LF-Series Flowmeters: Sensor/Transmitter Installation
I/O Wiring – DIN AN Transmitters
Figure 9-1
Basic mA output wiring
Figure 9-2
HART/analog single-loop wiring
820
Ω
maximum loop resistance
mA output
+
–
HART-compatible
host or controller
820
Ω
maximum loop resistance
For HART communications:
• 600
Ω
maximum loop resistance
• 250
Ω
minimum loop resistance
+
–