Chapter 2 Installation
2.1 Unpacking Inspection
1. Open the packing box of each module and take out the modules, visually examine the
modules for possible transit damage.
2. Check against the accessory lists (see tables 2-1 to 2-2) if the accessories of the power
module and battery module are present.
3. If the UPS arrives damaged, or if there is any missing accessory, please contact the
distributor immediately.
Table 2-1 Power module accessory list
Accessory
Quantity
Unit
Tower installation fittings
——
plastic support base
4 Pcs
Rack installation fittings
——
bracket
1 Pair
AC input cable
1
Pcs
Battery connection cable (as applicable)
1
Pcs
RS232 cable
1
Pcs
User manual
1
Pcs
Single UPS monitoring software CD
1
Pcs
Note:
1. The rated current of the AC input cable of GXT1000-RT, GXT1000L-RT and GXT2000-RT power modules is
10A. That of GXT2000L-RT, GXT3000-RT and GXT3000L-RT power modules is 16A.
2. Only long back-up time power modules are delivered with a battery connection cable--a 1.8m long cable with
OT terminals attached to one end and a connector attached to the other, which is a 3-pin one for GXT1000L-RT
module and a 5-pin one for GXT2000-RT and GXT3000L-RT modules.
Table 2-2 Battery module accessory list
Accessory
Quantity
Unit
Tower installation fittings
——
plastic middle base
2 Pcs
Rack installation fittings
——
bracket
1 Pair
Battery cable with a 5-pin connector attached to each end
1
Pcs
2.2 Installation Notes
1. When locating the UPS, make sure there is no hazardous objects around the UPS, and that
the installation environment meets the specifications (see section 5.5).
2. The UPS is cooled with the aid of the internal fan fitted in the back of the power module. A
clearance of at least 300mm should be maintained behind the power module to facilitate
adequate ventilation and heat dissipation.
3. When adopting rack installation, the UPS must be installed in a standard 19-inch equipment
rack at least 400mm deep. The user should provide the installation fittings and screws in the
rack.