Chapter 3 Installation Testing 13
NetSure 211 C45 Embedded Power Supply System User Manual
System operation status check
There should be no alarms during normal system operation. The system operation status check can be conducted
through the monitoring module.
Check item
OK
Comments
The system model is correct (48V/SET)
The monitoring module should display the correct AC voltage
The difference between the voltage displayed by the monitoring module and the actual value should
be less than ±0.3V
The difference between the battery current displayed by the monitoring module and the actual value
should be less than 1%
Check the number of the rectifier through the monitoring module. The number should be consistent
with the actual number
Check the voltage, current, current limiting point of rectifiers through the monitoring module. They
should agree with the actual parameters
For the system configured with temperature sensor, the monitoring module should display the battery
ambient temperature. Hold the probe of the temperature sensor and watch the monitoring module,
which should display the change of temperature
3.4 Final Steps
Check item
OK
Comments
Make sure that materials irrelevant to the equipment have been all removed
Fill in the installation report and hand it over to the user
Fill in the parameter table on the cabinet door
If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the
repairing center for fault analysis.