14
FXMP25 User Guide
www.controltechniques.com
Issue Number: 3
3.2
Electrical terminals
Figure 3-4 Location, terminal size and torque setting of power and protective
ground terminals
3.3
Routine maintenance
The FXMP25 should be installed in a cool, clean, well ventilated location. Contact with
moisture and dust should be prevented.
Regular checks of the following should be carried out to ensure the installation reliability
is maximized:
FXMP25
M
STORED CHARGE
10 min
Mode /Reset
4.5mm
Power connections
Torque: 0.6Nm (0.44 Ib ft)
3.5mm
Control connections
Torque: 0.4Nm (0.29 Ib ft)
4.5mm
Ground connection
Torque: 0.6Nm (0.44 Ib ft)
Environment
Ambient temperature
Ensure the enclosure temperature remains at or below
maximum specified
Dust
Ensure the FXMP25 remains dust free
Moisture
Ensure the FXMP25 enclosure shows no signs of
condensation
Enclosure
Enclosure door filters
Ensure filters are not blocked and that air is free to flow
Electrical
Screw connections
Ensure all screw terminals remain tight
Crimp terminals
Ensure all crimp terminals remains tight – check for any
discoloration which could indicate overheating
Cables
Check all cables for signs of damage