NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[15]
Direct AC Input Connections to 588705000 List 32 Module Mounting Shelves
Refer to
Figure 12.
Nominal 208/240 Volts AC Input Connections (Three-Phase) to a 588705000 List 32 Module Mounting Shelf)
(ØA)
(ØB)
(ØC)
(ØA)
(ØB)
(ØC)
Holes for 3/4"
Conduit Fitting
(AC Input)
Holes for 3/4"
Conduit Fitting
(AC Input)
Rear View
Rear View
FRAME GROUND CONNECTION
ONE 10-32 X 3/4" STUD
AND HARDWARE.
Recommended torque: 23 in-lbs.
FRAME GROUND CONNECTION
ONE 10-32 X 3/4" STUD
AND HARDWARE.
Recommended torque: 23 in-lbs.
Rectifier Module (PCU) Mounting Slots
(front view)
Rect.
(PCU)
1
Rect.
(PCU)
2
Rect.
(PCU)
3
Rect.
(PCU)
4
Rect.
(PCU)
5
Rect.
(PCU)
6
AC IN
Feed 2
(Rectifier
Modules
4-6)
AC IN
Feed 1
(Rectifier
Modules
1-3)
1 (ØA)
2 (ØB)
3 (ØC)
1 (ØA)
2 (ØB)
3 (ØC)
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
CONNECTIONS WITHIN THE SHELF
Mounting
Position
Rect 1
Rect 2
Rect 3
Rect 4
Rect 5
Rect 6
TB1, Terminal
TB2, Terminal
RECTIFIER (PCU) AC INPUT FEEDS
1 FEED PER 3 RECTIFIERS (PCU)
208-240VAC, 50/60Hz, THREE PHASE
Wire Size Capacity: 6-14 AWG.
Recommended Torque: 18 in-lbs.
Wire Size Capacity: 6-14 AWG.
Recommended Torque: 18 in-lbs.