
CSA
Max. cable length (volt
drop: 0.5V, with min. CSA)
Max. cable CSA
Max. cable length (volt drop:
0.5V, with max. CSA)
20A
20A
2.5mm
2
3.1m
4mm
2
5m
AWG12
4.6m
AWG10
6.1m
25A
25A
2.5mm
2
2.5m
2.5mm
2
4m
AWG12
3.6m
AWG10
4.8m
Note:
1. The specs are applicable at ambient temperature of 25°C.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core
flame-retardant cable as battery cable
The CSA of the system earth cable should be the same as that of the largest power distribution cable and not less
than 1.5mm
2
. The earth terminal is one M5 bolt.
2. Cable specifications of NetSure 211 C45-S2 power supply system
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70°C temperature
durability. Select the AC cable Cross-Sectional Area (CSA) according to Table 2-4.
Table 2-4 AC cable CSA selection
Connector
AC cable CSA
AC input MCB
4mm
2
(AWG10) ~ 10mm
2
(AWG6)
The CSA of DC cable depends on the current flowing through the cable, the allowable voltage drop and load peak
current. The recommended load peak current is 1/2 to 2/3 of MCB or fuse capacity.
Select the battery cable CSA according to Table 2-5. Select the load cable CSA according to Table 2-6.
Table 2-5 Battery cable CSA selection
Battery MCB
rated current
Max. battery
current
Min. cable
CSA
Max. cable length (allowable
voltage drop: 0.5V)
Max. cable
CSA
Max. cable length (volt
drop: 0.5V, with max. CSA)
63A
60A
10mm
2
4.3m
16mm
2
6.9m
AWG6
5.6m
AWG4
8.9m
Note:
1. The specs are applicable at ambient temperature of 25°C.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core
flame-retardant cable as battery cable
Table 2-6 Load cable CSA selection
Load route rated
current
Max. output
current
Min. cable
CSA
Max. cable length (volt
drop: 0.5V, with min. CSA)
Max. cable CSA
Max. cable length (volt drop:
0.5V, with max. CSA)
20A
20A
2.5mm
2
3.1m
6mm
2
7.5m
AWG12
4.6m
AWG8
10.7m
10A
10A
1.5mm
2
3.7m
6mm
2
15.1m
AWG14
5.8m
AWG8
21.4m
Note:
1. The specs are applicable at ambient temperature of 25°C.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core
flame-retardant cable as battery cable
The CSA of the system earth cable should be the same as that of the largest power distribution cable and not less
than 1.5mm
2
. The earth terminal is one M5 bolt.