Service Menu Parameters
82
Figure 70 Set alarms parameters screen - Page 6
Figure 71 Set alarms parameters screen - Page 7
SET ALARMS (page 6 of 7)
PASSWORD (Actual Level 0)
????
DELAY
EN-DIS TYPE
CUSTOMER INPUT 1
2 ENABLE
ALM
CUSTOMER INPUT 2
2 ENABLE
ALM
CUSTOMER INPUT 3
2 ENABLE
ALM
CUSTOMER INPUT 4
2 ENABLE
ALM
CALL SERVICE
2 ENABLE
ALM
HIGH TEMPERATURE
2 ENABLE
ALM
LOSS OF AIR BLOWER 1
2 ENABLE
ALM
REHEAT LOCKOUT
2 ENABLE WRN
HUMIDIFIER LOCKOUT
2 ENABLE WRN
FC LOCKOUT
2 ENABLE WRN
COMPRESSOR LOCKOUT
2 ENABLE WRN
S262
S263
S264
S265
S266
S267
S268
S269
S270
S271
S272
S273
S274
UNIT 01
SET ALARMS (page 7 of 7)
PASSWORD (Actual Level 0)
????
DELAY
EN-DIS TYPE
COMP 1 SHORT CYCLE
0 ENABLE WRN
COMP 2 SHORT CYCLE
0 ENABLE WRN
NO POWER
0 ENABLE WRN
CONDENSER 1 FAILURE
5 ENABLE WRN
CONDENSER 2 FAILURE
5 ENABLE WRN
EC FAN FAULT
0 ENABLE
ALM
S275
S276
S277
S278
S279
S280
S281
S282
S283
S284
S285
S286
S287
UNIT 01