Table 2.
Programmable Relay Outputs – IB2
Programmable
Relay Output
IB2
Pin No.
Alarms Assigned to this Relay
(Default)
Alarms Assigned to this Relay
(Custom)
1
NO
J6-5
The relays may be preprogrammed
for specific functions. Refer to the
configuration drawing (C-drawing)
supplied with your system for your
system’s specific configuration.
COM
J6-3
NC
J6-1
2
NO
J6-6
COM
J6-4
NC
J6-2
3
NO
J7-5
COM
J7-3
NC
J7-1
4
NO
J7-6
COM
J7-4
NC
J7-2
5
NO
J8-5
COM
J8-3
NC
J8-1
6
NO
J8-6
COM
J8-4
NC
J8-2
7
NO
J9-5
COM
J9-3
NC
J9-1
8
NO
J9-6
COM
J9-4
NC
J9-2
Note:
The ACU+ relay assigned to “Critical Summary” alarm (relay 1 by default) will operate in the “Fail Safe Mode”.
“Fail Safe Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts between the C
and NO terminals, and closing the contacts between the C and NC terminals.
The ACU+ remaining 7 relays energize during an alarm condition, closing the contacts between the C and NO
terminals, and opening the contacts between the C and NC terminals.