6
Chapter 1 System Outline
GIE 4820/3A/3.45KW Power Supply System User Manual
Table1-2 Function Illustrations of the Indicators on the Panel of the Module
Indication
Normal
State
Abnormal
State
Reasons of abnormity
RUN(Green light)
ON
OFF
No AC power input or input fuse damaged
ALM(Red light)
OFF
ON
Module failure and various protection
indications
FAN-ALM(Yellow
light)
OFF
ON
Fan failure indication
Technique Parameters
Input
Input voltage: 200V
AC
~
240V
AC
Frequency: 50/60Hz
Output
Output voltage: 53.5V
Rate output current: 15A
Weighted psophometric noise:
≤
2mV
Wide frequency noise voltage:
≤
50mV (3.4KHz
~
150KHz)
≤
20mV (150KHz
~
30MHz)
Peak-peak noise voltage:
≤
200mV (within 20MHz)
Load Regulation
≤±
0.5%
Line Regulation
≤±
0.1%
Efficiency
≥
90% (rated operation conditions)
Power Factor
≥
0.99 (rated operation conditions)
Cooling Method
Forced air cooling, with the built-in fan in the rectifier module
Mechanical
Parameters
Size: 132.3mm (Height)
×
65.5mm (Width)
×
280mm (Depth)
Weight: <3.0kg
Ambient Requirements
Operation temperature: -10
℃~
50
℃
Storage temperature: -40
℃~
70
℃
Relative humidity: 10%
~
90% (no condensing)
Atmosphere pressure: 86 kPa
~
106 kPa
No conductible dust and corrosive gas, no explosive danger.