FloBoss 103/104 Instruction Manual
Revised August-2017
Calibration
8-5
Figure 8-6. Set Midpoint 1
14.
If you are performing a
two-point
calibration, click
Done
.
Calibration for this input is complete.
15.
To calibrate midpoints, apply the desired pressure or temperature
and enter the applied value in the
Dead Weight / Tester Value
field. Note that you can calibrate the midpoints in
any
order.
16.
When the Live Reading is stable, click
Set Mid 1
to calibrate this
reading. The Set Midpoint 2 window displays.
Figure 8-7. Set Midpoint 2
17.
If you are performing a
three-point
calibration, click
Done
.
Calibration for this input is complete.
18.
To calibrate additional Midpoints, apply the desired pressure or
temperature and enter the applied value in the
Dead Weight /
Tester Value
field.
19.
When the Live Reading is stable, click
Set Mid 2
to calibrate this
reading. The Set Midpoint 3 window displays.
Figure 8-8. Set Midpoint 3