Reference Manual
Installation
MAN-0076, Revision 09
June 2016
Installation
9
Sensor Terminals
Transmitter power terminals
Sensor wires
Transmitter sensor board terminal
designation
Transmitter terminal
designation
Function
White
+Vdc (from transmitter)
RST
Remote Reset
Red
SigA
+Vdc (10.5-32Vdc)
Power (+)
Blue
SigB
COM
Power (-)
Black
Com
4-20 (CH1)
Channel #1 current loop output
Green
Earth ground
ISO (CH1)
+Vdc isolated 4-20mA power,
channel #1
4-20 (CH2)
Current loop output channel #2
ISO (CH2)
+Vdc isolated 4-20mA power,
channel #2
Figure 2-7 Sensor wiring and terminal connections
2.4.11
Remote reset
If the alarm relays are configured for latching operation it may be desirable to reset latched alarms from
a remote location. In this case a normally open, momentary pushbutton switch may be connected
across terminals RST and COM.