Appendix C: Sensor specifications
Table C-1 Millennium sensor specifications
* QPS Marking applies to MLP-A-SC1100, MLP-A-SC1100-SS, MLP-AR-SC1100, and MLP-AR-SC1100-SS controllers only.
Operating temperature range
-40 °F to 185 °F (-40 °C to 85 °C)
Weight
0.2 lb. (0.1 kg)
Enclosure material
Powder coated or anodized aluminum (optional stainless steel)
Range of detection
0 to 100% LEL of most hydrocarbons and hydrogen
Accuracy
±3% LEL up to 50%LEL, ±5% LEL above 50% LEL
Response time
<10 seconds to T50, < 30 seconds to T90
Linearity/repeatability
±3% LEL / ±2% LEL
Certification*
Class 1, Division 1, Groups B, C, and D T5 Type 3R
Ex d IIB+H2 T5 Gb
Performance certified to CSA C22.2 No. 152 when connected to Millennium Controller