NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[42]
Figure 27.
Bay-to-Bay Communications Cable Connections
Use standard Cat5 communications cables.
1. Remove terminating plug from bottom connector on the System Interface Circuit Card installed in the Main Bay
and place in bottom connector on the System Interface Circuit Card in the last bay.
2. Connect the bottom connector on the System Interface Circuit Card installed in the Main Bay
to the top connector on the System Interface Circuit Card installed in the 1st Supplemental Bay.
3. Connect the bottom connector on the System Interface Circuit Card installed in the 1st Supplemental Bay
to the top connector on the System Interface Circuit Card installed in the 2nd Supplemental Bay.
Main Bay
1st
Supplemental
Bay
2nd
Supplemental
Bay
Termination
Plug
System Interface
Card in Main Bay
System Interface Card
in 1st Supplemental Bay
System Interface Card
in 2nd Supplemental Bay
System Interface Card
in Last Bay
Front doors remove in
illustration for clarity only.