DVC6000 Digital Valve Controllers
September 2013
7-14
Note
In the next step, be sure the feedback
arm outer surface remains flush with
the end of the travel sensor shaft.
11. While observing the resistance, tighten the screw
(key 80) to secure the feedback arm to the travel
sensor shaft. Be sure the resistance reading remains
at the calculated resistance determined in step 8,
$
100 ohms. Paint the screw to discourage tampering
with the connection.
12. Disconnect the multimeter from the travel sensor
connector.
13. For the DVC6030 only, connect the travel sensor
connector to the PWB as described in Replacing the
Module Base.
14. Travel sensor replacement is complete. Install the
digital valve controller on the actuator as described in
the Installation section.
Travel Sensor Adjustment with the Field
Communicator
The next two steps do not apply if you used a
multimeter to adjust the travel sensor. Perform these
steps only if you elected to adjust the travel sensor
using the Field Communicator.
15. For the DVC6030 only, connect the travel sensor
connector to the PWB as described in Replacing the
Module Base.
16. For both the DVC6030 and the DVC6035, perform
the appropriate Travel Sensor Adjust procedure in the
Calibration section.
Troubleshooting
If communication or output difficulties are experienced
with the instrument, refer to the troubleshooting chart
in table 7-3. Also see the DVC6000 Troubleshooting
Checklist on page 7-18.
Checking Voltage Available
WARNING
Personal injury or property damage
caused by fire or explosion may occur
if this test is attempted in an area
which contains a potentially explosive
atmosphere or has been classified as
hazardous.
To check the Voltage Available at the instrument,
perform the following:
1. Connect the equipment in figure 2-26 to the field
wiring in place of the FIELDVUE instrument.
2. Set the control system to provide maximum output
current.
3. Set the resistance of the 1 kilohm potentiometer
shown in figure 2-26 to zero.
4. Record the current shown on the milliammeter.
5. Adjust the resistance of the 1 kilohm potentiometer
until the voltage read on the voltmeter is 11.0 volts.
6. Record the current shown on the milliammeter.
7. If the current recorded in step 6 is the same as that
recorded in step 4 (
±
0.08 mA), the voltage available is
adequate.
8. If the voltage available is inadequate, refer to
Wiring Practices in the Installation section.
7
Summary of Contents for Fisher FIELDVUE DVC6000
Page 2: ......
Page 22: ...DVC6000 Digital Valve Controllers September 2013 1 12 1 ...
Page 82: ...DVC6000 Digital Valve Controllers September 2013 4 22 4 ...
Page 94: ...DVC6000 Digital Valve Controllers September 2013 5 12 5 ...
Page 139: ...Loop Schematics Nameplates September 2013 B 1 B B Appendix B Loop Schematics Nameplates B ...
Page 161: ......