LF-Series Flowmeters: Sensor/Transmitter Installation
55
I/O Wiring – DIN CIO Transmitters
I/
O
Wiring – DIN
CIO
Retu
rn
P
o
li
c
y
Sp
ec
ifi
c
ati
o
n
s
I/
O
Wir
ing – DIN AN
10.3
mA output wiring
The wiring diagrams in this section are examples of proper wiring for the LF-Series DIN CIO
transmitter’s primary and secondary mA outputs. The following options are shown:
•
Basic mA output wiring – Figure 10-2
•
HART/analog single-loop wiring – Figure 10-3
•
HART multidrop wiring – Figure 10-4
Figure 10-2
Basic mA output wiring
820
Ω
maximum
loop resistance
mA1 output
mA2 output
420
Ω
maximum loop
resistance
+
+
–
–
Summary of Contents for Micro Motion LF Series
Page 6: ...iv LF Series Flowmeters Sensor Transmitter Installation ...
Page 10: ...4 LF Series Flowmeters Sensor Transmitter Installation ...
Page 14: ...8 LF Series Flowmeters Sensor Transmitter Installation ...
Page 28: ...22 LF Series Flowmeters Sensor Transmitter Installation ...
Page 36: ...30 LF Series Flowmeters Sensor Transmitter Installation ...
Page 48: ...42 LF Series Flowmeters Sensor Transmitter Installation ...
Page 52: ...46 LF Series Flowmeters Sensor Transmitter Installation ...
Page 58: ...52 LF Series Flowmeters Sensor Transmitter Installation ...
Page 72: ...66 LF Series Flowmeters Sensor Transmitter Installation ...
Page 86: ...80 LF Series Flowmeters Sensor Transmitter Installation ...
Page 102: ...96 LF Series Flowmeters Sensor Transmitter Installation ...
Page 103: ......