IC200CX EVO
user manual
26
Through the
CrEn
menu it is possible to disable the
operation of a single circuit from the keypad to allow
maintenance of the same or a "partialized" operation
of the unit.
Through the
COEn
menu it is possible to disable the
operation of a single compressor inside a circuit to
allow maintenance of the same or isolate it in case of
malfunction.
Note: during normal operation,
disabled circuits are signaled via the
b1dS or b2dS labels flashing on the
lower display.
Note: during normal operation,
disabled compressors are signaled
via the C1dS or C2dS labels flashing
on the lower display.
Enter the menu and press the key for 3
seconds corresponding to the label
Cr1E
or
Cr2E
(circuit 1 / circuit 2). Use the arrow keys to select the
diS
(disabled circuit operation) or
En
(enabled circuit
operation) label and press the key to confirm
the function and move to the next circuit (only the
loads relative to the circuit are disabled).
3 seconds
Enter the menu and press the key for 3
seconds corresponding to the
CO1E
or
CO2E
label
(compressor 1 / compressor 2). Use the arrow keys to
select the label
diS
(compressor operation disabled)
or
En
(compressor operation enabled) and press
the key to confirm the function and switch to
the next compressor.
3 seconds
8.2 Disableenable a circuit
8.3 Disableenable a single compressor