Installing a Liebert iCOM Unit-to-Unit Network
48
Wall-Mount Large Display
Only large displays can be used for remotely monitoring and controlling cooling units connected on
the same network. Each wall-mount large display requires 120V input power; Liebert provides an AC
adapter wall plug. A straight-through Ethernet cable must be connected between the network switch
and the P64 port on the back of the display. This will enable control and monitoring capabilities to
any cooling unit connected to the network.
Combining Large and Small Displays on a U2U Network
Setting up a network of cooling units equipped with large and small displays requires a network
switch. The controls are to be connected to the switch as described above.
Figure 30 Wiring a small display for stand-alone operation
182964
Page 1
Rev. 0
Small Graphics Display
On Unit Accent
Stand-Alone Unit
6-Wire Cable
P66 P67
CAN CAN
iCOM
Microprocessor and I/O Board
E1
E3
P4
P22
P38
P39
P53
P52
P54
P51
TB1
E2
E4
P43
Unit Electronics Compartment
P40
P8
P32
P34
P33
P35
P36
E5
P18 P65
P61
P63
P64
P66
P7
P13
P12
P1
1
P67
Summary of Contents for Liebert Challenger 3000