2 Chapter 1 Overview
NetSure 211 C45 Embedded Power Supply System User Manual
The configuration of the system is listed in Table 1-1.
Table 1-1 Configuration of the system
Component
Configuration
NetSure 211 C45-S1
NetSure 211 C45-S2
Rectifier
Model: R48-1000
Standard configuration: 4 pieces
Monitoring module
Model: M522B, M523B or M221B
Standard configuration: 1 piece
AC power distribution
AC input mode:
L + N + PE/220V, no AC input MCB
AC input mode:
L + N + PE/220V, 1 × 40A/2P MCB
DC power distribution
8 load MCBs:
4 × 20A/1P, 4 × 25A/1P
4 load MCBs:
2 × 20A/1P, 2 × 10A/1P
Battery routes
2 battery MCBs:
2 × 63A/1P
1 battery MCB:
1 × 63A/1P
Others
Two digital input ports, two dry contact output
ports, two temperature sensor ports
One digital input port, two dry contact output
ports, two temperature sensor ports
The monitoring module is available in three different models. Their configurations are listed in Table 1-2.
Table 1-2 Configuration of the monitoring module
Models
Configuration
M522B
2DI + 2DO, LCD display, network port, RS232 port
M523B
2DI + 2DO, LCD display, RS232 port
M221B
2DI + 2DO, no LCD display, three LED indicators indicating operation status of the system, RS232 port
1.3 Features
The rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99.
The system has wide AC input voltage range: 90Vac ~ 290Vac.
The rectifier uses soft switching technology, raising the efficiency to 91%.
The rectifier has ultra-low radiation. With advanced EMC design, the rectifier meets international standards such
as CE, NEBS and YD/T983. Both the conducted and radiated interference reach Class B.
The rectifier safety design complies with UL, CE and NEBS standards.
The rectifier is of high power density.
The rectifier is hot pluggable. It takes less than 1min to replace a rectifier.
The rectifier has two over-voltage protection methods: hardware protection and software protection. The latter
one also has two optional modes: lock-out at the first over-voltage and lock-out at the second over-voltage.
The monitoring module has perfect battery management. The management functions include battery low voltage
disconnection (BLVD), temperature compensation, auto voltage regulation, stepless current limiting, battery
capacity calculation, on-line battery test, and so on.
The monitoring module can save up to 200 pieces of historical alarm records, and 10 sets of battery test data
records.
The monitoring module is of network design. With an RS232 port, Ethernet, dry contacts and other
communication ports provided, flexible networking is enabled to achieve remote monitoring and unattendance.
The system has complete fault protection and fault alarm functions.