remote location.  Cable shall operate 

smoothly,  over pulleys and/or through  

conduit.  Do not kink cable or run cable 

around sharp corners.  If installed in  

conduit, keep water out of conduit.   

Frozen water, dirt or dried mud in the  

conduit will render the remote  

 

 

release inoperable.  

 

Remote releases used on Type N550 

valves shall not:    
(a) be made from plastic or fiber rope;    
(b) have any kind of fusible link which    

   could melt and prevent the cable  

       

     from pulling the Type N550 latch.  

 

To provide a remote release, aircraft cable can be  

connected to the short looped cable on the valve and  

run to the remote release point over pulleys or through  

conduit.  Adjust the cable so that minimal pull is 

required to close the emergency valves.   

Type P164B Cable Installation  

 

To connect a Type P164B remote release assembly, which 

is supplied with 50 feet (15 m) of cable: 
  1.  Run the inner cable and housing assembly to the 

remote release point.  Leave enough slack on 

each end for a smooth, flowing path, without sharp 

bends in the cable, between the Type N550 latch 

block and remote release handle.    

A bobtail truck can provide enough pull on the hose 

connection to cause a break in the system.  That  

break must not occur between the Type N550 and the 

storage tank. 

Fusible Element Location  

 

A fusible element that will close the Type N550 shall be  

located within five feet of the hose connection.  If the  

Type N550 is placed within five feet of the hose  

 

connection, this requirement is met.  If not, an additional 

fusible element must be provided near the hose coupling 

which will activate a remote release.  

 

Remote Release Installation    

In all installations a remote release shall be connected  

to the latch on all emergency valves at the bulkhead.  

The remote release has to extend to a place where it  

can be easily reached to close the Type N550 valve(s) 

in the event that an emergency makes the valve(s) 

inaccessible.  The remote release shall shutdown all 

emergency valves when activated.  Remote release 

activation may be by cable or pneumatic hook-up. 

Cable Hook-Ups  

 

!

WARNING

Remote release cables shall be installed 

so that they will close the Type N550 

valve(s) when pulled from the farthest  

Figure 2.

  Typical Installation of Type N550 Using Remote Cable Release

T20874

INCHES

(mm

)

HOSE CONNECTION

BULKHEAD

12 (305) 

OR MORE

NAMEPLATE UP

EMERGENCY SHUTOFF

VALVE TYPE N550

REMOTE CABLE TO

SAFE LOCATION

FIXED PIPING

3

Type N550

Summary of Contents for Fisher Snappy Joe N550

Page 1: ...ntended for in line use on LP Gas or Anhydrous Ammonia NH3 service The valves may be installed on both ends of transfer hoses where the hose connects the bulk plant piping to the bobtail transport or tank car They provide a quick way of shutting off gas flow in the event of a hose rupture and meet the requirements for such service when correctly installed with a remote release and proper piping su...

Page 2: ...en a storage tank and the transfer hose connection at the truck or tank car loading unloading area They can be placed in a line used either for filling or withdrawing from the storage tank or both The valve shall be installed to shutoff flow from the tank towards the hose enabling the valve to control product loss in case of a hose break WARNING The Type N550 valves are spring closed aided by pres...

Page 3: ...de enough pull on the hose connection to cause a break in the system That break must not occur between the Type N550 and the storage tank Fusible Element Location A fusible element that will close the Type N550 shall be located within five feet of the hose connection If the Type N550 is placed within five feet of the hose connection this requirement is met If not an additional fusible element must...

Page 4: ... of the cable housing and cable housing nut fit into the conical end of the latch block Pulling the excess inner cable through the housing from the remote release end will hold the housing in the latch block 10 Mount the remote release cylinder assembly to a suitable support at the remote release location 7 16 inch 11 mm diameter mounting hole but do not tighten the mounting nut 11 At the remote r...

Page 5: ...e Type P327D see Figure 4 1 Close the Type N550 valve Handle is parallel to the pipe 2 Remove the long end of the external spring from under the latch block DO NOT REMOVE SPRING FROM HANDLE 3 Remove latch bolt s Older valves will have 2 bolts DISCARD CABLE LATCH BLOCK 4 Use a 5 32 inch 4 mm Allen head wrench to screw 1 4 inch 6 4 mm long bolt into bottom hole 5 Tighten until bolt head seats firmly...

Page 6: ... connection When the hose stretches more than the amount of slack left in the cable the tightening cable will pull the lever down and close the Type N550 valve CAUTION Possible hand and finger pinch point between closing Type N550 handle and latch block Handle closes quickly and with extreme force Keep hands and fingers away from handle as it closes 10 Test the remote release and Type N550 operati...

Page 7: ...epaired in the field However due to the special fire resistant seals and assembly techniques repairs should be done only by trained personnel If repair should become necessary contact your local LP Gas Equipment Distributor for information and assistance Only parts manufactured by Emerson Process Management Regulator Technologies Inc should be used for the repair of Fisher Type N550 Valves Be sure...

Page 8: ...eel T12851T0012 29 Washer Carbon steel 2 Required T1207524082 30 Packing Stack T12854T0012 31 Follower 174 Stainless steel T12841T0012 32 Retainer Steel T20674T0012 33 Bolt Stainless steel 2 Required T12499T0012 34 Bushing T12551T0012 35 Washer Nylon PA T12781T0012 36 Latch Block Aluminum T13800T0012 37 Spring 302 Stainless steel T13877T0012 38 Plunger Polyester T12846T0012 39 Cable T12849T0012 40...

Reviews: