Power Connections
Revised August-2017
It is important to use good wiring practices when sizing, routing, and
connecting power wiring. Ensure that all wiring conforms to state, local,
and NEC codes. The CHG+ / CHG- terminal can accommodate up to 16
AWG wire
.
Warning
Use only solar panels approved for use with the FB100 in Class 1,
Division 2 locations.
These connections provide the input voltage and power for the battery
charging circuitry. The maximum voltage that can be applied to the
CHG+ / CHG- terminals is 28 volts dc.
3.7 Backing Up Configuration and Log Data
This procedure preserves the current flow computer configuration and
log data held in RAM. Perform this backup procedure
before
you
remove power from the FB100 for repairs, troubleshooting, removing or
adding components, or upgrades.
Caution
When installing equipment in a hazardous area, ensure that all
components are approved for use in such areas. Check the product
labels. Change components only in an area known to be non-hazardous.
Performing these procedures in a hazardous area could result in
personal injury or property damage.
To avoid circuit damage when working inside the unit, use appropriate
electrostatic discharge precautions such as wearing a grounded wrist
strap.
1.
Launch ROCLINK 800 software and connect to the FB100.
2.
Ensure that the configuration is saved in flash memory by
performing a
Save to Flash Memory
(
ROC
>
Flags
). This saves all
configuration settings, including the current states of the ROC Flags
and calibration values.
3.
Select
ROC
>
Collect Data
and select the All checkbox. Click
OK
.
This action saves event logs, alarm logs, report data, and history.
You can specify your own file name and path if desired.
4.
Select
File
>
Save
. The Save As dialog box appears.
5.
Type the desired
File name
for the backup file, or use the default.
6.
Click
Save
. The file is saved in the default directory C:/Program